WIKA IPT-2 Series User manual

Operating Instructions
Process pressure transmitter IPT-2x
Process pressure transmitter IPT-2x
4 … 20 mA
Metallic sensor

2
Contents
WIKA Operating Instructions - Process pressure transmitter IPT-2x
Contents
1 About this document ............................................................................................................... 4
1.1 Function ........................................................................................................................... 4
1.2 Target group ..................................................................................................................... 4
1.3 Symbols used................................................................................................................... 4
2 For your safety ......................................................................................................................... 5
2.1 Authorised personnel ....................................................................................................... 5
2.2 Appropriate use................................................................................................................ 5
2.3 Warning about incorrect use............................................................................................. 5
2.4 General safety instructions............................................................................................... 5
2.5 EU conformity................................................................................................................... 6
2.6 Permissible process conditions........................................................................................ 6
2.7 NAMUR recommendations .............................................................................................. 6
2.8 Installation and operation in the USA and Canada ........................................................... 6
3 Product description ................................................................................................................. 8
3.1 Conguration.................................................................................................................... 8
3.2 Principle of operation........................................................................................................ 9
3.3 Supplementary cleaning procedures.............................................................................. 12
3.4 Packaging, transport and storage................................................................................... 12
4 Mounting................................................................................................................................. 14
4.1 General instructions ....................................................................................................... 14
4.2 Ventilation and pressure compensation.......................................................................... 15
4.3 Process pressure measurement..................................................................................... 17
4.4 Level measurement........................................................................................................ 19
4.5 External housing ............................................................................................................ 20
5 Connecting to power supply................................................................................................. 21
5.1 Preparing the connection ............................................................................................... 21
5.2 Connecting..................................................................................................................... 22
5.3 Single chamber housing................................................................................................. 23
5.4 Housing IP 66/IP 68 (1 bar) ............................................................................................ 24
5.5 External housing with version IP 68 (25 bar)................................................................... 25
5.6 Switch-on phase............................................................................................................. 26
6 Set up with the display and adjustment module ................................................................ 28
6.1 Adjustment system......................................................................................................... 28
6.2 Measured value indication.............................................................................................. 29
6.3 Parameter adjustment - Quick setup .............................................................................. 29
6.4 Parameter adjustment - Extended adjustment................................................................ 30
6.5 Saving the parameterisation data................................................................................... 42
7 Diagnostics and servicing .................................................................................................... 43
7.1 Maintenance .................................................................................................................. 43
7.2 Diagnosis function.......................................................................................................... 43
7.3 Rectify faults................................................................................................................... 45
7.4 Exchange process module on version IP 68 (25 bar) ..................................................... 46
7.5 Instrument repair ............................................................................................................ 47
8 Dismount................................................................................................................................. 48
8.1 Dismounting steps.......................................................................................................... 48

3
Contents
WIKA Operating Instructions - Process pressure transmitter IPT-2x
8.2 Disposal ......................................................................................................................... 48
9 Supplement ............................................................................................................................ 49
9.1 Technical data ................................................................................................................ 49
9.2 Calculation of the total deviation..................................................................................... 64
9.3 Calculation of the total deviation - Practical example...................................................... 65
9.4 Dimensions .................................................................................................................... 67
9.5 Trademark ...................................................................................................................... 75
Safety instructions for Ex areas
TakenoteoftheExspecicsafetyinstructionsforExapplications.
These instructions are attached as documents to each instrument
with Ex approval and are part of the operating instructions.
Editing status: 2019-03-11

4
1 About this document
WIKA Operating Instructions - Process pressure transmitter IPT-2x
1 About this document
1.1 Function
This operating instructions provides all the information you need for
mounting, connection and setup as well as important instructions for
maintenance,faultrectication,theexchangeofpartsandthesafety
of the user. Please read this information before putting the instrument
into operation and keep this manual accessible in the immediate
vicinity of the device.
1.2 Target group
This operating instructions manual is directed to trained personnel.
Thecontentsofthismanualmustbemadeavailabletothequalied
personnel and implemented.
1.3 Symbols used
Information, tip, note
This symbol indicates helpful additional information.
Caution: If this warning is ignored, faults or malfunctions can result.
Warning: If this warning is ignored, injury to persons and/or serious
damage to the instrument can result.
Danger: If this warning is ignored, serious injury to persons and/or
destruction of the instrument can result.
Ex applications
This symbol indicates special instructions for Ex applications.
• List
The dot set in front indicates a list with no implied sequence.
→ Action
This arrow indicates a single action.
1 Sequence of actions
Numbers set in front indicate successive steps in a procedure.
Battery disposal
This symbol indicates special information about the disposal of bat-
teries and accumulators.

5
2 For your safety
WIKA Operating Instructions - Process pressure transmitter IPT-2x
2 For your safety
2.1 Authorised personnel
All operations described in this documentation must be carried out
onlybytrained,qualiedpersonnelauthorisedbytheplantoperator.
During work on and with the device, the required personal protective
equipment must always be worn.
2.2 Appropriate use
The IPT-2x is a pressure transmitter for process pressure and hydro-
static level measurement.
Youcannddetailedinformationabouttheareaofapplicationin
chapter "Product description".
Operational reliability is ensured only if the instrument is properly
usedaccordingtothespecicationsintheoperatinginstructions
manual as well as possible supplementary instructions.
2.3 Warning about incorrect use
Inappropriate or incorrect use of this product can give rise to applica-
tion-specichazards,e.g.vesseloverllthroughincorrectmounting
or adjustment. Damage to property and persons or environmental
contamination can result. Also, the protective characteristics of the
instrument can be impaired.
2.4 General safety instructions
This is a state-of-the-art instrument complying with all prevailing
regulations and directives.The instrument must only be operated in a
technicallyawlessandreliablecondition.Theoperatorisresponsi-
ble for the trouble-free operation of the instrument. When measuring
aggressive or corrosive media that can cause a dangerous situation
if the instrument malfunctions, the operator has to implement suitable
measures to make sure the instrument is functioning properly.
During the entire duration of use, the user is obliged to determine the
compliance of the necessary occupational safety measures with the
current valid rules and regulations and also take note of new regula-
tions.
The safety instructions in this operating instructions manual, the na-
tional installation standards as well as the valid safety regulations and
accident prevention rules must be observed by the user.
For safety and warranty reasons, any invasive work on the device
beyond that described in the operating instructions manual may be
carried out only by personnel authorised by the manufacturer. Arbi-
traryconversionsormodicationsareexplicitlyforbidden.Forsafety
reasons,onlytheaccessoryspeciedbythemanufacturermustbe
used.
To avoid any danger, the safety approval markings and safety tips on
the device must also be observed and their meaning read in this oper-
ating instructions manual.

6
2 For your safety
WIKA Operating Instructions - Process pressure transmitter IPT-2x
2.5 EU conformity
ThedevicefullsthelegalrequirementsoftheapplicableEUdirec-
tives.ByaxingtheCEmarking,weconrmtheconformityofthe
instrument with these directives.
2.6 Permissible process conditions
For safety reasons, the instrument must only be operated within the
permissibleprocessconditions.Youcannddetailedinformationon
the process conditions in chapter "Technical data" as well as on the
type label.
Thepermissibleprocesspressurerangeisspeciedby"MWP"
(Maximum Working Pressure) on the type label, see chapter "Struc-
ture".The MWP takes the element of the measuring cell and process-
ingttingcombinationwiththeweakestpressureintoconsideration
andmayappliedpermanently.Thespecicationreferstoareference
temperature of +20 °C (+68 °F). It also applies when a measuring cell
with a higher measuring range than the permissible pressure range of
theprocessttingisinstalledorder-related.
In order to prevent damage to the device, the test pressure may only
exceedthespeciedMWPbrieyby1.5timesatreferencetempera-
ture.Thepressurestageoftheprocessttingaswellastheoverload
resistance of the measuring cell are taken into consideration here
(see chapter "Technical Data").
Inaddition,atemperaturederatingoftheprocesstting,e.g.with
anges,canlimitthepermissibleprocesspressurerangeaccording
to the respective standard.
2.7 NAMUR recommendations
NAMUR is the automation technology user association in the process
industry in Germany. The published NAMUR recommendations are
acceptedasthestandardineldinstrumentation.
ThedevicefullstherequirementsofthefollowingNAMURrecom-
mendations:
• NE 21 – Electromagnetic compatibility of equipment1)
• NE 43 – Signal level for fault information from measuring transduc-
ers
• NE53–Compatibilityofelddevicesanddisplay/adjustment
components
• NE107–Self-monitoringanddiagnosisofelddevices
For further information see www.namur.de.
2.8 Installation and operation in the USA and
Canada
This information is only valid for USA and Canada. Hence the follow-
ing text is only available in the English language.
Installations in the US shall comply with the relevant requirements of
the National Electrical Code (ANSI/NFPA 70).
1) Notfullledwhenconnectingtoanexternaldisplayandadjustmentunit.

7
2 For your safety
WIKA Operating Instructions - Process pressure transmitter IPT-2x
Installations in Canada shall comply with the relevant requirements of
the Canadian Electrical Code
A Class 2 power supply unit has to be used for the installation in the
USA and Canada.

8
3 Product description
WIKA Operating Instructions - Process pressure transmitter IPT-2x
3 Product description
3.1 Conguration
The scope of delivery encompasses:
• Instrument IPT-2x
• Documentation
– Operating instructions IPT-2x
– Characteristicstestcerticate
– Instructions for optional instrument features
– Ex-specic"Safety instructions" (with Ex versions)
– Ifnecessary,furthercerticates
Note:
Optional instrument features are also described in this operating
instructions manual.The respective scope of delivery results from the
orderspecication.
This operating instructions manual applies to the following instrument
versions:
• Hardware from 1.0.0
• Software from 1.3.4
Note:
Youcanndthehardwareandsoftwareversionoftheinstrumentas
follows:
• On the type plate of the electronics module
• In the adjustment menu under "Info"
Thetypelabelcontainsthemostimportantdataforidenticationand
use of the instrument:
Scope of delivery
Scope of this operating
instructions
Type label

9
3 Product description
WIKA Operating Instructions - Process pressure transmitter IPT-2x
1
10
11
13
12
4
5
2
6
3
7
8
9
Fig. 1: Layout of the type label (example)
1 Instrument type
2 Field for approvals
3 Signal output and voltage supply
4 Technical data
5 Product code
6 Order number
7 Serial number of the instrument
8 Symbol of the device protection class
9 ID numbers, instrument documentation
10 Reminder to observe the instrument documentation
3.2 Principle of operation
IPT-2x is suitable for applications in virtually all industries. It is used for
the measurement of the following pressure types.
• Gauge pressure
• Absolute pressure
• Vacuum
Measured products are gases, vapours and liquids.
IPT-2x is especially suitable for applications with higher temperatures
and high pressures.
The IPT-2x is suitable for the measurement of the following process
variables:
• Process pressure
• Level
Application area
Measured products
Measured variables

10
3 Product description
WIKA Operating Instructions - Process pressure transmitter IPT-2x
Fig. 2: Process pressure measurement IPT-2x
The process pressure acts on the sensor element via the process dia-
phragm.The process pressure causes a resistance change which is
converted into a corresponding output signal and output as measured
value.
Piezoresistive sensor element
Measuringrangesupto40bar:piezoresistivesensorelementwith
internal transmission liquid is used.
1
3 4
2
Fig. 3: Conguration of the measuring system with piezoresistive sensor ele-
ment
1 Sensor element
2 Base element
3 Transmission liquid
4 Process diaphragm
Strain gauge (DMS) sensor element
For measuring ranges above 100 bar, a strain gauge (DMS) sensor
element (dry system) is used.
Measuring system
Other manuals for IPT-2 Series
1
Table of contents
Other WIKA Measuring Instrument manuals

WIKA
WIKA FLC-UFL Series User manual

WIKA
WIKA RVM/U-L-1 User manual

WIKA
WIKA CPH6300-S1 User manual

WIKA
WIKA SENSeOR AMS01 User manual

WIKA
WIKA DG-10-S User manual

WIKA
WIKA CPH6400 User manual

WIKA
WIKA 891.34 User manual

WIKA
WIKA 55 Series Operating instructions

WIKA
WIKA TR12 Series Operating instructions

WIKA
WIKA 632.50 User manual