Dinel CLM-70 User manual

Before the rst use of the level meter , read the instructions in this manual and keep it
carefully. The manufacturer reserves the right to make alterations without a prior notice.
Capacitive level meter
CLM–70
INSTRUCTION MANUAL
Applies to rmware version 1.0


Contents
1. Safety.............................................................................................................................................4
2. Basic description.........................................................................................................................4
3. Range of application ..................................................................................................................5
4. Variants of sensors ....................................................................................................................5
5. Dimensional drawings ..............................................................................................................6
6. Installation and putting into operation ...............................................................................8
7. Installation instructions ...........................................................................................................8
8. Electrical connection ............................................................................................................. 13
9. Setting elements...................................................................................................................... 14
10. Setting the level meter .......................................................................................................... 15
10.1. Basic settings.................................................................................................................. 15
10.2. Service settings............................................................................................................... 18
10.3. Additional functions ...................................................................................................... 19
11. HART®protocol......................................................................................................................... 21
12. How to install a custom measuring electrode, replace or shorten the electrode..........22
13. Order code................................................................................................................................. 24
14. Failure status indication........................................................................................................ 24
15. Accessories................................................................................................................................ 25
16. Safety, protection, compatibility and explosion proof................................................... 25
17. Use, manipulation, and maintenance ................................................................................ 25
18. Marking of labels ..................................................................................................................... 26
19. Menu structure ........................................................................................................................ 27
20. Technicalspecications ......................................................................................................... 28
21. Error codes ................................................................................................................................ 31
22. Packing, shipping and storage.............................................................................................. 31

CLM–70 © Dinel, s.r.o.
4
Capacitive level meters CLM-70 are compact measuring devices consisting of the level meter
body and a measuring electrode. The level meter body contains measurement electronics
and a display module. The electronics measure the electrical capacity of the electrode system,
which is dependent on the level height. The level meter’s electrical output corresponds to the
capacity (level height) and the measured data are shown on the meter’s display.
The level meter can be adjusted by the display module positioned under the transparent lid.
The level meter has 4–20mA current output with HART®communication. The level meter is
power supplied using a cable connected to the terminal block located under the display and
adjustment module.
Level meters are available in several measuring electrode modications (rod and rope-type
electrodes). Electrodes may be coated with insulation, which is important for their functioning
in the case of adherent, electrically conductive and aggressive media. Rod electrodes are
also available in a version provided with a reference tube or a pair of parallel electrodes for
measuring liquids in non-conductive tanks.
All operations described in this instruction manual have to be carried out by trained
personnel or by an accredited person only. Warranty and post warranty service must
be exclusively carried out by the manufacturer.
Improper use, installation or set-up of the sensor can lead to crashes in the ap-
plication.
The manufacturer is not responsible for improper use, loss of work caused by either
direct or indirect damage, and for expenses incurred at the time of installation or
during the period of use of the level sensors.
To ensure maximum safety of control processes, we have dened the following safety instruc-
tions and information. Each instruction is labelled with the appropriate pictogram.
Alert, warning, danger
This symbol informs you about particularly important instructions for installation and
operation of equipment or dangerous situations that may occur during the installation
and operation. Not observing these instructions may cause disturbance, damage or de-
struction of equipment or may cause injury.
Information
This symbol indicates particularly important characteristics of the device.
Note
This symbol indicates helpful additional information.
Used symbols
1 . safety
2 . basiC desCription

5
© Dinel, s.r.o. CLM–70
• CLM–70_–00 Without electrode; customer makes an electrode himself (types 10
or 30 only) and attaches it to the electrode holder using M8 threaded
connection.
• CLM–70_–10 Uncoated stainless steel rod electrode for level measurement of
electrically non-conductive liquids (oils, diesel fuel) and bulk solids (our,
sand, cement, granulated plastic materials, etc.). Length 0.2 ... 8 m.
• CLM–70_–11 Coated stainless steel rod electrode (PFA) with enhanced resistance
to penetration (diusion) of vapours and gases. For level measurement
of water and other electrically conductive liquids in food processing,
pharmaceutical, and chemical industries. It can be used temporarily for
high-temperature applications (e.g. sanitization with hot steam) or for
volatile aggressive liquids, etc. Length 0.2 ... 3 m.
• CLM–70_–12 Coated stainless steel rod electrode (FEP), suitable for level measure-
ment of water and other electrically conductive liquids. Also suitable for
impure liquids in metallic tanks, concrete sumps, etc. Length 0.2 ... 3 m.
• CLM–70_–13 Semi-coated stainless steel rod electrode (FEP) for level measurement
of electrically non-conductive liquids in environments where partial
condensation of vapours on the electrode may occur. Length 0.5 ... 8 m.
• CLM–70_–20 Uncoated stainless steel rod electrode with reference tube for level
measurement of unpolluted and electrically non-conductive liquids (oil,
diesel fuel, petrol). Length 0.2–3 m.
• CLM–70_–22 Coated stainless steel rod electrode (FEP) with reference tube for level
measurement of clean electrically conductive liquids (e.g. in plastic and
glass tanks) and for higher measuring accuracy. Length 0.2 ... 3 m.
• CLM–70_–30 Uncoated stainless steel rope electrode and weight for level
measurement of bulk solids and powders (sand, our, cement, etc.). The
rope can also be shortened. Length 1 ... 20 m.
• CLM–70_–31 Uncoated stainless steel rope electrode and coated dynamic anchor
for measurement of bulk solids in taller silos. Length 1 ... 20 m.
• CLM–70_–32 Fully coated stainless steel rope electrode and weight (FEP rope
insulation, PTFE weight insulation), designed for level measurement of
water and other electrically conductive liquids. Length 1 ... 12 m.
• CLM–70_–61 Two coated stainless steel rod electrodes (FEP electrode insulation,
PTFE head) for level measurement of aggressive liquids. Length 0.2 ... 2 m.
4 . Variants of sensors
3 . range of appliCation
The capacitive level meters are suitable for continuous level measurement of various liquids
and solid materials. The level meters are resistant to any changes in the atmosphere above the
level (vacuum, overpressure, steam, or dust).

CLM–70 © Dinel, s.r.o.
6
5 . dimensional drawings
CLM–70_–10CLM–70_–00 CLM–70_–13CLM–70_–11, 12
E200 ... E8000
24 97
62
70 4
M16x1,5
27
46
electrode
holder
electrode
thread*
coated
electrode
CLM–70_–61 Variant CLM-70
with a cable gland
for protective hose
High temperature
performance
CLM–70_T**
Process connection
Tri-clamp***
* types of thread: G1" (except type 61),
1″ NPT (except type 61)
** Except type CLM–70_–61
*** Only for type CLM–70_–11(12, 13, 32)

7
© Dinel, s.r.o. CLM–70
CLM–70_–20, 22
reference
pipe
CLM–70_–30CLM–70_–31 CLM–70_-32
compression
spring
hopper wall
(KV–31, PR–31)*
anchor
with ball joint
rope
electrode
coated rope
electrode
coated
weight
rope
electrode
weight
* anchor roll KV–31 or dust proof bushing
PR–31 (see accessories)

CLM–70 © Dinel, s.r.o.
8
BASIC INFO
• The level meters with an insulated electrode are equipped with a protective cap at the
electrode end, which must be removed before installation.
• The level meters are mounted vertically into the upper lid of the tank or hopper or on xing
brackets using a welding ange for a xing nut or a Clamp-type ange.
• When installing the level meter in a metal tank or hopper, the housing is not necessary to
be grounded separately.
• In the case of installation in concrete sumps or silos, the level meter is advisable to
be installed on an auxiliary metal structure (bracket, lid, etc.) and then connected to
a permanently submerged metal object or steel reinforcements in concrete (armouring).
E - electrode length [mm] –
select so that the electrode
end is submerged at least
20 mm below the lowest
measured level
h - distance from the bottom
– at least 50 mm
a - distance from the wall – at
least approx. E/20
d - diameter of the auxiliary
tubular vessel – at least 40
+ E/20 (smaller dimensions
must be discussed)
Auxiliary electrode
width = minimum
30 mm
(required for non-
metal vessels only)
Fig. 1: Installation of level meters with rod electrodes
6 . installation and pUtting into operation
This procedure has the following three steps:
• installation instrUCtions
• eleCtriCal ConneCtion
• settings
7 . installation instrUCtions
METAL AND NON-METAL VESSELS APPLIES TO: CLM-70_-10, 11, 12, 13

9
© Dinel, s.r.o. CLM–70
h- distance from the
bottom – at least 50
mm due to the possible
presence of heavier
fractions (water) in
petroleum products
k - distance from the wall –
arbitrary
Fig. 2: Installation of the level meter with a reference tube
VARIANTS WITH A REFERENCE TUBE APPLIES TO: CLM-70_-20, 22
DEEP METAL AND CONCRETE SILOS APPLIES TO: CLM-70_-30, 32
To be connected to
the armouring
Concrete silo
Metal tank
E- electrode length [mm] – to be selected so that the electrode end is placed at least 20 mm
below the lowest measured level
h- distance from the bottom – at least 100 mm
a- distance from the wall – at least E/20; otherwise, choose as large as possible (as far from
the wall as possible) in the middle between the wall and the vertical drain
Fig. 3: Installation of level meters with rope electrodes

CLM–70 © Dinel, s.r.o.
10
E- electrode length [mm]
t- guide rod length – approx.
500mm
p- compression spring length
– approx. 200 mm
c- distance from the hopper
axis (choose the minimum
one, if possible)
Anchor welding cylinder
(mat. 11375) or the
dust-tight bushing to the
hopper casing
Fig. 4: Installation of the level meter with arope electrode and anchor
E – electrode length [mm] –
submerge the electrode
end at least 20 mm below
the lowest measured level.
h – distance from the bottom
(at least 30 mm)
a – distance from the wall (at
least E/20)
Fig. 5: Installation of the level meter with a reference electrode
ROPE ELECTRODE WITH AN ANCHOR APPLIES TO: CLM-70_-31
AGGRESSIVE LIQUIDS, NON-METAL VESSELS APPLIES TO: CLM-70N-61
Table of contents
Other Dinel Measuring Instrument manuals

Dinel
Dinel ULM-53 series User manual

Dinel
Dinel ULM-53 series User manual

Dinel
Dinel CLM-36 User manual

Dinel
Dinel ULM-53 series User manual

Dinel
Dinel CLM-36-10 User manual

Dinel
Dinel DLM-35 User manual

Dinel
Dinel ULM - 54 User manual

Dinel
Dinel ULM-53 series User manual

Dinel
Dinel ULM-53L User manual

Dinel
Dinel ULM-70 Series User manual