2Specification
MAN104D-V1.4
2. SPECIFICATION
General
Display: LCD which is continuously powered.
Resettable Total: 7 digits with 10mm (0.4") high digits. Resettable
from front panel.
Accumulated Total: Displayed when the ACCUM TOTAL button is
pressed.
Rate: 4½ digits with 8.5mm (0.33") high digits.
K-factor: The pulses per unit of measure (eg. pulses/gallon)
is programmable in the range 0.000001 to
999,999.
Decimal Points: Decimal point positions are fully programmable
for both rate and total.
Timebase: Rate can be displayed in units per second, minute,
hour or day.
Frequency Range: 0.01Hz to 10kHz.
Signal Type: Link settable for sinewave (15mV P-P minimum),
open collector, reed switch, pulse or Namur
proximity switch.
Scale: The 4mA and 20mA points are programmable.
Resolution and Linearity: 0.05% of span.
Accuracy: 0.05% of span at 25°C.
0.1% (typ) of span, full temperature range.
Update Time: 0.5 second.
Connection: Two-wire.
Loop Power Supply: 9-28 Volts.
Supply Backup: 2 x User replaceable Lithium battery.
Outputs: Two open collector outputs suitable for driving DC
solenoids or external relays. The outputs can be
programmed to provide high and low flow alarms
or pulse output and low flow alarm.
Switching Power: 750mA. 30VDC maximum.