YTL D519050 User manual

1. Introduction
2. Features and Technical Parameters
3. Description
4. Display
5. Connection Diagram
6. Meter Dimensions
7. PC software
8. Installation Instruction
9. Safety Instructions
Three-Phase Four-Wire Meter
User Manual for D519050

1. Introduction
This is din rail three phase muli-funcational energy meter. It is popular in West European as its
standard installation with DIN EN 50022, with RS485, which is the ideal solution for residential
and commercial installations.
2. Features and Technical Parameters
2.1 Features
● DIN RAIL standard installation size.
● RS485 communication, Protocol: IEC1107
● Degree of Protection: IP51 (indoor meter).
2.2 Technical Parameters
Voltage: 3*230/400V
Current: 10(100)A
Accuracy class: 1.0
Standard: IEC62052-11, IEC62053-21
Frequency: 50-60Hz
Impulse constant: 800imp/kWh
Display: LCD 6+1
Power consumption: ≤8VA ≤0.4Wh
Starting current: 0.004Ib
Temperature range: -20~65℃
Flashing red: Impulse indication, width=90ms
Average humidity value of year: 75%
Maximal value: 95%
3. Description

1
A Impulse indication
B LCD display
C A phase current indication
D B phase current indication
E C phase current indication
Material
Case: ABS、PC、Alloy material
Hook: ABS material
4. Display
C
B
A
D
E

2
5. Connection Diagram
6. Meter Dimensions
Height 122mm
Width 100mm
Depth 65mm

3
Weight 0.70kg(Net)
7. Software
Connect the meter correctly to computers or other applicable communication equipments, and connect
to the power supply. The original address is 0. Usage and setting of software please see JPG and
Modbus agreement document. During the writing operation, the SET button must be pressed on first.
8. Installation Instruction
*Choose 35mm standard Din-Rail ( the length is confirmed by yourself ), fixed them in the
location which are waiting for installation
*Put the meter into the upper Din-Rail, then push down the clip in the meter bottom, see
Fig. 1.After the bottom of the meter install into the Din-Rail successfully, release the clip to
make sure the meter have fully installed, see Fig.2 and Fig. 3
Fig 1

4
Fig 2 Fig 3
*Fig. 4 is after installation
Fig 4
*Making the connection according to the wiring diagram,see Fig. 5

5
图5
*After connection, use lead sealing to seal terminal cover,see Fig. 6
图6
Recommended wire(For your reference):
Safe carrying capacity of rubber or plastic insulated wire(1)
specification(mm)
nominal cross
section
(mm2)
Safe carrying capacity(A)
BX
BLX
BV
BLV

6
1*1.13
1
20
18
1*1.37
1.5
25
22
1*1.76
2.5
33
25
30
23
1*2.24
4
42
33
40
30
1*2.73
6
55
42
50
40
7*1.33
10
80
55
75
55
7*1.76
16
105
80
100
75
7*2.12
25
140
105
130
100
7*2.50
35
170
140
160
125
19*1.83
50
225
170
205
150
19*2.14
75
280
225
255
185
19*2.50
95
340
280
320
240
Note:BX(BLX)copper(aluminum)core rubber insulated wire or BV(BLV)copper(aluminum)
core PVC plastic insulated wire,widely used in 500V or less than 500V AC and DC power
distribution system. The temperature for the data listed in the above table is 35℃、the safe
carrying capacity value for the wire on single coved.
9 Safety Instructions
Information for Your Own Safety
This manual does not contain all of the safety measures for operation of this equipment (module,
device) because special operating conditions, local code requirements or local regulations may
necessitate further measures. However, it does contain information which must be adhered to for
your own personal safety and to avoid damage to the equipment. This information is highlighted
by a warning triangle with an exclamation mark or a lightning bolt depending on the severity of the
warning.

7
Warning
Means that failure to observe the instruction can result in death, serious injury or considerable
material damage.
Caution
Means hazard of electric shock and failure to take the necessary safety precautions will result in
death, serious injury or considerable material damage.
Qualified personnel
Installation and operation of this equipment described in this manual may only be performed by
qualified personal.
Only people that are authorized to install, connect and use this equipment and have the proper
knowledge about labeling and grounding electrical equipment and circuits and can do so
according to safety and regulatory standards are considered qualified personnel in the manual.
Use for the intend purpose
The equipment (device, module) may only be used for the application cases specified in the
catalog and the user manual and only in connection with devices and components recommended
and approved by YTL.
Exclusion of liability
We have checked the contents of this publication and every effort has been made to ensure that
the descriptions are as accurate as possible. However, deviations from the description cannot be
completely ruled out, so that no liability can be accepted for any errors or omissions in the
information given. The data in this manual is checked regularly and the necessary corrections will
be included in subsequent editions. If you have any suggestions, pls let us know.
Subject to technical modifications without notice.
Copyright
Copyright Zhejiang Yongtailong Electronic Co., Ltd. April 2013 All rights Reserved.
It is prohibited to pass on or copy this document or to use or disclose its contents without our
express permission. Any duplication is a violation of the law and subject to criminal and civil
penalties. All rights reserved, particularly for pending or approved patents award or registered
trademarks.

8
General Warning
After removing the packaging make sure the integrity of the unit. If in doubt don't use the
equipment and contact technical staff.
Mounting of electric appliances must be carried out only by skilled electricians. It is imperative to
observe the generally applicable safety measures.
In case of failure and /or malfunctioning of the device, turn off it. For any repair only contact
technical staff. Failure to comply with the above may compromise the device safety.
Warranty
The manufactory will repair or exchange the products while the lead seal is still exited, within 18
months, when discovering the products not accordance with the technical specification.
Technical support
For any problems of our products please contact:
Zhejiang Yongtailong Electronic co.,ltd
No. 320 Tongsheng road, Tongxiang Zhejiang, China
Post:314500
Web: www.ytl-e.com
Tel: 0573-88105687 Fax: 0573-88100423
Table of contents
Other YTL Measuring Instrument manuals