Power supply 24VAC/VDC
Consumption 1.5 W Max ; 0.8 W avg
CO2 sensor Infrared Sensor with lifetime of 15 years
ABC Logic Self Calibration (default: effective)
CO2measuring range 0~2,000ppm
Accuracy@25℃(77℉),2000ppm ±40ppm + 3% of reading or ±75ppm (whichever is greater)
Response time <2 minutes for 90% step change
Warm up time for each turning-on 2 hours (first time) 2 min (operation)
6 LED lights
1st green light on as CO2 measurement≤600ppm
1st and 2nd green lights on as CO2 measurement>600ppm and≤800ppm
1st yellow light on as CO2 measurement>800ppm and≤1,200ppm
1st and 2nd yellow lights on as CO2 measurement>1,200ppm and≤1,400ppm
1st red light on as CO2 measurement>1,400ppm and≤1,600ppm
1st and 2nd red lights on as CO2 measurement>1,600ppm
On/Off output for control CO2 level <240VAC/30VDC 3A switching current (resistance load),
Operation conditions 0~50℃(32~122℉); 0~95%RH, non condensing
Storage conditions 0~50℃(32~122℉);
Dimensions 100mm×80mm×28mm (H X W X D)
Net weight 180g
Installment standard 65mm×65mm (2”×4”) wire box
Housing and protection class PC/ABS fire proof material with IP30
Standard approval CE-Approval
Version TSM-CO2-1A1R-ST02_65 (SE)
Mounting and Wire Connection
Notice the supply power voltage of the detector: 24VAC. Do not install the detector on voltages
higher than marked on the detector.
Firstly, prepare a flat head screwdriver and put it inside of the hole on the top of the detector
housing following step 1, and then open the cover from step 2 to step 4 in next page fig.1.
Mount the wall plate first, dimensions see next page fig. 2.
Connect wires to terminal strips, (see fig. 3).
Follow step 5 to step7 in fig. 4 to close the cover.
Tongdy CO2 Monitor with Relay (TON-0007)
UUsseerrMMaannuuaall
Specifications