For adjusting a selected parameter first press and hold key. Then, by using keys, adjustment can be made.
Parameter adjustment method
NOTE 1
If increment key is pressed and held 0.6 seconds, the value of the selected parameter changes rapidly. If waited enough, the value increases
100 at each step. After 1 second following the release of the key, initial condition is returned. The same procedure is valid for the decrement key.
S.Cod.
U.o.sc.
D.o.sc.
D.Ca.s.
S.Cod.
10/CA/
First press key. Then, by using keys, preset value can be
adjusted. If no key is pressed for 3 seconds Run mode is returned.
d.Cal. SeCU.
P.on.C.
R.tý.
o.D.TY.
o.E.TY.
D.tý.
D.oPt.
3/3
Preset
value
D.Pnt.
l.sCl.
Lo.Lý.
H.sCl.
Hý.Lý.
U.oPt.
1000
EDP141-E-05
SET
SET
ST
E
ST
E
SET
d.Pnt. = Decimal point.
Decimal point can be adjusted
between 1. and 3. digits.
See NOTE 1 for programming.
L.SCL. = Lower value of the scale.
It can be adjusted between -1999
and (H.SCL. -10) Output becomes
0V at the adjusted value.
See NOTE 1 for programming.
Lo.Li. = Lower limit for preset
value.It can be adjusted between
and Hi.Li.l.SCL.
See NOTE 1 for programming.
H.SCL. = Upper value of the scale
It can be adjusted between
(L.SCL. +10) and 8000.Output
becomes 10V at the adjusted value.
See NOTE 1 for programming.
Hi.Li. = Upper
Lo.li. and
limit for preset
value.It can be adjusted between
H.SCl.
See NOTE 1 for programming.
Programming mode
Run mode
If o.E.t.Y and o.d.t.Y parameters is adjusted to any value except dSAb parameter,
output can be controlled with and buttons.
P.on.C. = Control parameter when first energized.
ofF= When first energized, output is the voltage
that lower limit value is indicated.
Attention: If this parameter is selected, the set value
that was adjusted before is seen when set button is
pressed at first. In addition,if increasing or decreasing
that value is wanted the set value is equalized to
lower limit value and then adjustment can be done.
On= When first energized, output is the voltage
that the set value is indicated.
S.Str.= When first energized, output is increased
slowly from the voltage that lower limit value is
indicated to the voltage that set value is indicated
during r.ti.
See NOTE 1 for programming.
D.ti. = decreasing time for output.
It is adjusted between 1 and 250 seconds.
Output is decreased slowly to the lower limit value during
adjusted time.
See NOTE 1 for programming.
O.e.ty. = Adjusted type of the output to
with button.
preset value
dSAb. = Output cannot be adjusted to preset value with
button.
Enb. = Output can be adjusted to preset value with
button.
S.on. = Output is increased to voltage that set value is
displayed with button during r.ti. .
See NOTE 1 for programming.
O.d.ty. = Adjusted t
ype of the output to lower limit value
with button.
dSAb. = Output cannot be adjusted to lower limit value with
button.
Enb. = Output can be adjuested to lower limit value with
button.
S.oFF. = Output is increased to voltage that lower limit
value is displayed with button during d.ti. .
See NOTE 1 for programming.
R.ti. = increasing time for output.
It is adjusted between 1 and 250 seconds.
Output is incerased slowly to the set value during adjusted time.
See NOTE 1 for programming.
If key is pressed and held for 5
programming mode is entered
secondsIf key is pressed and held for 5
seconds
s.Cod. = Access code for safety menu.
This parameter should be 222.
See NOTE 1 for programming.
10.CA. = calibration for 0-10V output.
The device should be calibrated until
10.000V is obtained at the output.
Calibration procedure is as explained below.
When key is pressed, previous calibration
value is seen. While holding key, calibration
value should be adjusted until 10.000V is seen
at the output .
If key is released, calibration is exited. In
the mean time, the new calibration value is
saved in an EEPROM.
by using keys
ST
E
s.Cod. = Access code for safety menu.
This parameter should be 333.
See NOTE 1 for programming.
Uo.Sc. = U.oPt. menu protection level
parameter.
nonE = No menu is seen.
P. no = Menu is seen but can not be programmed.
P.yES.= Menu is seen and programming is possible.
See NOTE 1 for programming.
d.Ca.S. = d.CAL. menu protection level
parameter.
nonE = No menu is seen.
P. no = Menu is seen but can not be programmed.
P.yES.= Menu is seen and programming is possible.
See NOTE 1 for programming.
d.o.Sc. = d.oPt. Menu protection level
parameter.
nonE = No menu is seen.
P. no = Menu is seen but can not be programmed.
P.yES.= Menu is seen and programming is possible.
See NOTE 1 for programming.
P.on.C.
o.d.ty.
o.E.ty.
Lo.lý.
Lo.lý.
off
Dsab.
Dsab.
on
Enb.
R.ti.
R.ti.
Enb.
S.str.
S.off.
S.on.
PRESETPRESET
PRESETPRESET
Control can’t be done
with buttons.
Control can’t be done
with buttons. by pressing
the button
by pressing
the button
0V0V
PowerPower
OutOut
OutOut
OnOn
D.ti.
by pressing
the button
by pressing
the button
by pressing
the button
by pressing
the button
by pressing
the button
by pressing
the button
Entering from programming mode to run mode:
If no key is pressed within 20 seconds during programming mode data is stored automatically and the run
mode is entered. Alternatively the same function occurs by pressing key and holding for 5 seconds
SET
1000 1001 1002 1001
1000
SET
If no key is pressed
for 3 seconds
P.ý.d.t.
P.i/d/t/ = speed of preset value.increasing and decreasing
It is adjusted between 1 and 3. P.i.d.t. = 1, set value changes
one by one. P.i.d.t. = 2, set value changes 10 at each step.
P.i.d.t. = 3, set value changes 100 at each step.
See NOTE 1 for programming.