Omega DPF700 User manual

DPF700
Dual Relay Option Board
for the DPF700 Meter
www.omega.com
e-mail: [email protected]
User’s Guide
Shop on line at

It is the policy of OMEGA to comply with all worldwide safety and EMC/EMI regulations that apply. OMEGA is constantly pursuing certification of its products to the European New
Approach Directi es. OMEGA will add the CE mark to e ery appropriate de ice upon certification.
The information contained in this document is belie ed to be correct, but OMEGA Engineering, Inc. accepts no liability for any errors it contains, and reser es the right to alter
specifications without notice.
WARNING: These products are not designed for use in, and should not be used for, patient-connected applications.
This de ice is marked with the international caution symbol. It is important to read the Setup Guide before installing or commissioning this de ice as the guide contains important
information relating to safety and EMC.
This de ice is marked with the international caution symbol. It is important to read the Setup Guide before installing or commissioning this de ice as the guide contains
important information relating to safety and EMC.
!
Servicing North America:
USA: One Omega Dri e, P.O. Box 4047
ISO 9001 Certified Stamford CT 06907-0047
TEL: (203) 359-1660 FAX: (203) 359-7700
Canada: 976 Bergar
La al (Quebec) H7L 5A1
TEL: (514) 856-6928 FAX: (514) 856-6886
For immediate technical or application assistance:
USA and Canada: Sales Ser ice: 1-800-826-6342 / 1-800-TC-OMEGA®
Customer Ser ice: 1-800-622-2378 / 1-800-622-BEST®
Engineering Ser ice: 1-800-872-9436 / 1-800-USA-WHEN®
Mexico and TEL: (001)800-TC-OMEGA® FAX: (001) 203-359-7807
Latin America: En Español: (001) 203-359-7803
Servicing Europe:
Benelux: Postbus 8034, 1180 LA Amstel een, The Netherlands
TEL: +31 20 3472121 FAX: +31 20 6434643
Toll Free in Benelux: 0800 0993344
Czech Republic: Frystatska 184, 733 01 Kar iná
TEL: +420 59 6311899 FAX: +420 59 6311114
France: 11, rue Jacques Cartier, 78280 Guyancourt
TEL: +33 1 61 37 29 00 FAX: +33 1 30 57 54 27
Toll Free in France: 0800 466 342
German /Austria: Daimlerstrasse 26, D-75392 Deckenpfronn, Germany
TEL: +49 7056 9398-0 FAX: +49 7056 9398-29
Toll Free in Germany: 0800 639 7678
United Kingdom: One Omega Dri e
ISO 9002 Certified Ri er Bend Technology Centre
Northbank, Irlam Manchester M44 5BD United Kingdom
TEL: +44 161 777 6611 FAX: +44 161 777 6622
Toll Free in England: 0800 488 488
OMEGAnet® On-Line Service
www.omega.com
Internet e-mail
®
®

i
PREFA E
MANUAL OBJE TIVES
This manual shows you how to install and use the Dual-Relay option board with the DPF700
meter.
In this manual we pro ide procedures for:
* Setting up the Dual-Relay option board
* Installing the Dual-Relay option board
Use this manual with you DPF700 manual (M1676)
NOTES and AUTIONS
Information that is especially important to note is identified by these labels:
• NOTE
• WARNING
• AUTION
• IMPORTANT
NOTE: pro ides you with information that is important to successfully setup
and use the Programmable Digital Meter.
AUTION or WARNING: tells you about the risk of electric shock.
AUTION, WARNING or IMPORTANT: tells you of circumstances or
practices that can effect the meter's functionality and must refer to
accompanying documents
Note ☞

ii
TABLE OF ONTENTS
1.1 UNPACKING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
1.2 SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
2.1 INSTALLING THE DUAL-RELAY OPTION BOARD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
2.2 SETTING UP THE DUAL-RELAY OPTION BOARD . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
2.3 ELECTRICAL CONNECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
3.1 RELAY OUTPUT OPTION BOARD SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . .6
FIGURES
2.1 DUAL RELAY OPTION BOARD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
2.2 SETPOINT EXAMPLE ILLUSTRATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
2.3 ELECTRICAL WIRING FOR RELAY CONNECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
2.4 DUAL RELAY CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
TABLES
2.1 SETPOINT EXAMPLE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3

1.1 UNPA KING
Remo e the Packing List and erify that all equipment has been recei ed. If there are any
questions about the shipment, use the phone number for the Customer Ser ice Department
nearest you.
Upon receipt of shipment, inspect the container and equipment for any signs of damage. Take
particular note of any e idence of rough handling in transit. Immediately report any damage to
the shipping agent.
The carrier will not honor any claims unless all shipping material is saved for their
examination. After examining and removing contents, save packing material and carton
in the event reshipment is necessary.
1.2 SAFETY ONSIDERATIONS
Refer to your main owners guide manual for complete safety considerations.
This option card is intended for use in a DPF700 panel mount de ice that is protected in
accordance with Class I of EN 61010 (115/230 AC power connections). Installation of this
instrument should be done by Qualified personnel.
• Do not exceed oltage rating on the label located on the top of the instrument housing.
• Always disconnect power before changing signal and power connections.
• Do not use this instrument on a work bench without its case for safety reasons.
• Do not operate this instrument in flammable or explosi e atmospheres.
• Do not expose this instrument to rain or moisture.
• Unit mounting should allow for adequate entilation to ensure instrument does not
exceed operating temperature rating.
• Use electrical wires with adequate size to handle mechanical strain and power
requirements. Install without exposing bare wire outside the connector to minimize
electrical shock hazards.
1
1
Note ☞
Note ☞

2
2
2.1 INSTALLING THE DUAL-RELAY OPTION BOARD
To install the dual-relay option board, follow these steps (refer to the Figure 2-1):
!AUTION: The meter has no power-on switch, so it will be in operation
as soon as you apply power.
!IMPORTANT: Disconnect the power from the unit before installing this
option board.
1. Hold the board in a horizontal position, with the TB3 connector facing towards the
rear of the meter.
2. Line up the 3 connectors located on the back side of the board with pin groups J3, J4
and J5 on the mother card.
3. Push connectors down to secure on relay board.
Figure 2-1. Dual-Relay Option Board
NC1 N01 CM1 NC2 NO2 CM2
123456
TB3/RELAY
RELAY BD MAIN BD
123
TB1
123456
123456
TB2
S1
OPEN
CLOSED
12345678910
21
21
21
J4
J3
J5
TB3
S5
AB

3
2.2 SETTING UP THE DUAL-RELAY OPTION BOARD
You may enter a setpoint from -99999 to 999999 with a decimal point in any of the following
positions: 9.9.9.9.9.9. After applying the scale factor and offset, the displayed measurement is
compared to the setpoint alues.
LO ALARM
Displayed alue is less than Setpoint LO
HI ALARM
Displayed alue is more than Setpoint HI
HYSTERESIS
Relay 2 is energized when display alue is more than Setpoint HI. Relay 2 is not
energized when display alue is less than Setpoint LO
Setpoint Example:
Setpoint H is 500.0 and Setpoint LO is 100.0.
Reading changes from 0 to 600 and back to 0.
Figure 10-2 on the following page illustrates Table 2-1.
Table 2-1. Setpoint Example
Alarm Status
Reading LO (Relay 1) HI (Relay 2) HYS
0 On Off Off
99.9 Off Off Off
300 Off Off Off
500.0 Off Off Off
500.1 Off On On
600 Off On On
500.1 Off Off On
100 - 500 Off Off On
99.9 On Off Off
0 On Off Off
2

2
2.2 SETTING UP THE DUAL-RELAY BOARD ( ontinued)
Figure 2-2. Setpoint Example Illustration
To con ert Setpoint LO to a second high setpoint, set software switch 3 of the configuration
menu to 1 (ConFIG = XX1XXX). LO ALARM becomes acti e when the reading is greater (more
positi e) than that setpoint.
To con ert both setpoints to latched setpoints, set software switch 2 of the configuration menu to
1 (ConFIG =X1XXXX). When relays are energized, they stay energized until a Reset (either
front-panel or back connector reset).
STANDARD RELAY OPTION
RELAY OPERATION WITH HYSTERESIS
RELAY 1 (LO)
RELAY 2 (HI)
RELAY 2 (HI)
RELAY 1 (LO)
RELAY 2 (HI)
RELAY 1 (LO)
RELAY 2 (HI)
RELAY 1 (LO)
(RELAY ON OR ENERGIZED)
(RELAY ENERGIZED)
99.9
SET POINT 99.90
SET POINT 99.90
ON
ON
OFF
OFF
OFF
OFF
OFF OFF
OFF OFF
ON
ON
ON
OFF OFF
OFF OFF
ON
ON
OFF
OFF OFF
ON
ON
500.1
500.1
ON
4

5
2.3 ELE TRI AL ONNE TION AND SPE IFI ATION
Each relay has a form C contact. Refer to Figure 2-1 and Figure 2-3 to locate contacts and S5
switch.
* Install S5-A to control Relay 2 with hysteresis action.
* Install S5-B to control Relay 2 with setpoint HI.
* TB3-1 is a normally closed contact of relay 1.
* TB3-2 is a normally open contact of relay 1.
* TB3-3 is a common contact of relay 1.
* TB3-4 is a normally closed contact of relay 2.
* TB3-5 is a normally open contact of relay 2.
* TB3-6 is a common contact of relay 2.
Figure 2-3. Electrical Wiring for Relay onnections
Figure 2-4. Dual-Relay onnections
10-1. Dual-Relay Option Board
2
J1
J2
TB1
123
123456
1
6
TB2
TB3
EXTERNAL
LOAD
N
L
FUSE
RELAY 1 RELAY 2
NC1
NO1
CM1
NC2
NO2
CM2
TB3—1
TB3—2
TB3—3
NC1
NO1
CM1
TB3—4
TB3—5
TB3—6
NC2
NO2
CM2
RELAY1
RELAY2
K1
K2 A
BS5
P5
SETPOINT LOW OUTPUT
HYSTERESIS OUTPUT
SETPOINT HIGH OUTPUT

3
6
3.1 RELAY OUTPUT OPTION BOARD SPE IFI ATIONS
2 Form "C" on/off relays.
Configurable for latched and unlatched by software.
Max Current: 5 Amps, resisti e load.
Max Voltage: 250 Vac or 28 Vdction D
NOTES
aults
Other manuals for DPF700
2
Table of contents
Other Omega Measuring Instrument manuals

Omega
Omega DP18-RV1 User manual

Omega
Omega RH650 User manual

Omega
Omega CL551 User manual

Omega
Omega HHP680 User manual

Omega
Omega DFG-RS5 User manual

Omega
Omega RH820 User manual

Omega
Omega SP-014 User manual

Omega
Omega DP301AN User manual

Omega
Omega FMA-1600A Series User manual

Omega
Omega HHP460 User manual

Omega
Omega HHP360 Series User manual

Omega
Omega DP6060 User manual

Omega
Omega VSHYe Series User manual

Omega
Omega DP25B-E User manual

Omega
Omega HX71 Series User manual

Omega
Omega PHH-SD1 User manual

Omega
Omega DP461-S User manual

Omega
Omega RD2800 Series User manual

Omega
Omega HHAQ-108 User manual

Omega
Omega FMA1800A User manual