Check wire connections for operation power supply, with detection unit, between alarm unit and concentration display unit, etc.
■TurnthepowersupplyswitchONaftercheckinginputpowersupply
■ChecklightingofPowerLEDforalarmunitandconcentrationdisplayunit.
■Checkdisplayof"SELF"inFNDofconcentrationdisplayunit.
■When"Test"S/Wispushedformorethan2secinthedisplaystateofgasconcentration,Testmodeisenteredinto.
■When30minpassesafterthelastS/WoperationinTestmode,thedisplaystateofgasconcentrationis
automatically returned to.
6.1. Power ON 6.3. Test Mode
- Upon entering in Test mode, the figure for gas concentration display is displayed by blinking.
- This function allows testing in Channel Unit without gas injection in the detector sensor.
- Whentheusercansetanarbitraryvalueforgasconcentrationbypushing"Test"S/W,while
- Alarm Function is normally operated with the concentration value designated by the user.
-When"FUNC"S/Wispushedformorethan2sec,FND/LED/BarLEDTestfunctionisenteredinto.
- 3 Color bar graph LED alternatingly displays green, orange and red at an interval of 0.5sec,
- each function LED blinks at an interval of 0.5 sec.
-When"RESET"S/Wispushed,thedisplaystateofgasconcentrationisreturnedto.
▼▲
Full Range
■When"DOWN(Stand-by)"S/Wispushedformorethan2secinthedisplaystateofgasconcentration,thecheckup
mode is entered into.
■WhenETO(EmergencyTimeOut)wassetforONinOptionSettingModeandsominpasses,thedisplaystateof
gas concentration is automatically returned to.
■UponETOOFF,thedisplaystateofgasconcentrationisreturnedtoonlywhen"DOWN(Stand-by)"S/Wispushed
for more than 2 sec.
6.4. Checkup mode (Stand-by Mode)
- Function where STD-BY LED blinks, contact output f Trouble/Alarm relay for GTC-520A does
- not operate with all other functions operating in the checkup mode.
-When"DOWN(Stand-by)"S/Wispushedformorethan2sec,thedisplaystateofgas
- concentration is returned to.
- When the power supply for GTC-520A is turned ON, the current Firm Ware Version is displayed.
- Figures are displayed after VER is displayed in FND for 0.5 sec.
- Current Version is 2.09.
-"SELF"blinksforabout30secinFNDofconcentrationdisplayunit,anditimmediatelybecomes
- measuring state when Warming-up is finished.
- If abnormality occurs in the equipment or the detection unit at this time, breakdown alarm occurs.
■ IfthereisnoabnormalityinSELFTESTafterPowerOn,thefollowingstateofgasmeasurementisautomaticallyenteredinto.
6.2. Measuring Mode
- Gas concentrations received from the detector are displayed in FND digital display as figures.
- Gas concentration is displayed by 3 Color bar graphic LED and FND, in green when the
- concentration is less than the 1st Alarm, in orange when it is more than the 1st Alarm but less
- than the 2nd Alarm, and in red when it is more than the 2nd Alarm.
- When the detector is not connected or the current value inputted from the detector is inputted
- asacurrentvaluebelowthesetHighscalevalueby10%,thetextof"Undr"isdisplayedby
- blinking at an interval of 1 sec.
- Trouble LED is lighted, warning light blinks, and Buzzer sounds.
-When"BZSTOP"S/Wispushed,warninglightisturnedonandBuzzerstops.
- When the current value inputted from the detector is inputted as a current value more than the
- setHighscalevalueby10%,thetextof"oUEr"isdisplayedbyblinkingatanintervalof1sec.
-Alarm1,2,3LED'sarelighted,warninglightblinks,andBuzzersounds.
- Circular LED on the topmost among 3 Color bar graphic LED is lighted in red.
- When the gas concentration value is recognized as being higher than the Alarm setting value,
- the relevant Alarm function counts Alarm maintenance time and the Alarm function is operated
- if it is more than the Alarm maintenance time.
- Alarm relay is turned ON when it becomes more than the Alarm maintenance time.
-WhenAlarmLatchTypeisin"ON"modeandAlarmfunctionisoperated,Alarmstateandgas
- concentration value are maintained at the maximum value, Even when the gas concentration
- isloweredbelowtheAlarmvalue,itisnotclearedandmustbeclearedby"RESET"S/W.
-WhenAlarmLatchTypeisin"OFF"mode,Alarmfunctionisautomaticallycleareddepending
- on the gas concentrations.
6. How to operate6. How to operate