Acrel AIM-R100 User manual

166
AIM-R100 Residual Current Monitoring
Products
Installation and Operation Manual V1.3
Acrel Co., Ltd.

Declaration
Please read this manual carefully before using these products, in which the involved pictures,
logos, symbols, etc. are all reserved by the Acrel Co., Ltd. Personnel not inside the company shall not
publicly reprint all or part of the contents without written authorization.
Before using the product, please read the tips and precautions in this operation manual, and Acrel
does not take responsibility for personal injuries or economic losses caused by ignoring tips of this
manual;
The contents of the manual will be continuously updated and revised, thus the products functions
in this manual may inevitably have a slight discrepancy with the real objects during the continuous
upgrading process. Users should give first place to the purchased real products, and can search www.
acrel.cn to downloads or through sales channels to obtain the latest version of the manual.

Contens
1 Introduction ................................................................................................................................ 1
2 Functional characteristics ........................................................................................................... 2
2.1 Function characteristics of AIM-R100 ................................................................................ 2
2.2 Function characteristics of AID150 .................................................................................... 2
2.3 Function characteristics of ACLP10-24 .............................................................................. 2
2.4 Function characteristics of AKH-0.66/L-20........................................................................ 2
3 Reference standards ................................................................................................................... 3
4 Technical parameters .................................................................................................................. 3
4.1 Technical parameters of AIM-R100 .................................................................................... 3
4.2 Technical parameters of AID150 ........................................................................................ 3
4.3 Technical parameters of AKH 0.66P26/L-20 ...................................................................... 4
5 Installation and connection ........................................................................................................ 4
5.1 Appearance and installation opening size ........................................................................... 4
5.2 Method of installation ......................................................................................................... 5
5.3 Wiring method..................................................................................................................... 7
5.4 Typical wiring method ........................................................................................................ 9
6 Operation and Usage ................................................................................................................ 10
6.1 Panel .................................................................................................................................. 10
6.2 LED instructions ............................................................................................................... 10
6.3 Function description of keys .............................................................................................. 11
6.4 Key operation instructions ................................................................................................ 12
7 Communication Protocol ......................................................................................................... 14
7.1 Communication protocol introduction .............................................................................. 14
7.2 Introduction to function code ............................................................................................ 15
7.3 AIM-R100 communication address table ......................................................................... 16
8 Typical applications ................................................................................................................. 18
9 Power on and debugging instructions ...................................................................................... 18
9.1 Wiring check ..................................................................................................................... 18
9.2 Common faults and eliminations ...................................................................................... 19

1
AIM-R100 Residual Current Monitoring Product
1 Introduction
Residual current monitoring products are suitable for medical class 2 and class 1 places and other places that
need to monitor the residual current, mainly used for monitoring the residual current of TN-S distribution system
mains and branches. When the residual current value exceeds the preset threshold, the system will send an alarm
signal to remind the staff to deal with it according to the actual situation, so as to eliminate the potential safety
hazards such as electrical fire and electric leakage shock caused by the residual current and provide clean, safe and
continuous power supply for the equipment. The residual current monitoring products are also the monitoring
instruments developed by Acrel with rich product design experience and strict reference to the requirements in the
standards and specifications. The product conforms to the enterprise standard Q31/0114000129C025-2017
Residual Current Monitoring Device.
The remaining current monitoring products mainly include AIM-R100 residual current monitor, AKH-
0.66/L-20 residual current transformer, AID150 centralized alarm and display instrument and ACLP10-24 DC24V
power supply, as shown in Table 1 below.
Table 1 Residual current monitoring products
Type and Name Picture Introduction
AIM-R100 Residual
current monitor
AIM-R100 residual current monitor adopts advanced
microcontroller technology, with high integration, small
size, easy installation, intelligent, digital and networked, it
is the preferred product for multi-loop residual current
monitoring in medical class 1, class 2 and other places.
AKH-0.66/L-20
Residual current
transformer
AKH-0.66/L-20 residual current transformer is used
together with AIM-R100 residual current monitor, high
accuracy and ratio is 2000:1. The current transformer is
installed in the cabinet in the way of screw direct fixation,
which is flexible and convenient for installation and use.
AID150 Centralized
alarm and display
instrument
AID150 centralized alarm and display instrument
adopts LCD display and RS485 bus communication, which
can centrally monitor the data of up to 16 sets of AIM-
R100 residual current monitors or the insulation monitors
such as AIM-M10 and AIM-M100, and it can alarm
remotely by sound and light.

2
ACLP 10-24 is DC24V power supply for AID150,
which uses a completely isolated linear transformer. It has
the characteristics of stable output voltage, small ripple,
high voltage withstand grade. It adopts the standard guide
way to install, and can be installed on the same guide way
near the residual current monitor.
2 Functional characteristics
2.1 Function characteristics of AIM-R100
Monitoring TN-S system real-time and display the residual current;
Monitoring the residual current transformer wiring short circuit, break line, and the failure alarm real-time;
Relay output, LED alarm indication and various fault indicator function;
Advanced field bus communication technology, and centralized alarm and display, communication, can
monitoring system operation condition real-time;
SOE function, it can record the time of the alarm and fault types, convenient operating personnel analysis
system running status, promptly eliminate malfunction;
Self-checking function, through the function test device of residual current detection function;
Remote reset function, can remote reset residual current monitor, eliminate the alarm message.
2.2 Function characteristics of AID150
Advanced field bus technology, which can be communicated with the residual current monitor;
Centralized alarm and display instrument can set the number of monitor and residual current alarm threshold
in system remotely;
When residual current exceeded threshold or connection failure, it provides sound and light alarm function,
and it can be eliminated;
Up to 16 AIM-R100 residual current monitors or AIM-M10, AIM-M100 insulation monitors can be monitored,
wall installation, apply to the operating room, ICU, or other places of centralized monitoring.
2.3 Function characteristics of ACLP10-24
Adopts linear transformer isolation, has strong anti-interference ability, low ripple;
AC 220V input and DC 24V output, the maximum output power is 3W;
Used to AID150 alarm and display instrument with DC24V power supply.
2.4 Function characteristics of AKH-0.66/L-20
Measurement precision is 0.2 class, ratio is 2000:1;
Measuring residual current in load with AIM - R100 residual current monitor.

3
3 Reference standards
3.1 IEC 60364-7-710:2002 Electrical installations of buildings - Part 7-710: Requirements for special installations
or locations - Medical locations
3.2 IEC62020-1:2020 Electrical accessories - Residual current monitors (RCMs) - Part 1: RCMs for household and
similar uses
4 Technical parameters
4.1 Technical parameters of AIM-R100
They are shown in Table 2.
Table 2 Parameters of AIM-R100 residual current monitor
Items parameters
Accessory
power supply
Vo l t a g e AC 220V±10%
Power
dissipation
≤3VA
Residual
current
monitoring
Loops 12
Measure range 0~5000mA
Setting range 6~1000mA
Frequency 50±5 Hz
Relay output
output 1 relay output, normally open
Contact
capacity
AC 250V/3A DC 30V/3A
Communicatio
n
Interface RS485
Protocol Modbus-RTU
MTBF ≥50000 hour
4.2 Technical parameters of AID150
They are shown in Table 3.
Table 3 Technical parameters of AID150 centralized alarm and display instrument
Items parameters
Accessory
power supply
Vo l t a g e DC 24V
Power
dissipation
< 0.6W
Residual current display range ×

4
Self-check function √
Number of systems ≤16
alarm Sound and light alarm, sound can be eliminated
SOE Leakage fault, transformer break, short circuit of
transformer, equipment fault
Communication RS485, Modbus-RTU
Display 128×64 dots LCD
4.3 Technical parameters of AKH 0.66P26/L-20
They are shown in Table 4.
Table 4 Technical parameters of the AKH-0.66/L-20 residual current transformer
Items parameters
Precision 0.2
Ratio 2000:1
Rated (secondary) current 50mA
Secondary output of transformer Cable line
5 Installation and connection
5.1 Appearance and installation opening size
5.1.1 Appearance and mounting hole size of AIM-R100 Residual current monitor (unit: mm)
Front view Side view
5.1.2 Shape and mounting hole size of AID150 centralized alarm and Display Instrument (unit: mm)
Acrel
AIM-M100
Acrel
AIM-M100
Acrel
AIM-M100
Acrel
AIM-M100
Acrel
AIM-M100
AcrelAcrel
AIM-M100
Acrel
AIM-M100
Acrel
AIM-M100
Acrel
AIM-M100
Acrel
AIM-M100
Acrel
AIM-R100
On
Comm
Fault
Alarm
Medical Residual Current Monitor
Menu/
Test/Esc
12 4589 1112
13 14 25 26 20 21 22 23 24
U1 U2 I2I3I6
COM2
Z1 Z2
DO1+ DO1-
I7
I1
367
I4I5
10
I 8
COM1
I12 I 11 I10 I 9
15 16
AB

5
Front view hole size side view
5.1.3 Shape and mounting hole size of AKH-0.66/L-20 residual current transformer (unit: mm)
Front view bottom view
5.2 Method of installation
In addition to the AID150 centralized alarm and display instrument, the residual current monitoring products
are best centrally installed in the distribution cabinet. AIM-R100 residual current monitor uses 35mm standard
guide rail to install, AKH-0.66/L-20 residual current transformer uses screws (attached) directly fixed installation.
When the AID150 centralized alarm and display instrument is used in the operating room, it can be embedded in
the wall and installed next to the information panel in the operating room for medical personnel to view; When
AID150 is used in other medical places, it is recommended to install in the nurse station. It can also be installed in
other locations that are easy to monitor. External wiring of the AID150 centralized alarm and display instrument
includes two DC24V power supply lines and two RS485 communication lines, which are drawn from the
distribution cabinet. Pipelines should be reserved during construction. In the centralized monitoring, the RS485
communication between the AIM-R100 and AID150 should be connected hand in hand.
5.2.1 Installation method of AIM-R100 residual current monitor
The AIM-R100 residual current monitor is installed with guide rail and fixed with buckles, as shown in the
figure below:
Test
Mute Menu
Acrel
On Comm
AID150

6
5.2.2 Installation method of AID150 alarm and display instrument
AID150 centralized alarm and display instrument, which is suitable for embedded wall installation.
installation diagram is shown in figure below.
During the decoration, firstly, the AID150 should be embedded in the wall to be fixed and be close to the
knockouts of the pipeline, so that the wires (two power cords and two-core shielded twisted pair) can be drawn to
the front cover, and then fix the cover on the shell with screws.
If the AID150 centralized alarm and display instrument is installed by opening the cabinet door, the
installation diagram is shown in figure below.
1.Product shape 2.Size of wall
openings
3.Insert the shell
into the wall
5.Fixed LCD board
and Shell
4.Connect to the
LCD board through
the terminal
Attention:
As our products
are constantly
updated, this
drawing is for
reference only
until it has been
confirmed by the
relevant
personnel.
Acrel
Run Comm Error Alarm
AID150
TEST
MENU

7
5.2.3 Installation method of ACLP10-24 DC24V power supply
The ACLP10-24 DC24V power supply is used to install in the way of guide rail, which is fixed with snap-in
type. It can also be installed on the same guide rail side by side with the AIM-R100 insulation monitor.
5.3 Wiring method
5.3.1 Wiring method of AIM-R100 residual current monitor
Upper terminals: U1, U2 (1, 2) are AC220V auxiliary power supply. I△1~I△8 (3, 4, 5, 6, 8, 9, 10, 11) are
connected to one end of the residual current transformer, and COM1 (7) or COM2 (12) are connected to the other
end of the residual current transformer corresponding (wiring without polarity).
Lower terminal: Z1, Z2 (13, 14) access to external self-check reset button, DO1+, DO1- is alarm relay
output, A, B is centralized alarm and display instrument terminal, I△9-I△12 (24, 23, 22, 21) access to the end of
the residual current transformer, COM3 (20) access to the other end of the residual current transformer (wiring
without polarity).
AID150 shape Separate the product
body from the cassette
Install the cassette on
the door panel
Hole size of door
panel
Screw Clasp
Fix the panel to
the cassette
Screw
Attention:
As our products
are constantly
updated, this
drawing is for
reference only
until it has
been confirmed
by the relevant
personnel.
8 9 10 11 121234567
U1 U2
Table of contents
Other Acrel Measuring Instrument manuals

Acrel
Acrel AID120 User manual

Acrel
Acrel ADL400 Owner's manual

Acrel
Acrel DJSF1352-RN Owner's manual

Acrel
Acrel ARTM-Pn User manual

Acrel
Acrel ADL400 Owner's manual

Acrel
Acrel AMC Series Owner's manual

Acrel
Acrel AGF-AE-D/200 User manual

Acrel
Acrel AMC Series Owner's manual

Acrel
Acrel ADL3000-E Owner's manual

Acrel
Acrel AID120 User manual

Acrel
Acrel AMC Series Owner's manual

Acrel
Acrel ADL400 Owner's manual

Acrel
Acrel AIM-T500L Series User manual

Acrel
Acrel ADW310 Guide

Acrel
Acrel GGF Series User manual

Acrel
Acrel ACR10R-D TE Series Technical specifications

Acrel
Acrel AMC Series Owner's manual

Acrel
Acrel ADL200 User manual

Acrel
Acrel ADW310 Quick guide

Acrel
Acrel ADL400 Owner's manual