3. BASIC REQUIREMENTS AND OPERATIONAL SAFETY
In the security scope, the meter meets the requirements of EN 61010-1
standard.
Remarks concerning the operator safety:
All operations concerning the meter installation and connections
should be carried out by qualified skilled personnel and national
regulations for the prevention of accidents must be observed.
Before connecting the meter to the power, one must check the
correctness of connections.
Do not connect the meter to the network through an
autotransformer.
Before the removal of the meter housing, one must disconnect its
supply and all measuring circuits.
The housing removal from the meter during the guarantee contract
causes its cancellation.
The meter fulfils requirements concerning the electromagnetic
compatibility in the industrial environment.
In the building installation should be a switch or a circuit breaker,
situated near the meter, easy accessible for the operator and
suitably marked.
4. MOUNTING
The meter is adapted to be mounted in a panel by means of holders
acc. to fig.1.
The meter housing is made of a self-extinguishing plastics. Meter dimen-
sions: 96 96 70.5 mm. One must prepare a hole of 91+0.5 91+0.5
mm in the panel which the thickness should not exceed 6 mm.
The meter must be introduced from the panel front with disconnected
supply voltage. At the rear side of the meter there are terminal strips
which enable the connection of wires up to 2.5 mm2.
After the insertion into the hole, fix the meter by means of two holders.