DFE TI-11 User manual

INSTRUCTION MANUAL
MODEL TI-11
DOC 801-0545 R2

217 Pickering Road
Rochester, NH 03867-4630 U.S.A.
For assistance, please call:
TECHNICAL SERVICE - Installations, Start-Up, Troubleshooting, Repairs, Field
Service, Returns.
CUSTOMER SERVICE - Replacement Parts, Individual Products, Questions
about Orders, Manuals.
SALES - Product Information, Systems Application Questions,
Placing orders for standard products and special
systems.
Telephone: (603) 332-6150 Fax: (603) 332-3758
E-mail: info@dfe.com Internet: www.dfe.com
©2003 Dover Flexo Electronics, Inc. All rights reserved. Dover Flexo Electronics has made reasonable effort to ensure accuracy of this
document. However NO WARRANTY, whether expressed or implied, is given regarding the completeness or correctness of information in
this document. Dover Flexo Electronics shall not be liable for damages of any kind arising from the use or misuse of this document. Dover
Flexo Electronics reserves the right to make changes, additions, and deletions to this document without notice and without obligation.

TABLE OF CONTENTS
SECTION ONE DESCRIPTION PAGE
1.1 General Description 1
1.2 Outputs 1
1.3 TI-11 Exploded View 1
1.4 Specifications 2
1.5 Standard Features
0-10 Volt Tension Output 2
Meter Damping 2
Power Voltage Selection 2
4-20ma Tension Output 2
0-1mA Tension Output 2
Status Lights 2
Diagnostic Connector 2
1.6 Options
230 Volt Power 2
Extended Range 2
0-100mv Tension Output 2
0 to -10V Tension Output 2
Isolation From Earth Ground 3
1.7 Accessories 3
1.8 Front Panel 3
SECTION TWO INSTALLATION
2.1 Dimensions 4
2.2 Installing the Circuit Card 5
2.3 Electrical Connections 6
2.4 Electrical Connections to Plug-in Adapter 6
SECTION THREE CALIBRATION AND SETUP
3.1 Mechanically Zero The Tension Meter 7
3.2 Calibrate The Meter For Accuracy 7
3.3 The TI-11 Circuit Card 8
3.4 Power Voltage Selection 8
3.5 Tension Meter Outputs 9
3.6 4-20mA Current Outputs 9
3.7 High Voltage Outputs 9
3.8 Meter Damping 9
3.9 Extended Range 9
3.10 Isolation From Earth Ground 9
SECTION FOUR OPERATING INSTRUCTIONS 10
SECTION FIVE CARE & MAINTENANCE 11

SECTION SIX TROUBLESHOOTING GUIDE
6.1 Troubleshooting Procedure 12
6.2 Diagnostic Connector 12
SECTION SEVEN REPLACEMENT PARTS 13
APPENDICES
APC Board and DIP Switch Settings 14
BElectrical Connections 15
CTransducer Electrical Connections 16
DTypical Tensions 20
TERMS AND CONDITIONS OF SALE 21
DECLARATION OF CONFORMITY 22
INDEX 23
LIST OF ILLUSTRATIONS
FIGURE DESCRIPTION PAGE
1 TI-11 Exploded View 1
2 Front Panel 3
3 Dimensions 4
4 Optional Plug-in Adapter Dimensions 4
5 Optional Analog Meter Dimensions 5
6 Meter Mounting Dimensions 5
7 Electrical Connections 6
8 Electrical Connections to Plug-in Adapter 6
9 Web Path 7
10 TI-11 Circuit Card 8
11 Power Selection Switch 8
12 Diagnostic Connector 12
13 TI-11 PC Board 14
14 Electrical Connections, Standard 15
15 Optional Electrical Connections 15
16 Transducer Wiring, Models C and UPB 16
17 Transducer Wiring, Model RF 17
18 Transducer Wiring, Models TR and NW 18
19 Transducer Wiring, Model LT 19

1
SECTION 1 DESCRIPTION
1.1 GENERAL DESCRIPTION
The TI-11 dual tension indicator is a device to output and display tension measurements. It can be used
with any type of DFE tension transducer to display actual web tension on an analog or digital meter for
reference by the machine operator. It also has voltage and current outputs that are proportional to tension,
and which can be connected to tension recorders, variable speed drive systems, computers, and other
devices for tension control or display purposes. The TI-11 contains two independent tension indicator
circuits on one card. Each has its own calibration adjustments and outputs. The card is an
IEC/ANSI/IEEE type 2 plug-in unit for installation in a standard size 3U 19 inch rack.
1.2 OUTPUTS
Each tension indicator circuit has three outputs.
A. 0 to 1mA (standard) or 0 to 100mV, selectable. Usually used for a tension indicating meter.
B. 4 to 20 mA
C. 0 to +10 Vdc (standard) or 0 to -10 Vdc, selectable and adjustable for 3.5 to 12 Vdc
1.3 TI-11 INDICATOR EXPLODED VIEW
Figure 1 - TI-11 INDICATOR- EXPLODED VIEW

2
1.4 SPECIFICATIONS
Power Input . . . . . . . . ................... 115 Volts 60/50Hz single phase @ 1 Amp
230 Volts 60/50Hz single phase @ 1/2 Amp
Earth Ground Connection ................. Circuit-commonconnected to earth ground by the AC
power ground connection.
TensionSignalOutputs .................. 0to+10Vdc@2mAOR4-20mA
. [ or 0 to -10 Vdc @ 2mA Optional]
TensionMeterOutputs ................... 0to1mA
[ or 0 to 100mV @ 10mA , or 0 to +10Vdc @ 2mA
Optional]
Weight ............................ 1.15 lbs. (0.5 Kg)
TransducerSignalIn..................... 500 mVdc at rated load
TransducerExcitation.................... 5Vdc (10VdcwithXRoption)
MatingCircuitCardConnector ............ VERO#17-2873H or equivalent
MatingDiagnosticConnector.............. MaleDB15. AMP #745494-6 or equivalent
Zero(Tare)Range ...................... 95%oftransducerrating,minimum
CalibrationRange....................... 25:1
TemperatureRange...................... 32°Fto104° F (0° C to 40° C)
SystemAccuracy ....................... 1-3%typical
TensionMeter(optional) ................. Analog,2%,1mA,48ohm
StandardTensionMeterScales ............ 0-1,5,10, 25, 50, 100, 150, 250, 500, 1000
(tension meter is optional)
1.5 STANDARD FEATURES
SOME OF THESE FUNCTIONS REQUIRE CONFIGURING OR EXTERNAL WIRING. REFER TO
SECTION 3 FOR CONFIGURING AND SECTION 2 FOR WIRING.
•0 to +10 Volt dc Tension Output. Proportional to web tension. Used as an input to other control
systems, computers or data collection devices. Adjustable.
•Meter Damping. Minimizes vibration of the optional analog tension meter needle.
•Power Voltage Selection. The TI-11 Indicator is designed to operate on two ranges of AC power;
115 Volts 60/50 Hz, and 230 Volts 60/50 Hz. A switch on the circuit board selects between the two.
•4-20mA Tension Output. Used as an input to control systems, computers, or data collection devices.
•0-1mA Tension Output.Typically used for an input to a tension readout meter.
•Status Lights. Shows status of power supplies.
•Diagnostic Connector. Located on front panel. Permits inputs and outputs to be checked easily.
1.6 OPTIONS (The option code is shown in parentheses)
SOME OF THESE OPTIONAL FUNCTIONS REQUIRE CONFIGURING OR EXTERNAL WIRING.
REFER TO SECTION 3 FOR CONFIGURING AND SECTION 2 FOR WIRING.
•230 Volt Power (230V). 230 volt 50/60 Hz power input.
•Extended Range (XRE). 10Vdc excitation for transducers. Allows measurement of much lower
tension than usual. Transducers must also have the XR option. WARNING! If one tension indicator
circuit requires XR, then the other must use it too. Both circuits must use the same transducer voltage.
Both sets of transducers must have the XR option even if only one requires it for tension range.
•0-100 mV Tension Output (100MV). Alternate to the standard 0-1mA meter output.
•0 to 10 Vdc Tension Output (10V).Alternate to the standard 0-1mA meter output.
•0 to -10 Vdc Tension Output (-10V). Replaces the standard 0 to +10 Volt dc output.

3
•Isolation From Earth Ground (IFEG). Removal of a jumper allows the TI-11 to float at a variable
electrical potential above earth ground. The jumper disconnects the circuit- common pc board trace
from the earth-grounded pin on the electrical connector. This can eliminate ground-loop problems or
output polarity contentions between the TI-11 and devices connected to its outputs. However, if the
jumper is removed, one of the devices connected to the TI-11 outputs MUST be grounded. This will
prevent the TI-11 from floating far enough above ground potential to cause problems. If no ground
connection exists, it is possible that the transducers may short-circuit to ground at the strain gages. The
result being electrical failure of the transducers. Must apply to both indicator circuits.
1.7 ACCESSORIES
•Analog Tension Meter (AM). 1mA, 48 Ohm movement. Must be remotely installed. A separate
meter is required for each tension circuit. DFE part #722-1385.
•Nonstandard Meter Scale (NMS). Any nonstandard analog meter scale. See Specifications, page 2,
for standard scales.
•Type 5 Plug-in Adapter. Plug the TI-11 into this adapter instead of a 19 inch rack. Terminal strips for
hard-wired connections. Install the unit in your own enclosure.
1.8 FRONT PANEL
Figure 2 - FRONT PANEL

4
SECTION 2 INSTALLATION
2.1 DIMENSIONS inches (mm)
Figure 3 - DIMENSIONS
DIMENSIONS OF OPTIONAL PLUG-IN ADAPTER inches (mm)
Figure 4 - OPTIONAL PLUG-IN ADAPTER

5
DIMENSIONS OF OPTIONAL ANALOG TENSION METER inches (mm)
Figure 5 - OPTIONAL ANALOG METER
MOUNTING DIMENSIONS FOR ANALOG METER inches (mm)
Figure 6 - METER MOUNTING DIMENSIONS
2.2 INSTALLING THE CIRCUIT CARD
The TI-11 is plugged into a standard 19 inch rack having an opening 3U high by 14HP wide. The
optional plug-in adapter may also be used.
Note: The TI-11 has been tested to meet the EMC directive, and for that compliance, the unit must be
installed in a shielded enclosure and used with shielded cables (Dover cables are shielded).

6
2.3 ELECTRICAL CONNECTIONS
Refer to the drawing below for electrical connections to the rear connector of the TI-11.
Figure 7 - ELECTRICAL CONNECTIONS
2.4 ELECTRICAL CONNECTIONS TO PLUG-IN ADAPTER
Figure 8 - ELECTRICAL CONNECTIONS TO PLUG-IN ADAPTER