Entes MPR-1 Series User manual

1
Network Analyzer
User Manual
MPR-1X
Series
www.entes.eu

2
SAFETY AND WARNING.............................................................................. 3
Attention.................................................................................................... 3
Safety ....................................................................................................... 3
OPERATING CONDITIONS .......................................................................... 4
INTRODUCTION........................................................................................... 5
General Specications.............................................................................. 5
Applications .............................................................................................. 6
MPR-1 Product Family.............................................................................. 7
Appearance and Interface ........................................................................ 7
Terminal Structures................................................................................... 8
Structure of the MPR-14S Terminal: ......................................................... 8
Structure of the MPR-15S-22 Terminal:.................................................... 9
Structure of the MPR-16S-21 Terminal:.................................................. 10
Structure of the MPR-17S-23 Terminal:...................................................11
CONNECTION TYPES................................................................................ 12
3P4W (Three-Phase Four-Wire) Connection.......................................... 12
3P3W (Three-Phase Three-Wire) Connection........................................ 13
ARON Connection .................................................................................. 13
3P4W BLN
(Three-Phase Four-Wire Balanced)
Connection .................. 14
3P3W BLN (Three-Phase Three-Wire Balanced) Connection................ 14
Communication Line Termination Resistance......................................... 15
Device Communication Settings............................................................. 16
TECHNICAL INFORMATION AND ATTACHMENTS................................... 17
Technical Information.............................................................................. 17
IEC 61557-12 Properties ........................................................................ 18
Compliance with the Standards .............................................................. 19
Index

3
SAFETY AND WARNING
Attention
If the following instructions are not carefully followed, the circumstances which can cause
death and serious injuries might happen.
• The installation of the device must be performed by the qualied and trained personnel.
• Please, cut the whole power while installing the device. Please, use a suitable circuit
breaker on the installation terminal.
• You must connect the power lead-ins of the device by using a current transformer. Do not
apply direct current connection.
• Never, remove the front panel while the device is connected to the mains.
•
Never, clean the device by any solvent or similar material. Only use dry cloth for cleaning it.
• Before, turning on the device, make sure that the connections are correct.
• Please, contact your authorized dealer in case of any problem with your device.
• The device is only for interior panel type assembly. Only the front panel of the device
should be accessible from the switchboard.
• The fuse to be used must be CATIII and F type and the current limit value should be 1A
• Current measurement inputs must be connected with auxiliary current
transformers which have reinforced insulation.
• The power meter shall not be used for primary protection or applications where
its failure can cause harm or death.
• Please de-energize the device before replacing RTC backup battery. It must be Li/MnO2
battery.
The manufacturer rm cannot be held responsible in any way for any circumstance which might
arise if the mentioned precautions are not implemented.
Safety
Please, read the entire operating manual before using the device.
•
Connect a button or a circuit breaker between the mains and the supply inputs of the device.
• The button or circuit breaker to be connected should be close to the device.
• It should be labeled that the button or circuit breaker to be connected will be used for
separating the device from the mains.
• This device is used for analyzing the electricity mains and it must not be used for main
protection function.
Guarantee
The guarantee term of the device is 2 (two) years. In case of any problem, the repair of
the device must be done only by the manufacturer rm; otherwise, the guarantee of the
device becomes invalid.

4
OPERATING CONDITIONS
Operating Conditions Value Range
Operating voltage 95-270 VAC/DC (±%10) ,12-50 VDC
(for MPR-1X-D )
Frequency Range 50 ~ 60 Hz. (Tolerances up to +/-10%)
Maximum Measured Current 6A, Measurement should not be done
without current transformer.
Maximum Measured Voltage 300 VAC (VLN) / 480x VAC (VLL)
Operating Temperature Range -10 ~ +70 ºC
Storage Temperature Range -20 ~ +80 ºC
Maximum Ambient Humidity % 95
Communication Speed 2400 ~ 115200 bps

5
INTRODUCTION
General Specications
• Wide supply voltage range (95 – 270 VAC/DC ±-10%, 12-50 VDC for MPR-1X-D series)
• 3 voltage measurement input
• 3 current measurement input
• 4 different language options
• 4 MB Internal Memory
• Real time clock (RTC)
• Alarm
• Time counters (Operating time and overall time)
• Measured parameters via RS-485 (MODBUS):
o Current
o Neutral current
o Voltage (Phase to Phase, Phase neutral)
o Active, Reactive and Apparent power
o Frequency
o Active Power
o Reactive Power
o Apparent Power
o Cos φ
o Power Factor
o Total Active Power
o Total Reactive Power
o Total Apparent Power
o Total Cos φ
o Total Power Factor
o Total Harmonic Distortion of the Current (% THD-I)
o Total Harmonic Distortion of Phase- Phase Voltages (% THD-VLL)
o Total Harmonic Distortion of Phase-Neutral Voltages (% THD-VLN)
Instant minimum and maximum measured parameters::
o Current
o Phase to Phase Voltage
o Phase Neutral Voltage
o Active Power
o Reactive Power
o Apparent Power
o Frequency
o Total Harmonic Distortion of the Current
o Total Harmonic Distortion of Phase - Phase Voltages (% THD-VLL)
o Total Harmonic Distortion of phase-neutral current (% THD-VLN)

6
Demand and Maximum Demand parameters measured by integration time:
o Current
o Active Power
o Apparent Power
• Insulated Digital Input and Output, Relay and Analog Output
• Saving 256 event logs
• DIN4 type rack assembly
• Measurement by 5 different connections: 3-phase 4-wire, 3-phase 3-wire, 3-phase
Aron, 3-phase 4-wire balanced, 3-phase 3-wire balanced
• Adjustable Demand time
• Summer-Winter time application
Applications
This is a MPR-1 series 3-phase mains analyzer. It is a microprocessor based device which
is designed for measuring all parameters of an electricity main; calculate consumptions and
transferring desired parameters with Modbus and I/O outputs.
Thanks to the RTC clock chip and ash memory of the device, the operations performed by
the operator such as interruption records, time and setting changes, reset operations are
recorded in real time. These records can be remotely read and monitored with Modbus RTU
protocol over RS-485 communication line.
The current connection is made by connecting it to a 1A or 5A secondary current
transformer.

7
MPR-1 Product Family
Appearance and Interface
The appearance of the device’s front is as below:
Product Code
3xV, 3xl, Frequency, W
VAr, VA,SP, SQ,SS, kWh,
kVArh, Demand,
Max, Min, Cosj, I nötr
95-270 VAC/DC Besleme
MPR-14S DIN4 128 4MB
MPR-15S-22 DIN4 2 2 128 4MB
MPR-16S-21 DIN4 51 2 1 128 4MB
MPR-17S-23 DIN4 51 2 2 1 128 4MB
12-50 VDC Besleme
MPR-14S-D DIN4 128 4MB
MPR-15S-22-D DIN4 2 128 4MB
MPR-16S-21-D DIN4 51 2 2 1 128 4MB
MPR-17S-23-D DIN4 51 2 2 1 128 4MB
% THD I
Dimensions
% THD V
AyrıAyrı
Number of Samples
Current-Voltage
95-270
RS-485
Digital Input
Digital Output
Analog Output
Harmonics
Relay Output
In one Period
Unbalances
VAC/DC
Memory
X/5,X/1
12-50 VDC

8
Terminal Structures
The terminal structures according to the models are described in this section:
Structure of the MPR-14S Terminal:
Current Terminals: K1, L1, K2, L2, K3, L3
An external current transformer must be used for the 3-phase system connection to these terminals
where the current up to 5A can be input.
Supply Terminals: A1, A2
Please, apply 95-270 VAC/DC (12-50 VDC for MPR-1X-D series) supply connection through
these terminals.
Voltage Terminals: N, L1, L2, L3
Please, apply 3-phase voltage connection through these terminals.
Communication Terminals: A(+), B(-), GND, TR
RS-485 communication terminals are used for Modbus RTU communication connection. A (+)
and B (-) terminals are connected in parallel between devices.
When the communication distance exceeds 10 meters and there are more than one device on
the line, communication instability may occur. In this case;
• A 120 Ohm connection resistor from the device box is installed between the A (+) terminal and
the B (-) terminal,
• Short circuit between the TR terminal and the A (+) terminal.
In this way, line balancing is done.
A(+) B(-)

9
Structure of the MPR-15S-22 Terminal:
DOC terminals is referred to digital output common, digital output reference connection is done
with this terminal.DO1 and DO2 is also referred to 1st and 2nd digital output terminals.
INC terminal is referred to Input Common and it is the digital input reference. IN1 and IN2 are also
referred 1st and 2nd digital input terminals.
Digital Input Terminals: INC, IN1, IN2
As the INC terminal will be the joint point (reference), the IN1 and IN2 inputs are used
as digital inputs between 5-30V. Inputs have 1kV insulation level.
Digital Output Terminals: OC, O1, O2
As the OC terminal will be the joint point (reference), the O1 and O2 terminals are used
as insulated outputs. As it can be seen from the following gure, these Open Collector
outputs should be fed by an external supply for operation.
5-30 VDC
MPR-1X
OC
O1
O2
Relay Coil

10
Structure of the MPR-16S-21 Terminal:
Different from the MPR-16S-21’den these terminals which are used for relay output are the
terminals next to the voltage terminals. They are indicated with the key symbol on the front view.
The terminal structure of the MPR16S-21 model is as in the following:
Digital Input Terminals: INC, IN1, IN2
As the INC terminal will be the joint point (reference), the IN1 and IN2 inputs are used
as digital inputs between 5-30V. Inputs have 1kV insulation level.
This manual suits for next models
8
Table of contents
Other Entes Measuring Instrument manuals

Entes
Entes EVM-R3 User manual

Entes
Entes EVM-3 Instruction manual

Entes
Entes DCV-10 User manual

Entes
Entes EPM-4A User manual

Entes
Entes AKC Series User manual

Entes
Entes MPR-53S User manual

Entes
Entes EVM-15 User manual

Entes
Entes MPR-32 User manual

Entes
Entes ES3 Series User manual

Entes
Entes EVM-R3 User manual

Entes
Entes MPR-4 Series User manual

Entes
Entes MPR-4 Series User manual

Entes
Entes EMG Series User manual

Entes
Entes EMK-01 User manual

Entes
Entes DCA-10 User manual

Entes
Entes MPR-53CS User manual

Entes
Entes EVM-05C User manual

Entes
Entes MPR-3 Series User manual

Entes
Entes EPR-04 Instruction manual

Entes
Entes MPR-45 User manual