© 2018 EPG Companies Inc. 4 Bulletin 3594
RUN MODE
2.0 Levels and Alarms
During normal operation the meter will display the real time process level in the units (inches,
centimeters etc) in which the level transducer and the CHS1200 were calibrated during setup.
During normal operation the display indicates the process level. If the meter is in alarm or a pump
is on, every 15 seconds the display will toggle to briefly indicate this status (i.e. AlHi, P etc.).
Pressing the UP and DOWN arrows simultaneously will cause the METER TYPE to be displayed.
2.1 Min / Max
During normal operation pressing either the UP or DOWN arrows will cause the most recent
minimum or maximum process level values recorded by the meter since the last active meter reset.
An Active Reset is performed by simultaneously pressing the UP arrow (max reset) or DOWN arrow
(Min reset) and the SETUP/ENTER key together.
2.2 LED Indicators
There are three LED’s located vertically on the left side of the display that indicate the meter’s real
time operating status.
The TOP LED flashes in alarm if the communications option board is present and the
communication has failed. A small LED to the left of this LED flashes if the option is installed and
the meter is communicating.
The MIDDLE LED is non-operational and reserved for future use.
The BOTTOM LED is ON if either a local or remote pump lockout is enabled.
2.3 Real Time Digital Input Status
Press the SETUP/ENTER key momentarily. The display will read ZERO. Enter a Setup Code value
of 2 by pressing the UP arrow twice and press the SETUP/ENTER key. The display will show
‘d????’. Each ‘?’ will be either a 1 (on) or 0 (off) with each digit representing the status of a local
digital inputs. The meter will continue to monitor and control the pumps while this operation is
performed.
CONFIGURATION PROCEDURE
The meter when first plugged in will quickly perform a startup routine confirming the operation of all
the LED segments. It will then display the current input value. If there is no input and the meter
was setup at EPG, (EPG standard configuration is for a 0-5PSIG input with 4-20mA output) the
meter will display –34.6. In order to change any set points or internal values, one must enter the
respective SETUP MODE as defined in the Configuration Guide on page 10 of this manual. To
enter a SETUP MODE (25, 35, 45) simply firmly press the SETUP/ENTER key momentarily. Upon
release the meter’s display will indicate ZERO. Using the UP/DOWN arrow keys, increment this
value to the desired entry code (25, 35, or 45) and press the SETUP/ENTER key. The meter will
automatically step to the next menu item. The meter will display the next menu item briefly and then
either wait for an entry or toggle to show the current value. Use the UP/DOWN keys to set the
required value.
Pressing the SETUP/ENTER key will enter this value into the meter’s internal memory and
increment the display to the next menu item.
* Keyboard inactivity for more than three minutes will cause the meter to exit the setup mode
and return to the run mode.