All components are manufactured under a quality assurance
scheme, certificate No. FM 557622, administered by British
Standards in accordance with BS EN 9001: 2008. In addition
SFL operate a CE approved factory production control system as
required under the Construction Products Directive 93/68/EEC.
Installation / Regulations
Connection to an appliance which is not connected to the fuel
supply, may be carried out by a competent person. However,
connection to an appliance that is connected to the fuel supply
MUST be carried out by an approved and registered heating
engineer, e.g. Gas Safe, HETAS (Solid Fuel) or OFTEC (Oil).
The Installation of the Supra product must be in accordance with
local building regulations and associated National Standards and
Code of Practice. Relevant standards are as follows:-
Document J - DOE Building Regulations
Section F - Building Standards (Scotland)
Section L - Building Regulations (Northern Ireland)
Solid Fuel & Oil Fired Appliances: BS EN15287-1:2007
Domestic Gas Installations: BS5440: Part 1: 2008
Where Supra is used to reline an existing stack, it is imperative that
the product is not supported by suspending from the top of the
stack. In all instances the liner must be lowered down the stack
using a Support Length at the bottom. Location Bands must
then be used at intervals not exceeding 3.0 metres. The Location
Bands are to be secured underneath a joint and are designed
to centrally locate and brace the system when lowered into an
existing chimney or shaft. When required, the Location Bands
can be manufactured to bespoke dimensions provided by the
customer to suit the required chimney / shaft dimensions.
For condensing (WET) applications it is important that horizontal
sloping runs are angled not less than 3° to the horizontal where
head room is limited, but preferably 5°. Various components are
available to facilitate either a 3° or 5° incline from the horizontal.
Drainage components MUST be used strategically within the
system to facilitate the removal of condensation, see Fig 3.
Above 350mm where Supra is used on condensing applications,
Elastomer Seals must be fitted and preferably bonded to the
product. Prior to making the joint, ensure that both mating ends
are clean and free of dirt and apply a generous amount of SFL Seal
Lubricant around the face of the seal to aid installation.
Commercial Applications
The Supra Product is suitable for commercial applications up to
and including 600ID. Due to the complexity of most installations,
SFL can manufacture to order bespoke components including
special angled elbows, tees and multi-inlet manifolds. Please
forward your requirements complete with detailed dimensioned
drawing to SFL Technical Department who will assess your
requirements.
SFL also employ state of the art software to model the
thermodynamic and flow characteristics of the proposed system,
allowing the most economic system design to be achieved. All
designs are calculated in accordance with EN 13384 parts 1 &
2. SFL can also offer advice on the Clean Air Act requirements
and calculate chimney heights to the requirement of the Clean Air
Act Memorandum. For further information please contact SFL
Technical Department.
Elastomer Seal (P1 / W Applications)
The Elastomer Seal is located in the recess of the female end of
the Supra chimney system as detailed in Fig 1. Product sizes from
80mm to 350mm are supplied complete with the Elastomer Seal
factory fitted and bonded. Above 350mm, Joint Seals must be
ordered separately. Where Supra is being used for condensing
(WET) / positive pressure (P1) applications up to 200Pa at a
maximum flue gas temperature of 200°C, Elastomer Seals MUST
be fitted at each joint within the system.
Note: Joint Seals are only suitable for gas and 28Sec (Kerosene)
applications within the above limits.
Where Elastomer Seals are being used, the chimney system must
be installed with a minimum of 3° or preferably 5° incline to the
horizontal to ensure adequate back drainage of condensation.
Failure to maintain an adequate incline and lack of drainage
component in the system may lead to premature failure of the
product / seals.
Seal Size Code Number
80mm 4006308
100mm 4006310
130mm 4006313
150mm 4006315
180mm 4006318
200mm 4006320
250mm 4006325
300mm 4006330
350mm 4006335
400mm 4006340
500mm 4006350
600mm 4006360
SUPRA JOINTING DETAILS
Fig 1
Ensure the Seal Lips
face down
See Fig. 2
Joint Seal
Female
Socket
Elastomer Seals
Supplied bonded on 80mm - 350mm
Standard Supra. Where used on
Supra 400mm and above, the Seal
has to be purchased separately using
the Code Numbers detailed below.
Replacement seals for all diameters
are also given below.
Fig 2
Seal lubricant (P1/W))
This must be applied around the circumference
of the fitted seal to provide a lubricated interface
between the seal and the liner when the
product is used for positive pressure and wet
applications.
Code Number
Seal Lubricant (250ml) 3107500
Only SFL lubricant should be used as it has been specially
formulated for use with both silicone and EPDM seal materials.
Failure to use SFL lubricant when installing seals in Supra product
may invalidate the product warranty.