TE331 1 6T 8722-02a
Tebis TX100 Configurator
Consumption indicator TE331
Electrical / Mechanical characteristics: see product user's instructions
Product reference Product designation TX100 version TP device
RF device
TE331 Consumption indicator > 2.7.58
Input modules Consumption indicator TE331 Products KNX
Display
Tariff
Measurement of
electricity consumption
Temperature
measurement
(Only for France)

TE331 2 6T 8722-02a
1. Description of the system.................................................................................................................................................. 3
1.1 General overview......................................................................................................................................................... 3
1.2 General outline ............................................................................................................................................................ 4
2. Presentation of the functions ............................................................................................................................................ 5
2.1 Main functions overview .............................................................................................................................................. 5
2.2 Description of measurement........................................................................................................................................ 6
2.3 Possible installations ................................................................................................................................................... 9
2.4 "Tele-information" Tariff Description.......................................................................................................................... 10
2.5 Description of temperature measurement ................................................................................................................. 10
3. TE331 inputs and outputs ............................................................................................................................................... 11
4. Product installation.......................................................................................................................................................... 11
5. Display of the input numbering ....................................................................................................................................... 12
6. Configuration and setting in standard mode ................................................................................................................... 13
7. "Tele-information Setting ................................................................................................................................................ 13
8. Configuration and setting in Expert mode....................................................................................................................... 13
8.1 General points ........................................................................................................................................................... 13
8.2 Easy Prog mode........................................................................................................................................................ 14
8.3 Expert Prog mode...................................................................................................................................................... 14
8.4 +info mode................................................................................................................................................................. 15
9. Configuration and use with domovea.............................................................................................................................. 16
9.1 Adding the device...................................................................................................................................................... 16
9.2 Importation of group addresses................................................................................................................................. 17
9.3 Choice of tariff under domovea ................................................................................................................................. 18
10. Operation ...................................................................................................................................................................... 20
10.1 Installation ............................................................................................................................................................... 20
10.2 Meaning of the LED's .............................................................................................................................................. 20
10.3 Current outage and return ....................................................................................................................................... 22
10.4 Connection of the toroids according to the number of phases ................................................................................ 22
11. Other functions.............................................................................................................................................................. 24
Summary

TE331 3 6T 8722-02a
The consumption indicator informs users of their consumption through several metering channels including one specifically
dedicated to "Tele-information"*. It is used to monitor and control energy consumption and is built into an automatic global energy
management system.
It is also used to meausre the energy produced for installations with a photovoltaic system. This product can be used in a single-
phase or three-phase installation. All this data is sent on the KNX bus.
In addition to metering, the consumption indicator also has:
• 2 tariff inputs: "Tele-information" and "T1 / T2",
• a temperature input for the connection of an outdoor sensor or an ambiance sensor.
The system can be constructed with several TE331 on the bus. This thus makes it possible to measure one or more circuits using
toroids.
The consumption indicator is adapted to display consumption. It can also be interfaced with the ambiance units or other display
systems thanks to object sent on the KNX bus.
It is used to display the current tariff and the energy consumption according to the current tariff. The tariff can also be distributed
to other devices on the bus.
* Only used in France - See chapter 2.4.
1. Description of the system
1.1 General overview

TE331 4 6T 8722-02a
1.2 General outline
TYD480
Room programmer 6 zones
domovea
TJA450
Clock TX022, TX023
N L1 L2 L3
TE331
CTz
CTy
CTx
N L1 L2 L3
TE331
Ranges clock:
EG103x,
EG203x
All other meters with tariff relay
by dry contact 230V (T1=0V,
T2=230V)
French energy meter
Temperature sensor
indoor EK089 or
outdoor EK088
L1
CTx
L2
CTy
L3
CTz
KNX
T1 / T2
Tele-info

TE331 5 6T 8722-02a
■Tariff
The function is used to:
• Supply the value of the current tariff on the bus for an ambiance display,
• Supply the value of the coming tariff on the bus for display in ambiance - only available with Tele-information,
• Index the current tariff to each metering measurement.
■Power
The function is used to supply the power demand value on the bus for each metering channel.
■Energy
The function is used to supply the consumed energy value on the bus for each metering input.
■Partial meter Reset
The function is used to reset the partial counters to zero for all the metering inputs.
■Metering data dynamic mode
The function is used to refresh the metering data at a higher frequency.
The control is received from a display interface when the requet for data display is made.
■Temperature measurement
The function is used to measure the temperature via a temperature probe.
The data is sent on the bus for remote display.
2. Presentation of the functions
2.1 Main functions overview

TE331 6 6T 8722-02a
The consumption indicator has 7 measurement channels:
- 3 physical channels used to measure voltage and current,
- 1 virtual channel tele-information used to measure the total consumption,
- 1 virtual channel addition used to add up the physical channels,
- 1 virtual channel others used to calculate the difference between the tele-information channel and the physical channels,
- 1 virtual channel three-phase uniting the 3 physical channels to create a single channel.
The current is measured using toroids. The polarity of the toroids is of no importance.
• 1 channel to report the data from the general meter by tele-information (Only for France)
2.2 Description of measurement
1 Power meter
1 Total energy meter
1 Partial energy meter
Send measurement
Meter reset
Measurement by 1
toroid
KNX
KNX
METERING
3 Power meter
3 Total energy meter
3 Partial energy meter
Send measurement
Meter reset
Measurement by 3
toroid
KNX
KNX
2 Power meter
2 Total energy meter
2 Partial energy meter
Send measurement
Meter reset
Measurement by 2
toroid
KNX
KNX
"Tele-info" Power Meter
"Tele-info" Total Energy Meter
"Tele-info" Partial Energy Meter
Send measurement
Meter reset
KNX
KNX
"TELE-INFO"
METERING
Measurement by EDF
meter (Only for
France)
"Tele-info" output

TE331 7 6T 8722-02a
• 1 measurement channel by addition of the channels
• 1 measurement channel by calculation
• 1 three-phase measurement channel
"Addition" power meter
"Addition" total energy meter
"Addition" partial energy meter
Send measurement
Meter reset
KNX
KNX
ADDITION METERING
Measurement by
adding the channels
The channels are added as follows:
• Channels 1, 2 and 3
"Other" power meter
"Other" total energy meter
"Other" partial energy meter
Send measurement
Meter reset
KNX
KNX
METERING BY
CALCULATION
Measurement by
calculation
Metering is the result of a calculation between the total consumption and one or more metering channels.
Metering by calculation is performed as follows:
• Total - channel 1, 2 and 3
The use of "tele-information" metering is mandatory in this case.
Three-phase X power meter
Three-phase Y power meter
Three-phase Z power meter
Three-phase power meter
"Three-phase total energy meter
"Three-phase" partial energy meter
Send measurement
Meter reset
KNX
KNX
THREE-PHASE
METERING
Measurement by 1,
2 and 3 toroids
Metering is performed using 3 toroids connected to each phase.

TE331 8 6T 8722-02a
Installation type
This product can be used in a single-phase or three-phase installation. Three-phase consumption can be measured on each
phase. The measurement is an absolute value.
The measurement channels are used to meter either consumption of energy production (e.g. in the case of a photovoltaic
installation).
It is the display system (in domovea for example) which defines the display of consumption or energy production.
Precaution for connection
Voltage measurement is performed between a phase and neutral.
Each toroid can meter a current up to 90 A. It is possible to pass several conductors in one toroid. The metering channel CTx is
referenced to the Lx phase, CTy to the Ly phase and CTz to the Lz phase.
In the single-phase version, it is essential to bridge phases Ly and Lz when outputs CTy and CTz are used for metering. Straps
are provided for this bridging.
(See chapter 10.4 for all the connection cases).
Reset
The total energy is the energy counted since the product was installed and cannot be reset.
The partial energy can be reset manually by the user using a control on the KNX bus.
Last mode stored
Only the indexes for the current total and partial energies are saved in the TE331.
Updating the data
The metering channels give the instantaneous power and the total and partial energy. This data is sent when the value changes
or periodically.
Single-phase version Balanced three-phase version Unbalanced three-phase version

TE331 9 6T 8722-02a
Possible installations are given below for the configuration of the electricity metering channels only.
* Inputs x, y and z can be allocated to Sockets or Others use to possibly benefit from additional sub-metering:
- Possible values for Sockets: different socket circuits
- Possible values for Others: different lighting, pump or CMV circuits
■Example 1: Electric heating and electric DHW or heat pump + DHW boiler
Channel settings:
Channel x: Heating
Channel y: DHW
Channel z: Sockets
Others = TIC* - (Heating + DHW + Sockets)
* Client Tele-Information
2.3 Possible installations
Installation type Input x Input y Input z Additional settings
Electrical heating + DHW
boiler
OR
Heat pump + DHW boiler
Heating DHW Sockets /
2 in 1 heat pump (Heating +
DHW) Heating / DHW Not used or sockets
or others* Sockets Heating / cooling dates (See
settings)
3 in 1 heat pump (Heating +
Cooling + DHW)
Heating / Cooling /
DHW
Not used or sockets
or others* Sockets
Heating / cooling dates (See
settings)
DHW distribution key (Installer
settings)
Reversible heat pump with
separate DHW production Heating / Cooling DHW Sockets Heating / cooling dates (See
settings)
Heating and DHW production
other than electrical
Not used or sockets
or others*
Not used or sockets
or others*
Not used or sockets
or others* /
Others Sockets DHW Heating

TE331 10 6T 8722-02a
■Example 2: 2 in 1 heat pump (Heating + DHW)
Channel settings:
Channel x: Heating / DHW
Channel y: Sockets with, for example, Ground floor sockets as a label
Channel z: Sockets with, for example, First floor sockets as a label
Others = TIC* - (Heating + DHW + Sockets)
■Example 3: Heating and DHW production other than electrical
This case can only be configured by ETS.
The "Tele-information" link is a standardised bus used only in France which is used to connect electricity management
equipment to one's electronic meter (EDF). It uses the data availalbe in the meter such as the tariff option subscribed to, the
power subscribed to and the consumption data.
By connecting this interface to equipment, it is possible to monitor the development of one's consumption in real time, to calculate
costs or control equipment according to the tariff.
The function allows the temperature to be measured with an indoor (Ref: EK089) or outdoor (Ref: EK088) temperature sensor.
This additional input has no connection with consumption measurement. It is used to measure temperature without adding
additional devices to the KNX bus and send the measurement to a display interface (measurement range: -30°C to +70°C).
2.4 "Tele-information" Tariff Description
2.5 Description of temperature measurement
Others Sockets DHW / Heating