8
7.
8.
9.
10.
11.
12.
Connect other input and output wires to the corresponding input and
output terminals according to the following diagram.
It is requested to use the accessorial terminal splices which can be
compacted on the wires ghtly, to ensure the connecon between
the wires and the terminal block is reliable.
Install an output breaker between the output terminal of UPS and
the load, and the breaker should be with leakage current protecve
funcon if necessary.
Turn o all the loads rst before connecng the load with the UPS,
then perform the connecon and nally turn on the loads one by one.
Aer compleng the installaon, please check the wires to make sure
all were connected correctly and ghtly.
Suggest charging the baeries for 8 hours before use. Aer Installaon,
turn on the mains power switch and turn the input breaker in the
“ON” posion, the UPS will charge the baeries automacally. It can
also use the UPS immediately without charging the baeries, but the
backup me may be less than the standard value.
If it is necessary to connect the inductance load such as a electri
engine or a laser printer to the UPS, it must be taken into account
that this kind of loads could have a huge current spike at the start-up
that can exceed the UPS’s capacity and easily trigger the overload
protecon in the UPS, which will halts the UPS into error state and
shuts down the electrical power.
Input and output terminal block wiring diagram
Note: Make sure that the input and output wires and the input and
output terminals are connected ghtly.
6.
Fig. 3