BLUCHER Connected Roof Installation and operating instructions

USER MANUAL & INSTALLATION GUIDE
BLÜCHER®Connected Roof
SIPHONIC
ROOF
GREEN
ROOF
BLUE
ROOF
GRAVITY
ROOF
INTELLIGENT
ROOF
BALCONY
& PARKING
REV. 03 / APRIL 2021

2 BLÜCHER®CONNECTED ROOF - REV. 02 - MARCH 2021
Content
1 Introduction ................................................................................................................................... 3
2 Scope of delivery........................................................................................................................... 4
3 Safety instructions and regulations............................................................................................. 4
4 Technical specication................................................................................................................. 5
4.1 Product overview ..................................................................................................................... 5
4.2 Gateway specications ............................................................................................................ 6
4.3 Monitor specications .............................................................................................................. 7
5 Mechanical installation................................................................................................................. 7
5.1 Gateway .................................................................................................................................. 7
5.2 Monitor ................................................................................................................................. 10
6 Commissioning ........................................................................................................................... 12
6.1 SD card ................................................................................................................................. 12
6.2 Conguration le .................................................................................................................... 13
7 Functions ................................................................................................................................. 14
7.1 Display ................................................................................................................................. 14
7.1.1 Menu structure.............................................................................................................. 14
7.1.2 Menu content................................................................................................................ 15
7.1.3 Display information ........................................................................................................ 16
7.2 Info button ............................................................................................................................. 16
7.3 Relay ................................................................................................................................. 17
7.4 Measurement values.............................................................................................................. 18
7.4.1 Water Level ................................................................................................................... 18
7.4.2 Temperature.................................................................................................................. 18
7.5 Diagnostics............................................................................................................................ 18
7.5.1 Offset ............................................................................................................................ 18
7.5.2 Systems Diagnostics ..................................................................................................... 20
7.6 Monitor modes ...................................................................................................................... 20
7.6.1 Operation Mode ............................................................................................................ 20
7.6.2 Test Mode ..................................................................................................................... 20
7.7 Power up / reboot.................................................................................................................. 20
8 Modbus interface ........................................................................................................................ 21
8.1 Supported function codes...................................................................................................... 21
8.2 Modbus Termination .............................................................................................................. 21
9 Gateway software update .......................................................................................................... 21
10 Service and maintenance........................................................................................................... 22
11 Troubleshooting .......................................................................................................................... 23
12 Disclaimer ................................................................................................................................. 24
13 Appendix – Conguration le parameters................................................................................ 25
14 Appendix – Modbus tables......................................................................................................... 26

REV. 02 - MARCH 2021 - BLÜCHER®CONNECTED ROOF 3
1 Introduction
Thank you for buying this BLÜCHER®Connected Roof product. We hope that it will live up to
your expectations and make monitoring your roof performance easier.
All documents related to this product can be found at www.blucher.com.
BLÜCHER®Connected Roof allows you to easily supervise the performance of your roof.
The system is designed to detect a possible blocked drainage system before any major
issues occur.
The system consists of Gateway(s) and Monitors. The Monitor is mounted next to the roof
drain and collects water level- and temperature data. The Monitor sends a wireless signal to
the Gateway.
The Gateway functions as a master to the Monitors with one Gateway monitoring up to 16
Monitors. Additional Gateways must be installed if you have more than 16 Monitors in the
system.
You can set the system up in different ways to receive the information.
1) The information can be read directly on the Gateway display.
2) You can use the relay output to trigger a visual or an acoustic alarm.
3) You can use the Modbus signal to communicate directly with the Building Management
System (BMS).
4) You can apply a GSM-gateway to receive the information on your mobile phone or via
email.
This user manual and installation guide describes the installation and start-up for BLÜCHER®
Connected Roof Gateway item number #900.000.400, and how to connect the Connected
Roof Monitor item number #900.100.400 to the Gateway.
Prior to installation, please read these installation and operating instructions. Installation
and operation must comply with local regulations and accepted codes of good practice.
Receives signal
from roof monitors
Sending signal
to Gateway
Building Management
System
Climate change

4 BLÜCHER®CONNECTED ROOF - REV. 02 - MARCH 2021
2 Scope of delivery
Please carefully check all components in the box. Should something be missing, contact your
dealer at once.
Gateway:
Item Description Quantity
Gateway Connected Roof Gateway 1
Power supply 5VDC, 1A 1
SD Card Micro SDHC, Class 4, 4 GB 1
Antenna 868 MHz SMA connection 1
Quick start Getting started instructions 1
Monitor:
Item Description Quantity
Monitor Connected Roof Monitor 1
Mounting bracket Mounting frame for Monitor 1
Quick start Getting started instructions 1
Optional accessories:
Item Description
External antenna 868 MHz SMA connection
w/ 3 m cable
Must to be ordered
separately, item number
(900.900.000)
3 Safety instructions and regulations
Installation must be suitable for the on-site conditions and comply with the local regulations
and technical rules.
Please note that alterations, or improper repairs to the product are not permitted. If alterations
or improper repairs are carried out, the CE-mark and the manufacturer’s warranty will
become invalid.
CAUTION
Correct, reliable operation of the product requires proper transport, storage, positioning
and assembly as well as careful operation. Only qualified personal should install or operate
the device.

REV. 02 - MARCH 2021 - BLÜCHER®CONNECTED ROOF 5
4 Technical specication
4.1 Product overview
GATEWAY
1. Antenna
2. Info button
3. SD card
4. Input for power supply
5. Relay output
6. Internal power supply
7. Modbus
8. Jumper switch
MONITOR
9. Mounting bracket
10.Level sensor
11.Monitor ID
1
2
3
4
223 mm
80 mm 567
8
10
11
9

6 BLÜCHER®CONNECTED ROOF - REV. 02 - MARCH 2021
4.2 Gateway specications
Power supply
Voltage 5V DC 1A
Nominal power 0,5 W
Electrical protection class Class 3
Wireless
Frequency 868 MHz
Antenna connector SMA
Signal range Up to 1500m in free line of sight
User input
Push button 1
Display
Type 0.96” OLED
Size 128*64 dot
SD card
Type MicroSDHC Class 4 or higher
Size >4 GB
Relay
Type 1RT NO/NC
Load limit 230VAC 5A
Connection 3 pin screw terminals (Max 1.5mm²)
MODBUS
Physical Layer RS485
Baud rate Up to 115200 Bauds
Connection 3 pin screw terminals (Max 1.5mm²)
Termination Yes, ON/OFF jumper conguration
Cable glands
Size PG7 (diameter 2.5-6.5mm)
Enclosure
IP protection IP 30
Material ABS
Size 120 x 65 x 40mm (without antenna and cable glands)
Mounting hole Ø4 mm
Environmental
Working temperature -10°C - 55°C
Storage temperature -30°C - 80°C
Humidity Below 80% non-condensing

REV. 02 - MARCH 2021 - BLÜCHER®CONNECTED ROOF 7
4.3 Monitor specications
Power supply
Battery Lithium battery LS 14500 3.6V (internal) AA
Battery life Up to 10 years
Level Sensor
Sensor electrodes Stainless A2
Enclosure
IP protection IP68
Material Anti-UV PC
Size 120 x 65 x 60mm
Environmental
Working temperature -35°C - 85°C
Storage temperature -35°C - 85°C
5 Mechanical installation
5.1 Gateway
We recommend that the Gateway is placed centrally in relation to the Monitors, and in line
of sight to ensure the best possible signal strength. Please note that obstructions such as
concrete and metal can reduce the signal range.
Do not install the BLÜCHER®Connected Roof Gateway in areas with a risk of water exposure and high humidity levels.
The ambient temperature should be in the range between -10 °C and 55 °C and the humidity below 80% non-condensing.
Please consider the material/thickness of the gateway enclosure for maximized signal strength.
Temperature
-10 – 55°C
Humidity
< 80% - non
condensing

8 BLÜCHER®CONNECTED ROOF - REV. 02 - MARCH 2021
Mounting instructions
To mount the enclosure:
60 mm
Min. 50 mm
35 mm
To acces
Micro SD card
Unscrew the 4 no. screws on the front cover, then remove
the front cover to access the mounting holes. The mounting
holes are Ø4 mm, and screws are not included.
Ensure there is enough free space around the unit to
enable access to the SD card, and to allow space for
the antenna and cable glands.
If there is no room for the gateway, because of the antenna, or if the placement of the gateway will disturb the signal to the
antenna, an external can be an option. Item number #900.900.000
The external has a magnetic socket and can be mounted directly on metal. If preferred it can also be glued.

REV. 02 - MARCH 2021 - BLÜCHER®CONNECTED ROOF 9
Electrical wiring
In the bottom of the Gateway you can make three different electric wire connections - Relay,
Internal power and Modbus. Below you will nd the different ways to set it up.
Relay
Relay can be wired as NO or NC.
Internal power
As an alternative to the power
connector on the right side of the
Gateway, a 5V DC power supply
can be wired directly to the power
terminals.
Modbus
If connection to a Modbus RTU BMS
system is required, a suitable RS485,
cable must be used and connected to A,
B, GND. If connection to a Modbus RTU
BMS system is required, a suitable RS485
cable must be used and connected to A,
B, GND.

10 BLÜCHER®CONNECTED ROOF - REV. 02 - MARCH 2021
5.2 Monitor
We recommend that one Monitor is installed next to each drain on your roof. Monitors should
be installed at the primary drainage system and not at emergency outlets and drains. This
gives the system the best conditions to evaluate the performance of the drainage system.