KRK KNA NETWORK ANALYZER User manual

Phone: 444 4 575 web:www.krk.com.tr USER GUIDE
KNA NETWORK ANALYZER
2
GARANTİ
YIL
KNA96
R
NETWORK ANALYZER
SH

GENEL ÖZELLİKLER
12
WARNING
1.Cut all power before connecting device.
2.Do not connect the current measurement inputs
directly to the current source. Always connect
the current source using a current transformer.
3. Once the device is energized, do not remove
the front panel.
4.Do not attempt to clean the device with a
solvent or another similar agent. Use only a dry
piece of cloth.
5.Check the correct connections before energized
the device.
6.To prevent potential fire shock hazard, do not
exposed the instrument to rain or moisture.
7.Do not open the instrument under any
circumstances when it is connected to power source.
8. Contact your authorized seller in case of any
problems with your device.
9.Device is only for panel mounting.
WARRANTY
Device has a two year warranty. Any repairs on the
device must be done only by manufacturer.
Otherwise, the device warranty will be void.
GENERAL FEATURES
LCD display
3 voltage measuring inputs
3 current measuring inputs
Communication via Rs485
MEASURED PARAMETERS
Voltage ( Phase-Phase, Phase-Neutral )
Current
Active, Reactive and Apparent power
Frequeny
Active energy
Apparent energy
Cosfi
Total Active Power
Total Reactive Power
Total Apparent Power
Total Cosfi
Harmonic Distortion for Current
Harmonic Distortion for Voltages.

APPLICATIONS
KNA Network Analyser is microprocessor-based
device which is designed to measure all
parameters of an electrical network, calculate
the consumption values and display these on its
LCD screen.
TERMINALS
1
2
N
L3
L2
L1
k2
S3 S2S1
S4
6
S
S6
5
S
L1 NL3 L2 L1
SYSTEMSYSTEM
L1
GND
A
B
1. Voltage Inputs
L1----1st Phase Voltage input
L2----2nd Phase Voltage input
L3----3rd Phase Voltage input
N-----Neutral İNPUT
L1-N----Supply voltage
2. Current Terminals
S1---1st Phase Current input
S2---1st Phase Current input
S3----2nd Phase Current input
S4----2nd Phase Current input
S5----3rd Phase Current input
S6----3rd Phase Current input
1
2
3
3. Communication
B A GND---- RS 485 input
434

54
S
BUTTON FUNCTIONS
SET BUTTON ( ) : Press SET button for device
adjustment.
HARMONIC BUTTON ( ) : When you press
Harmonic button ( ) you can see current and
voltages harmonics for each phases.
DOWN BUTTON ( ) : When you press DOWN
button you can see phase to phase voltages and
L1,L2,L3 Cosfi values.
UP BUTTON ( ) : When you press UP button
you can see kVA, kW, kVArL, kVArC values.
ENTER BUTTON ( ) : When you press ENTER
button you can see total kW, kVArL, kVArCvalues.
Later on respectively.
- kW value for L1, L2, L3 phases and total kW value
- kVArL, kVArC values
- kWh, kVArLh and kVArCh values.
- kWh values for each phases and total value.
- kVArLh values for each phases and total value
- kVArCh values for each phases and total value
ADJUSTMENT
First of all we have to enter current transformer ratio
and necessery parameters into device.
Press SET
( ) button
You will see below screen.
00001
Utr
If you are using voltage transformer you can enter
the value by using UP( )/DOWN( ) button.
If you are not using voltage transformer leave the
value: 00001 and press ENTER button.
Utr : Voltage transformer
S
HH HH
S
6

00001
Ctr
You can enter current transformer ratio By using
UP( )/DOWN( ) button. Example : If you
are using 100/5 current transformer you should
enter value : 00025 Then press ENTER button.
You will see blow screen.
00001
NTn
CTr
Ntn : Network communication number
Press UP( )/DOWN( ) button to enter network
number.
Press ENTER button again to return to main screen.
OPERATING
When you power up the system you will see
voltages , current, frequency and cosfi values for
L1, L2, L3 phases.
Volt
l1000
l2000
l3000
cos000
Amper
0.000
0.000
0.000
00.00Hz
: Current transformer ratio
You will see below screen.
78

When you press DOWN ( ) button you can
see phase to phase voltages and current
When you press DOWN button again you will see
L1, L2 , L3 Cosfi values.
When you press UP ( ) button first you will see
kVA values for each phases on the screen.
If you press UP ( ) button again , respectively you
will see kW, kVArL/ kVArC values for each phases on
the screen.
When you press ENTER ( ) button you will see total
kW,/kVArL,/kVArC values.
Later on respectively ( pressing ENTER button )
- kW value for L1, L2, L3 phases and total kW value.
- kVArL/ kVArC values.
- Total kWh/ kVArLh/ kVArCh values.
- kWh values for each phases and total value.
- kVArLh values for each phases and total value.
- kVArCh values for each phases and total value..
Volt
l12000
l23000
l31000
cos000
Amper
0.000
0.000
0.000
00.00Hz 0000
0000
0000
0.000
0.000
0.000
Volt
l1000
l2000
l3000
cos000
0.000
0.000
0.000
00.00
kW
kVArL
kVArC
910

Otomatik kademe (güç) tanıtma
Power Supply : 220 Vac ±15%(N-L1) 50 Hz
Power Consumption : < 2VA
Current Transformer : ...../5A
Current Measurement Range : 0.005...6A
Operation Temperature : -25 + 60 C
Remote Control :
Protection Class Front :Ip52
Protection Class Rear : Ip20
Voltage Measurement Accuracy : %0.5+-1
Current Measurement Acuracy : %0.5+-1
Power Measurement Accuracy : %0.5+-1
Harmonic Measurement Accuracy : % 2
RS 485
TECHNICAL SPECIFICATIONS
90 mm
90 mm
88 mm
100 mm
100 mm
DIMENSIONS
When you press Harmonics ( ) button you can see
Current and voltages harmonics for each phases
To return back press ( ) button.
HARMONICS MEASUREMENT
HARMONIC%
Volt
l1000
l2000
l3000
03
Amper
0.000
0.000
0.000
H
H
11 12