MRC PHT-3109 User manual

HUMIDITY/TEMP.
CONTROLLER/MONITOR
Model : PHT-3109
Your purchase of this HUMIDITY/TEMP. CONTROLLER,
MONITOR marks a step forward for you into the field of
precision measurement. Although this METER is a
complex and delicate instrument, its durable structure
developed. Please read the following instructions carefully
and always keep this manual within easy reach.
OPERATION MANUAL
3, Hagavish st. Israel 58817 Tel: 972 3 5595252, Fax: 972 35594529
MRC. 11.19

Caution Symbol
Caution :
* Risk of electric shock !
Caution :
* Do not use fingers or any tool
to touch the Wire Terminals.
* Do not apply the relay contact load
current > 0.5 Amp.
* The instrument contains no user
serviceable parts and should not
be opened by the user.
* Repair or after service should be
done by a qualified technician only.
* Power supply should apply the
correct ACV power voltage
* Cleaning - Only use the dry cloth to
clean the plastic case !
* Equipment protectted throughout
by Double Insulation or Reinforced
Insulation.
Environmental Condition
* Comply with EN61010.
Transient overvoltage at Mains Supply 2500V.
* Pollution Degree 2.
* Altitude up to 2000 meters.
* Indoor use.
* Relative humidity 80% max.

TABLE OF CONTENTS
1.FEATURES................................................................1
2.SPECIFICATIONS......................................................
.
1
2-1 General Specifications..........................................1
2-2 Electrical Specifications........................................3
3.FRONT PANEL DESCRIPTION.....................................4
3-1 Display...............................................................4
3-2 PV ( process value ) indicator...............................4
3-3 SV ( set value ) indicator.....................................
.
4
3-4 Set Button..........................................................
.
4
3-5 Button............................................................▼4
3-6 Button............................................................▲4
3-7 RH/Temp Button.................................................4
3-8 %RH control relay indicator.................................
.
4
3-9 Temp. control relay indicator................................4
3-10 %RH ( humidity ) indicator.................................4
3-11 Temp. indicator.................................................4
3-12 Wire terminals ..................................................4
3-13 RS232 terminal..................................................4
3-14 Input socket .....................................................4
3-15 Case holder ......................................................4
3-16 Probe plug........................................................4
3-17 Probe head ( Humidity & Temperature )..............4
3-18 Probe handle.....................................................4
3-19 Probe fix holder.................................................4
4.MEASURING PROCEDURE..........................................5
4-1 Terminal connection............................................5
4-2 Humidity/Temp. measurement............................
.
5
4-3 1st layer setting procedures.................................6
4-4 2nd layer setting procedures................................8
5. RS232 PC SERIAL INTERFACE...................................
.
12
6. SYSTEM RESET........................................................ 14
7.THE ADDRESS OF AFTER SERVICE CENTER................15

1. FEATURES
* Professional Humidity measurement monitor and
controller.
* Build in humidity control relay and the Temp.
control relay.
* Relay will be make action ( On/Off ) when the reading
value reach high limit or low limit value.
* Offset value setting.
* Hysteresis value setting for high and low alarm.
* , temp. unit setting with default.℃℉
* High precision humidity sensor with fast response time
and high accuracy.
* Large red LED display, high brightness and easy to read.
* RS232 computer interface, send out the humidity and the
temperature data at the same time.
* Optional data acquisition software.
* Optional GSM controller.
* Microprocessor circuit ensures high accuracy and
provides special functions and features.
* Standard 96 X 48 mm DIN case.
2. SPECIFICATIONS
2-1 General Specifications
Display 4 digits red LED, digit size : 14 mm.
Unit Temp. ,℃℉
Humidity %RH
Circuit Custom chip of microprocessor LSI
circuit.
Sensor Humidity Semiconductor
Structure Temperature Semiconductor
1

Sampling Time Approx. 1 second.
Relay outputs Number 2 relays
Function
Relay 1 :
Humidity control relay.
Relay 2 :
Temperature control relay.
Max load 0.5 ACA/250 ACV
0.5 DCA/24 DCV
* Do not apply the relay
contact load current
> 0.5 A, other wise the
relay may be damaged
permanently without
warranty.
Setting value High limit value setting.
Low limit value setting.
Hysteresis value setting.
Offset value setting.
* Setting for Humidity and Temp.
External DC 12 V, 50 mA max.
Power Supply
Data Output RS 232 PC serial interface.
Operating 0 to 50 .℃
Temperature
* Meter
Operating Less than 80% R.H.
Humidity
* Meter
Power Supply 90 to 260 ACV, 50/60 Hz.
Power Approx. 4.7 VA/AC 110V.
Consumption Approx. 5.3 VA/AC 220V.
Weight 384 g/ 0.84 LB.
* Including probe.
Dimension DIN size : 96 x 48 mm.
Depth : 110 mm.
Accessories Instruction manual.....................
.
1 PC
Included Humidity/Temp. probe................1 PC
Case holder with screw...............2 PCs
Probe fix holder..........................1 PC
2

Optional * Data Acquisition software,
Accessories SW-U801-WIN.
* RS232 cable, UPCB-02.
* GSM controller, GSM-889.
* Interface cable ( cable between meter
to GSM-889 ), GMCB-89.
2-2 Electrical Specifications (23±5 )℃
Humidity
Range 10 % to 95 % R.H.
Resolution 0.1 % R.H.
Accuracy 70% RH≧± (3% reading + 1% RH).
< 70% RH - 3% RH.
±3%RH.
Temperature
Measuring Range 0 to 50 /32 to 122℃℃℉ ℉
Resolution 0.1 /0.1℃℉
Accuracy ± 0.8 /1.5℃℉
*
T
he above specifications is for the probe only.
*
A
bove specification tests under the environment RF Field Stren
g
th less than
3
V
/M & frequency less than 30 MHz only.
3

3. FRONT PANEL DESCRIPTION
Fig. 1
3-1 Display
3-2 PV ( process value ) indicator
3-3 SV ( set value ) indicator
3-4 Set Button
3-5 Button▼
3-6 Button▲
3-7 RH/Temp Button
3-8 %RH control relay indicator
3-9 Temp. control relay indicator
3-10 %RH ( humidity ) indicator
3-11 Temp. indicator
3-12 Wire terminals
3-13 RS232 terminal
3-14 Input socket
3-15 Case holder
3-16 Probe plug
3-17 Probe head ( Humidity & Temperature )
3-18 Probe handle
3-19 Probe fix holder
4

4. MEASURING PROCEDURE
Terminal layout Fig. 2
4-1 Terminal connection
1)Input the ACV power ( 90 to 260 ACV ) to T1, T2.
Do not input the
over voltage to the
AC input terminals.
2)Connect the " Humidity Control Relay " output from T3, T4.
Connect the " Temp. Control Relay " output from T5, T6.
4-2 Humidity/Temp. measurement
1)Connect the " Probe plug " ( 3-16, Fig. 1 ) to
" Input socket " ( 3-14, Fig. 1 ).
2)Power on the meter, the " Display " ( 3-1, Fig. 1 ) will
show the humidity value, in the same time the " %RH
indicator " ( 3-10, Fig. 1 ) will light.
5

]
3)Press the " RH/Temp Button " ( 3-7, Fig. 1 ) once,
the " Temp. indicator " ( 3-11, Fig. 1 ) will light, the
" Display " ( 3-1, Fig. 1 ) will show the Temp. value.
* Press the " RH/Temp Button " ( 3-7, Fig. 1 ) once again,
the " Display " will return the " Humidity value ", in the
same time the " %RH indicator " ( 3-10, Fig. 1 ) will light again.
4-3 1st layer setting procedures
LoLt Low Limit
HILt High Limit
Low Limit Value Setting
1)Press the " Set Button " ( 3-4, Fig. 1 ) once, the "
Display " will show " LoLt ", now the meter is ready
for the Humidity " Low Limit " value setting.
Press the " RH/Temp Button " ( 3-7, Fig. 1 ) once,
the " Temp indicator " ( 3-11, Fig. 1 ) will light, now
the meter is ready for the Temperature " Low Limit "
value setting.
Remark :
* Under " Display " show " LoLt ", if " % RH indicator "
( 3-10, Fig. 1 ) is lit, meter is ready for " Humidity
Low Limit " setting.
* Under " Display " show " LoLt ", if " Temp. indicator "
( 3-11, Fig. 1 ) is lit, meter is ready for
" Temperature Low Limit " valuesetting.
* The function of " Low Limit value " setting, refer to
page 10, Fig. 2.
6

2)Use the " Button " ( 3-5, Fig. 1 ) and the "▼▲
Button " ( 3-6, Fig. 1 ) to adjust the desiring " Low
Limit " value.
* When adjust the value, the " SV indicator " ( 3-3, Fig. 1 )
will light.
High Limit Value Setting
1)After set the " Low Limit " value, press the " Set
Button " ( 3-4, Fig. 1 ) twice, the " Display " will show
" HILt ", now the meter is ready for the humidity
" High Limit " value setting.
Press the " RH/Temp Button " ( 3-7, Fig. 1 ) once,
the " Temp indicator " ( 3-11, Fig. 1 ) will light, now
the meter is ready for the Temperature " High Limit "
value setting.
Remark :
* Under " Display " show " HILt ", if " % RH indicator "
( 3-10, Fig. 1 ) is lit , meter is ready for " Humidity
High Limit value " setting.
* Under " Display " show " HILt ", if " Temp. indicator "
( 3-11, Fig. 1 ) is lit, it meter is ready for
" Temperature High Limit value " setting.
* The function of " High Limit value " setting, refer to
page 10, Fig. 2.
2)Use the " Button " ( 3-5, Fig. 1 ) and the "▼▲
Button " ( 3-6, Fig. 1 ) to adjust the desiring " High
Limit " value.
* When adjust the value, the " SV indicator " ( 3-3, Fig. 1 )
will light.
7