10
● Make sure a DC breaker or other protecve device between
UPS and the external baery pack is installed for added safety. If
not, please install it carefully. Switch o the baery breaker before
installaon.
NOTE: Set the baery pack breaker in “OFF” posion and then
install the baery pack.
● Pay special aenon to the rated baery voltage marked on
the rear panel. If you want to change the numbers of the baery
in a chain, make sure you modify the UPS seng accordingly.
Connecon with wrong baery voltage may cause irreversible
damage of the UPS.
● Pay special aenon to the polarity marking on external baery
terminal block. Connecon with wrong baery voltage may cause
irreversible damage of the UPS.
● Make sure the protecve grounding/earthing wiring is adequate.
The current spec, color, posion, connecon and conductance
reliability of the wire should be veried.
● Make sure the ulity input & output wiring is rated correctly.
The current spec, color, posion, connecon 8 and conductance
reliability of the wire should be veried. Make sure the L/N side is
correct, not reverse or short-circuited.
WARNING
2.4 UPS Installaon for Parallel System
If the UPS is only for single operaon, you may skip this secon.
1) Install and wired the UPS according to the secon 2-3.
2) Connect the output wires of each UPS to an output breaker.
3) Connect all output breakers to a major breaker. This major output
breaker will then connect directly to the loads.
4) Either common baery packs or independent baery packs for each
UPS are allowed.