1. Mount the transmitter in the device to be monitored using the ICC provided zip
tie, velcro or screw. The optimal mounting is to zip tie the transmitter to the
existing shelving (as shown in the photo on the right) towards the side so the
transmitter cannot be obstructed by product.
Testing for signal strength
1. After mounting the probe, return to the display unit
2. Press the menu key and then press option 2 “Probe
Settings” on the display touch screen.
3. Press “Signal” on the touch screen
4. On the display to the right of the probe name and to the
left of the temperature, observe the time in seconds
counting up.
5. If the number resets to 1 every 10 to 30 seconds no
repeater is needed for that transmitter.
6. If the number consistently counts above 50, proceed to the installing repeater
section
Installing Repeater (sold separately)
1. Mount a repeater between the display control box and the transmitter, 5 to 10
feet from the transmitter.
2. Plug the power supply labeled “FOR USE WITH ICC REPEATER ONLY” into
the repeater and a power outlet.
3. After installing the repeater view the signal period and verify the
number is resetting to 1 every 10 to 30 seconds.
4. If the number consistently counts above 60, use another
repeater with different DIP switch settings (see below)
5. Mount another repeater with different DIP switch settings
between the first repeater and display control box 25 to 35 feet
away from the first repeater.
6. Repeat steps 2 - 3 mounting additional repeaters until the signal period is
constantly below 60.
Installing Long Range Repeater (Sold Separately)
When using multiple repeaters, change
the DIP switch settings as shown on
the right.
Repeater #3
Repeater #4
Repeater #2
O
N
Repeater #1
For the repeater furthest from the
TempMinder control (Repeater #1),
use the settings: 3 & 4 down/on.
The next repeater (#2) should have 3
down/on, 4 up/off
Continue in this sequence, no two
adjacent repeaters should have the
same settings.
Temp Minder™Installation Manual – 896950_I Rev A
Page 4