
Free Catalog and Application Assistance
1.800.328.6170
Website: www.electro-sensors.com
990-007000 Revision A
the SG1000RA behaves as follows:
• Both green LEDs are solid ON.
• When the gate is at the fully-closed position (0% open), then
the 0%-open Relay1 de-energizes, and the 100%-open Relay2
remains energized. This behavior modies slightly when
accounting for any effect of the SW1 set-point and hysteresis
selection.
• When the gate is at the fully-open position (100% open), then
the 100%-open Relay2 de-energizes, and the 0%-open Relay1
remains energized. (Again, allow for any effect of the SW1
selection).
• Any gate position between 0% open and 100% open is
represented both relays being energized. (Again, allow for
any effect of the SW1 selection).
• If the gate is moved to a position that is slightly beyond
(outboard of) the fully-closed (0% open) calibrated position,
then Relay1 remains de-energized. This is known as 0% ‘run-
out’, and it holds to a certain point. If the encoder is turned
far enough beyond the fully-closed calibrated position, then
the encoder “wraps-around” and the relays ip-op to the
fully-open value of 100%-open Relay2 de-energized, and the
0%-open Relay1 energized.
• If the gate is moved to a position that is slightly beyond
(outboard of) the fully-open (100% open) calibrated position,
then Relay2 remains de-energized. This is known as 100%
‘run-out’, and it holds to a certain point. If the encoder is
turned far enough beyond the fully-open calibrated position,
then the encoder “wraps-around” and the relays ip-op to
the fully-closed value of 0%-open Relay1 de-energized, and
the 100%-open Relay2 energized.
• For a properly calibrated SG1000RA, the direction of
calibration (auto-detected CW or CCW), and the encoder
values for the fully-closed and fully-open gate positions are
all stored in the SG1000RA’s EEPROM memory
Note: Since a properly calibrated SG1000RA can never enter
Calibration Mode again by itself after Calibration
Mode is exited, this means that for a properly calibrated
SG1000RA running in Normal Operating Mode the
calibration results are protected until the user wants to
purposefully enter Calibration Mode again.
If re-calibration is needed, see the section below
titled “How to clear-out the existing calibration and
reprogram the SG1000RA.”
Invalid Calibration (Error condition behavior)
Assuming the user followed the calibration process incorrectly,
the SG1000RA behaves as follows:
• Both green LEDs are in a rapid ash.
• Both relays remain de-energized.
An “invalid calibration” is most likely due to one of the
following errors:
- If the user did not move the gate (or moved it but less
than 1/4th-turn, or more than 6-turns, of the encoder shaft)
between teaching the SG1000RA the fully-closed and fully-
open positions, then the closed and open positions have the
same (or nearly the same) encoder count.
- The user “double-pressed” SW2 during during entry into
Calibration Mode or while teaching the SG1000RA the fully-
closed position.
Power-ups; Calibration vs. Normal Operating Mode
• An SG1000RA that is un-calibrated (or if the calibration
attempt was invalid) automatically powers-up in Calibration
Mode, the next time power is applied.
• A properly calibrated SG1000RA powers-up in Normal
Operating Mode, when power is applied.
• If the user accesses Calibration Mode via the “power-up”
method, then any previous calibration is immediately cleared.
• If the user accesses Calibration Mode via the “on-the-y”
method, then any previous calibration is retained until the
new calibration points have been acquired. (This allows
the user the option to bail out of Calibration Mode before
completing the new calibration by simply removing the
Vac power. In this case of intended power interruption, the
EEPROM never gets called to save any new calibration, thus
the old calibration is retained
Troubleshooting Hints
1) If your SG1000RA operates both relays, but not at the gate
positions expected, then double-check the following:
a) Do you have the Relay set-point/hysteresis selection
16-position rotary switch (SW1) set properly?
b) As your gate moves from fully-closed to fully-open, does
the SG1000RA’s encoder-output-shaft turn less than 1/4th-
turn, or more than 6-turns? If so, then the SG1000RA will
not work in your application.
c) Is your SG1000RA terminal TB1 wiring correct?
• Do you have your relay wiring ip-opped?
• See the section “Electrical Connections” for proper
terminal TB1 connections vs the internal Relay1 and
Relay2 pin-outs.
d) Assuming conditions (a) through (c) are proper, and your
SG1000RA still seems to behave improperly, then try
re-calibrating again, paying close attention to the eight
calibration steps and your gate’s fully-closed and fully-
open positions.
How to clear-out the existing calibration, and
reprogram the SG1000RA (Two methods)
One, remove the Vac power, press-in and hold the calibration
switch SW2, then reapply the Vac power. When the two
green LEDs are ashing on the User Interface Board then the
SG1000RA is in Calibration Mode, then release the SW2 button.
(This is referred to as “power-up” entry into Calibration Mode).
The old calibration has now been cleared-out, and the SG1000RA
is in Calibration Mode awaiting new calibration.
Or two, while the SG1000RA remains powered, press-in and hold
the calibration switch SW2, for a constant 5 to 6 seconds. When
the two green LEDs are ashing on the User Interface Board then
the SG1000RA is in Calibration Mode, then release the SW2
4-6