General Alarm settings*
Alarms 1 & 2
Select
A12Y
A12n
Enable
Disable (Select this option for PMX420) Toggle Accept
Alarms 3 & 4
Select
A34Y
A34n
Enable
Disable (Select this option for PMX420) Toggle Accept
Setpoint
security
SECy
SECn
Setpoints fixed at setup
Can change setpoints Toggle Accept
Alarm reset
sequence
nOr
rES
Automatic reset
Manual reset Toggle Accept
Note: alarm settings are only shown if the relevant alarm channel is enabled.
Alarm channel one settings*
Coil energisation A1nE
A1nd
Normally energised
Normally de-energised Toggle Accept
Alarm type A1=L
A1=H
Low type (active below setpoint)
High type (active above setpoint) Toggle Accept
Setpoint value SP1=
50.00
Setpoint value
e.g., 50.00 %
-
Dec
-
Inc
Next
Accept
Deadband value db1=
0.01
Deadband value
e.g., 0.01 %
-
Dec
-
Inc
Next
Accept
Timer delay dL1=
20
Timer delay (set to 0 s to disable)
e.g., 20 s
-
Dec
-
Inc
Next
Accept
Alarm channel two settings*
As alarm channel one, except uses A2nE, A2nd, A2=L,A2=H, SP2=, db 2= and dL2=.
Alarm channel three settings*
As alarm channel one, except uses A3n E, A3nd, A3=L,A3=H, SP3=, db3= and dL3=.
Alarm channel four settings*
Coil energisation A4nE
A4nd
Normally energised
Normally de-energised Toggle Accept
Alarm type
A4=L
A4=H
A4=G
A4=S
Low type (active below setpoint)
High type (active above setpoint)
Group alarm
Siren alarm (manual reset mode only)
Toggle Accept
Note: for group or siren alarms, the setpoint, deadband and timer settings are skipped
Setpoint value SP1=
50.00
Setpoint value
e.g., 50.00 %
-
Dec
-
Inc
Next
Accept
Deadband value db1=
10.00
Deadband value
e.g., 10 %
-
Dec
-
Inc
Next
Accept
Instrument Setup (continued)