1. Record inside diameter (ID). Ensure the actual
pipe ID matches the pipe ID shown on the
match, refer to p59.
2. Record up/downstream straight-pipe
requirements based on Pipe ID and meter
style (insertion or inline). [refer to p. 19]
3. a. The Flow Direction Indicator must point in
b. The housing can be rotated for a better
view of the meter's display. Note that the
2 set screws must be loosened before the
housing will turn. [refer to p. 23]
4. Ensure correct probe depth setting. If using 1
½" size pipe, please see note on p. 22.
5. Open the housing. If needed, the orientation
of display can be rotated in 90° increments for
a better view.
[refer to p. 24 for more information]
6. Ensure power wiring [p. 32] and 4-20mA
wiring [p. 33 - p. 34] properly connected.
[refer to Wiring section p. 30 for more
information]
7. Ensure remote wiring is correct if remote
option ordered.
[refer to p. 40 - p. 41 for more
information]
8. Verify you have the proper output signal
wiring
[refer to p. 33 - p. 39 for more
information]
9.
10.
front panel of the display or by using the FT4X View™ software tool. Record the settings in the
spaces given for items A - F on the following page.
Use the table below as a guide while using the worksheet on the next page to record your notes.
NOTE! Please read the entire quick-start procedure before beginning installation.
ID OUTER
DIAMETER
FLOW
4X = INLINE
8X = INLINE
15X = INSERTION
PIPE ID MIN.
INDICATOR:
- POINT IN DIRECTION
OF FLOW
- LOOSEN SET SCREWS TO
ROTATE HOUSING ±90º, ±180º
- TIGHTEN SET SCREWS
WHEN DONE
FLOW
FLOW
0.73"
(18.5 mm)
L
C
F1 F2 F3 F4
ACCESS DISPLAY
BY UNSCREWING
COVER REMOVE SCREWS
ON DISPLAY TO
ROTATE DISPLAY
±180°
3 PULSE (+)
4 PULSE (-)
7 COMMON
6 Tx/Rx (-)
5 Tx/Rx (+)
2 SWITCH INPUT (-)
1 SWITCH INPUT (+)
POWER (+) 1
POWER (-) 2
4-20mA #1 (+) 3
4-20mA #1 (-) 4
4-20mA #2 (+) 5
4-20mA #2 (-) 6
TS2
TS1
F1
0.75A
TP1
TP2
+12 TO 28VDC
12 TO 28VDC RETURN
#4
#6
#3
#5
#2
Cable Shield
Electronics Enclosure
RED WHT
BLU YEL
Probe Sensor Wired By Fox
SENSOR
Remote Enclosure
#7
#8
#1
Splice
Green Wire
Shield Wire (insulate)
F1 F2 F3 F4
Initializing...
3 PULSE (+)
4 PULSE (-)
7 COMMON
6 Tx/Rx (-)
5 Tx/Rx (+)
2 SWITCH INPUT (-)
1 SWITCH INPUT (+)
POWER (+) 1
POWER (-) 2
4-20mA #1 (+) 3
4-20mA #1 (-) 4
4-20mA #2 (+) 5
4-20mA #2 (-) 6
TS2
TS1
F1
0.75A
TP1
TP2
FT4XCUSTOMER PLC OR DCS
+12 TO 28VDC
PULSE OR ALARM OUTPUT
12 TO 28VDC RETURN
+
-
2.4K OHM TYPICAL WITH 24VDC POWER
1.2K OHM TYPICAL WITH 24VDC POWER
4
Model FT4X
DISCLAIMER
4
INTRODUCTION
Quick Start Guide