Lamtec FMS 4 User manual

www.lamtec.de
Sensors and Systems for Combustion Engineering
Quick Reference for Endusers
Combustion Management System FMS


2
Table of Contents
Table of Contents
1 General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.1 Validity of these Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2 Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.1 Explanation of the Symbols in the Safety Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
3 Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3.1 O2 Trim. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3.1.1 Resetting Faults. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3.1.2 Calling up O2 Trim Text Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
4 System Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
4.1 Mode Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
4.1.1 Mode Abbreviations Used . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
4.1.2 O2 Trim Modes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
4.2 Check Sums - Hours of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
4.2.1 Calling the Checksums . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
4.2.2 Displaying the Running Time Meter. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
4.3 Messages / Faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
4.3.1 What Happens if There is a Fault? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
4.3.2 Reading Faults. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
4.3.3 Resetting Faults. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
4.3.4 Recalling Fault History. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
4.3.5 What happens if a fault occurs in the O2 trim? . . . . . . . . . . . . . . . . . . . . . . . . . 11
4.3.6 Air Deficiency Failure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
4.3.7 Resetting O2 Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
4.3.8 Calling Fault History O2 trim . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
4.4 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
4.4.1 Replacing Relay Module R16 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
5 Appendix. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
5.1 EU Declaration of Conformity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

3
1 General Information
1 General Information
1.1 Validity of these Instructions
This instructions apply to the Combustion Management System FMS 4 and FMS 5 in any con-
figuration.
The software-related information relates to software version v5.8. The software version can
be found on the label of the programme EPROM. In case of doubt ask the LAMTEC Service
- phone: +49 (0)6227 6052-33 or email: support @lamtec.de
If you use another software version as the version mentioned above, some of the described
functions may not be available or some function which are available with your software version
may not be described in this manual.
The devices conform to the following standards and regulations:
European directives:
Harmonised European standards:
Application standards:
NOTICE
Respect the national safety regulations and standards.
2014/30/EU Electromagnetic Compatibility (EMC)
2014/35/EU Low Voltage Directive
(EU)2016/426 Appliances Burning Gaseous Fuels
2014/68/EU Pressure Equipment Directive, conformity assessment categories IV
module B and D
DIN EN 298: 2012-11
DIN EN 1643:2014-09 Integrated leakage check, gas line DIN DVGW PÜZ
N6-2510 ASO 324
DIN EN 12067-2:2004-06
DIN EN 13611:2011-12
DIN EN 60730-2-5: 2015-10
DIN EN 60730-1 :2012-10
DIN EN 676:2017-02 if applicable
DIN EN 267:2017-02 if applicable
DIN EN 12952-8 u. -11 if applicable
DIN EN 12953-7 u. -9 if applicable
DIN EN 50156-1 u. -2 if applicable
EN 746-2
Test mark: CE-0085 AS 0254

4
2 Safety
2 Safety
2.1 Explanation of the Symbols in the Safety Notes
The following symbols are used in this document to draw the user's attention to important safe-
ty information. They are located at points where the information is required. It is essential that
the safety information is observed and followed, and that applies particularly to the warnings.
DANGER!
This draws the user's attention to imminent danger. If it is not avoided, it will result in death or
very serious injury. The plant including its surroundings could be damaged.
WARNING!
This draws the user's attention to the possibility of imminent danger. If it is not avoided, it may
result in death or very serious injury. The plant including its surroundings could be damaged.
CAUTION!
This draws the user's attention to the possibility of imminent danger. If it is not avoided, it may
result in minor injuries. The plant including its surroundings could be damaged.
NOTICE
This draws the user's attention to important additional information about the system or system
components and offers further tips.
The safety information described above is incorporated into the instructions.
Thus, the operator is requested to:
1 Comply with the accident prevention regulations whenever work is being carried out.
2 Do everything possible within his control to prevent personal injury and damage to prop-
erty.

5
3 Commissioning
3 Commissioning
3.1 O2 Trim
3.1.1 Resetting Faults
WARNING!
Before deleting a fault, it is absolutely necessary to call up the fault text!
Press the ENTER key to call up the fault text.
Automatically:
O2 faults will be reset automatically at every burner start-up.
3.1.2 Calling up O2 Trim Text Messages
Manually:
Turn selector switch to ’O2 TRIM’ mode.
Press the key ENTER and call up error text.
Push key 3 (2) upwards
Switch display to O2-trim.
Turn selection switch (1) to STATUS,
Push channel key 3 (4) upwards
Press the ENTER key (3) to call up the indication.
Back → press ENTER key again (3),
or turn selection switch (1) to another position.

6
4 System Operation
4 System Operation
4.1 Mode Display
4.1.1 Mode Abbreviations Used
ON → SWITCH-ON SEQUENCE
BE → READY
ZÜ → IGNITION POSITION
EZ → SETTING/IGNITION
GL → BASE FIRING RATE
EG → SETTING/BASE FIRING RATE
NA → POST-PURGE
AU → OFF
EI → SETTING
SL → CLEAR MEMORY
EV → SETTING/PRE-PURGE
ES → SETTING/CONTROL
ST → FAULT
VO → PRE-PURGE
HA or HAND → MANUAL MODE
LE → FIRING-RATE EXTERN
no indication → CONTROL MODE
BE indicates that the signal is present on terminal 2, and all other signals = 0
If the FMS controls a flue gas damper, it opens. It is possible to switch to
SETTINGS.
ZÜ
EZ
indicates that pre-purge is finished and the ignition position relay pulls
on. The FMS is in the ignition position, but the flame signal is absent.
Switching to SETTING merely causes the mode display to switch to EZ.
Programming is not possible in this mode.
GL
EG
indicates that the burner is on (terminal 8=1), but the control release is
absent (terminal 4=0). The FMS therefore remains in base firing rate
position.Switching to SETTING merely causes the mode display to
switch to EG. Programming is not possible in this mode.
NA indicates that the FMS is in post-purge mode.
All signals = 0
All air channels open. When the configured time has elapsed, the FMS
changes to AU mode.
AU indicates that the FMS is OFF. All control elements closed.
Selector switch on AUTOMATIC, all signals = 0
EI indicates that the mode selector switch is on SETING. Single points can
now be altered or new curves can be entered.
SL indicates that the mode selector switch is set to CLEAR MEMORY. By
pressing the ENTER key the existing curve is cleared and a new curve
can be entered.

7
4 System Operation
4.1.2 O2 Trim Modes
ES indicates that although the mode selector switch is on SETTING.
It's control function is working according to a calculated curve in the
RAM. The curve is calculated from a partial curve, which is already
entered. This mode is reached if the burner is switched off and is
restarted during a programming sequence. The programming can be
continued by operating a switch (change to ’EI’ mode). Flame signal and
control release are present.
ST indicates that the FMS is set to FAULT. The fault code can be called up in
switch position STATUS. In the switch position FIRING RATE the firing-
rate at the time when the fault occurs, is displayed.
VO
EV
indicates that FMS is in PRE-PURGE mode. PRE-PURGE is
active.Switching to SETTING only changes the indication of the mode in
EV. Programming is not possible in this mode.
HAND
or
HA
indicates that the FMS has been switched to manual mode whilst the
burner is running. In the selector switch position FIRING RATE the
firing-rate can be adjusted by actuating the channel 1 switch. To quit
manual mode, actuate any switch but the channel 1 switch.
ext.Hand indicates that the FMS was switched to manual operation, but the firing-
rate was specified externally and not via the channel 1 key (that is, e.g.
via remote software or bus).
LE indicates that the output controller of the FMS is deactivated and the fir-
ing rate is controlled by an external signal
op O2 trim in standby (during burner start-up), or O2 trim temporarily switched off as a
function firing rate via parameters 914 and 915.
or O2 - trim active.
ot O2 trim temporarily deactivated (air deficiency, probe dynamics etc).
od O2 trim deactivated (fault), e.g. test routine failed during burner start-up, dynamic test
negative, O2 trim temporarily deactivated for over 1 hour etc.
C Optimisation at increasing firing rate
c Optimisation at decreasing firing rate

8
4 System Operation
4.2 Check Sums - Hours of Operation
4.2.1 Calling the Checksums
Each of the parameter levels is safeguarded by its own checksum. The checksum for each
level and the safety and pre-purge times are displayed here in succession.
Order:
1st oil safety time in seconds
2nd oil safety time in seconds
1st gas safety time in seconds
2nd gas safety time in seconds
Pre-purge time in seconds
On the FMS without pilot burner the statement of the 2nd safety time contains safety time. The
statement of the 1st safety time is then irrelevant.
NOTICE
If the parameter has been changed, the checksum will change, too, if a total reboot has been
proceeded or the duration of 1h has passed.
Switch (1) to SETPOINT FEEDBACK
Press ENTER (3) and keep pressed
– the display shows the checksum and the safety
times one after the other.
CRC 16 level 0: adjustable without password
1: adjustable by person commissioning
2: adjustable by the burner manufacturer or the boiler manufacturer
3: adjustable by LAMTEC only
4: adjustable by LAMTEC only

9
4 System Operation
4.2.2 Displaying the Running Time Meter
NOTICE
The sum of the curve set 1 running hours and curve set 2 running hours does not necessarily
give the running hours value, which is displayed in total. The total counter relates to the FMS
running hours. It runs as soon as the unit is connected to a power supply (this also provides
the basis for the fault history).
The single running time meters relate to the burner running hours. These run as soon as the
burner is in operation with the respective curve set (flame signal to the FMS).
4.3 Messages / Faults
4.3.1 What Happens if There is a Fault?
NOTICE
If the processor detects a fault, it runs the outputs in the programmed direction, e.g. air on, fuel
off, re-circulation closed.
The fuel solenoid valves close. The fault signal relay pulls on with a few seconds delay. Auto-
matic restarting may be possible, depending on the nature of the fault.
Turn selector switch (1) to SETPOINT
the display shows a moving text with the following
content:
– total running hours
– running hours on curve set 1
– starts on curve set 1
– running hours on curve set 2
– starts on curve set 2
If you use the 4 curve set or 8 curve set option the dis-
play shows the running hours and starts on the addi-
tional curve sets.