hilmor 1950217 Troubleshooting guide

Model
1950217
Wireless
Vacuum Gauge
Operation and Maintenance Instructions


Introduction ........................................................................................................2
Safety & Limited Warranty............................................................................3
Certifications......................................................................................................4
Quick Start Guide ..............................................................................................5
Wireless Vacuum Gauge Components.....................................................6
Screen & Button Layouts...............................................................................7
Technical Specifications ................................................................................8
Operating Instructions............................................................................. 9-10
Advanced Setting ............................................................................................ 11
Maintenance..................................................................................................... 12
Troubleshooting ..............................................................................................13
TABLE OF CONTENTS
1
1-800-628-8810

hilmor.com
2
INTRODUCTION
It is important to read the entire instruction manual carefully
for a complete understanding of the hilmor® Wireless Vacuum
Gauge features, limitations, and specifications before use.
hilmor® products are designed and manufactured to be used
by trained and licensed HVAC/R technicians. Incorrect use may
result in accidents, injuries or death. Refer to page 3 for safety
precautions.
The hilmor® Wireless Vacuum Gauge come with a two-year
limited warranty. Visit hilmor.com/registration to register
the gauge and activate the warranty.
The hilmor® Wireless Vacuum Gauge offers the ability
to replace the remote sensor if the original one gets
contaminated. This manual should also be referred to when
changing out the remote vacuum sensor.
The serial number can be found on the product label located on
the backside of both the Handheld Display and Remote Sensor
unit.
hilmor® Wireless Vacuum Gauge Replacement Sensor
part number: 1950219

1-800-628-8810 3
SAFETY PRECAUTIONS:
• To prevent personal injury, please read the operating manual carefully and
operate only as instructed.
• Wear safety glasses, gloves and all other recommended safety gear when
working with refrigerants. Contact with refrigerants may cause injury. Please
see any warnings associated with refrigerants.
LIMITED WARRANTY:
• The hilmor® Wireless Vacuum Gauge has a 2-year limited warranty from the
purchase date.
• Product must be registered at hilmor.com/registration to
activate the warranty.
• Warranty service claims are subject to authorized inspection for product
defects. If found defective, hilmor will repair or replace registered products
within warranty period.
• Often, a returned hilmor® Wireless Vacuum Gauge can be serviced with field
maintenance, such as cleaning or replacing the remote sensor or making
minor adjustments found in the Troubleshooting section of this manual. If
the problem persists, contact hilmor Technical Support at 1-800-642-0010
or visit the hilmor website, hilmor.com.
SAFETY/LIMITED
WARRANTY

hilmor.com
4
CERTIFICATIONS
This device complies with part 15 of the FCC Rules. Operation is subject to the following
two conditions:
1. This device may not cause harmful interference, and
2. This device must accept any interference received, including interference that
may cause undesired operation of the device.
NOTE: This equipment has been tested and found to comply with the limits for a Class B
digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide
reasonable protection against harmful interference in a residential installation.
This equipment generates, uses and can radiate radio frequency energy and, if not
installed and used in accordance with the instructions, may cause harmful interference
to radio communications. However, there is no guarantee that interference will not
occur in a particular installation.
If this equipment does cause harmful interference to radio or television reception,
which can be determined by turning the equipment o and on, the user is encouraged
to try to correct the interference by one or more of the following measures:
• Reorient or relocate the receiving antenna.
• Increase the separation between the equipment and receiver.
• Connect the equipment into an outlet on a circuit dierent from that to which the
receiver is connected.
• Consult the dealer or an experienced radio/TV technician for help.
Changes or modifications not expressly approved by the party responsible for
compliance could void the user’s authority to operate the equipment.
This device complies with Industry Canada license-exempt RSS standard(s).
Operation is subject to the following two conditions:
1. This device may not cause interference, and
2. This device must accept any interference, including interference that may cause
undesired operation of the device.
Le present appareil est conforme aux CNR d'Industrie Canada applicables aux appareils radio
exempts de licence. L'exploitation est autorisee aux deux conditions suivantes : (1) l'appareil ne
doit pas produire de brouillage, et (2) l'utilisateur de l'appareil doit accepter tout brouillage
radioelectrique subi, meme si le brouillage est susceptible d'en compromettre le fonctionnement.

1-800-628-8810 5
Install batteries into Handheld Display and Remote Sensor.
Power On Handheld Display and Remote Sensor.
Handheld Display and Remote Sensor will sync automatically:
observe reading on Handheld Display.
Connect Remote Sensor to Valve Core Removal Tool or Refrigerant
Hose using Female-Female Adaptor if needed.
Pull vacuum to desired vacuum reading.
Quick Change-Out Guide for Replacement Sensor:
Purchase the hilmor® Wireless Vacuum Gauge Replacement Sensor.
Unscrew the 2 flathead screws on the back of the Remote Sensor.
Disconnect the 2 white plugs that connect the Remote Sensor
to the Replacement Sensor.
Plug in the new Replacement Sensor and gently tuck the wires into
the Remote Sensor body.
Screw the door back on to the Remote Sensor to secure the
Replacement Sensor.
Turn on the Handheld Display to automatically sync.
QUICK START GUIDE

hilmor.com
6
WIRELESS VACUUM
GAUGE COMPONENTS
SYNC Indicator Light
Remote Sensor
Power/Backlight
Button
Function Button
LCD Screen
Handheld Display
Power/SYNC Button
Remote Sensor
Transmitter
Replacement Vacuum
Sensor
1/4" Male Fitting
1/4" Female-to-Female
Adapter
Up/Down Arrows

1-800-628-8810 7
1/4" Female-to-Female
Adapter
check sensor
Pa kPa
mTorr Torr mmHG micron
alarm moisture
low point high point
units/min
.8.8.8.8.8.8
.0.0.0.8
.8.8.8. 8.8.8.8
check sensor
units/min
.0.0.0.8
alarm
moisture
Sync /
Signal Strength
Check Sensor –
Connection Lost
Battery Level
Pressure Reading
Units of Vacuum
Rate of Change
Alarm ON
Moisture Detected
Alarm Set Value - Low
Alarm Set Value - High
Vacuum
Progress Bar
SCREEN & BUTTON
LAYOUTS
SCREEN ICONS
Scroll Up
Scroll Down
BUTTONS
Power/Backlight Button
Function Button

hilmor.com
8
TECHNICAL
SPECIFICATIONS
Part Number 1950217
Replacement Sensor Part Number 1950219
Batteries Handheld Display AA Alkaline (3)
Remote Sensor AAA Alkaline (3)
Wireless Range 33 Feet unobstructed
Remote Sensor Connection Fitting 1/4" male flare
Adapter Accessory 1/4" 45˚ Flare Female x 1/4" 45˚Flare Female
Acuracy +/- 5% of reading +/- 10 microns
Resolution
5 to 2,000 microns - 1 micron
2,000 to 5,000 microns - 100 microns
5,000 to 10,000 microns - 250 microns
10,000 to ATM - 1,000 microns
Units micron, mTorr, Torr, mmHg, mBar, kPa and Pa
Operating Temperature -20˚C to 50˚C, -4˚F to 122˚F
Operating Humidity Up to 75% relative humidity
Temperature Compensation Range 0˚C to 50˚C , 32˚F to 122˚F
Max Momentary Overpressure 300 PSI
Refresh Rate Every 0.5 seconds
Set Point Alarm User Programmable - See Advanced Settings
Power Management Sleep Mode and configurable backlight - See Advanced
Settings
Battery Life 80 hours without backlight
Dimensions Handheld Display 2.95" x 4.62" .90"
Remote Sensor 2.20" x 5.7" 1.5"
Weight Hand Held Display 9 oz.
Remote Sensor Unit 4.8 oz.