Alderon Industries 7039 User manual

USER GUIDE
PART NUMBER:
7039
Cast Iron Cable Weight
Control and Pump Switches

Contents
Introduction................................................................................................................................................................. 3
Safety Guidelines ................................................................................................................................................... 3
Product Included .................................................................................................................................................... 4
Features ................................................................................................................................................................. 5
Installation .................................................................................................................................................................. 6
Installing Float Switch Cable .............................................................................................................................. 6, 7
Installing Float Switch Cable in Application Area ................................................................................................... 8
Test ing .................................................................................................................................................................... 8
General Operation...................................................................................................................................................... 9
Narrow Angle Control or Pump Switch Information ............................................................................................... 9
Medium Angle Control Switch Information........................................................................................................... 10
Medium Angle Pump Switch Information ............................................................................................................. 10
Wide Angle Control or Pump Switch Information................................................................................................. 11
Multiple Float Application Example ...................................................................................................................... 11
Troubleshooting ........................................................................................................................................................ 12
Specications ........................................................................................................................................................... 13
Warranty Information ................................................................................................................................................ 14
Company Information ............................................................................................................................................... 16
Cast Iron Cable Weight - USER GUIDE

Alderon Industries™ - Leading Edge Control Products | 3
Cast Iron Cable Weight - USER GUIDE
Introduction
The cast iron cable weight is used as a pivot point for the activation of a control or pump oat switch. Typically used in a tank where
the oat switch cable is suspended from a mounted oat bracket or per local codes. This product can be used with different types
of oat switches for a variety of applications, including but not limited to: lift stations, septic tanks, holding tanks, pump chambers,
and water tanks for liquids up to 200° F. Made with zinc plated cast iron.
Safety Guidelines
Before proceeding with the installation or operation of this product, read all instructions thoroughly, as well as complying with
all federal, state and local codes, regulations, and practices. This product must be installed by qualied personnel familiar with
all applicable local electrical and mechanical codes. Refer to the National Electrical Code (NFPA 70). Failure to properly install
and test this product can result in personal injury or equipment malfunction.
WARNING
1. DISCONNECT POWER when installing or servicing the product. Failure to disconnect all power sources could result in
serious injury or death.
2. NEVER enter a ooded space without proper Personal Protective Equipment (PPE). Always wear dielectric rubber boots
and other applicable protective equipment when water is on the oor and you must service an energized pump, alarm
system, or product.
3. DO NOT enter the water if the water level is higher than that of the protection your PPE offers or if your PPE is not
watertight.
4. DO NOT use this product with or near ammable liquids.
5. DO NOT install this product in locations classied as hazardous or in explosive atmospheres as dened by any applicable
electrical safety code.

4 | Alderon Industries™ - Leading Edge Control Products
Cast Iron Cable Weight - USER GUIDE
Product Included
(1) Cast Iron Cable Weight
The cast iron cable weight is used as a pivot point for the desired
activation level of the oat switch.
(2) Screws
Secures the cast iron cable weight to the oat switch cable.
The standard product will include: (1) Cast Iron Cable Weight and (2) Screws.
1
2

Alderon Industries™ - Leading Edge Control Products | 5
Cast Iron Cable Weight - USER GUIDE
Features
Refer to the illustration below to reference the feature descriptions provided.
(1) Cable Weight Halves - The cast iron cable weight is
separated into two halves to afx around the oat switch
cable. Made from zinc plated cast iron.
(2) Screw Holes - Two screw holes are located on the front
outside portion of the cable weight.
(3) Threaded Screw Holes - Two threaded screw holes are
located on the inside back portion of the cable weight.
(4) Screws - Two screws are included to fasten both halves
of the cable weight together.
(5) Cable Slots - The slots are located on both inside halves
of the cable weight, sized for 18 AWG to 14 AWG type oat
switch cables and the bottom side of the weight acts as a
pivot point for the control or pump oat switch.
1 1
2
3
4
5
5

6 | Alderon Industries™ - Leading Edge Control Products
Cast Iron Cable Weight - USER GUIDE
Installation
DISCONNECT ALL POWER SOURCES WHEN INSTALLING OR SERVICING THIS PRODUCT. FAILURE TO
TURN OFF ALL POWER SOURCES COULD RESULT IN SERIOUS INJURY OR DEATH.
Installing Float Switch Cable
STEP 1: REMOVE SCREWS
Remove the two screws from the front of the cable weight by
unscrewing until they release from the screw holes (1A) and pull
directly away (1B).
STEP 2: TETHER LENGTH
Determine the desired activation level, place oat switch cable
in the cable slot on the bottom half of the cable weight while the
top half is removed, and tether oat switch to the appropriate
length. Refer to the instructions that came with the oat switch
for recommended tether length guides to determine activation
or pumping range.
Note*: When installing the cable weight, make sure the narrow
end is facing up to ensure proper operation of the oat switch
and prevent debris from collecting on the cable weight.
Control Switches (Narrow Angle)
Minimum recommended tether length is 6 inches
Pump Switches (Wide Angle)
Minimum recommended tether length is 6 inches
1A
1B
(*) Correct installation position
example, narrow end up.
Tether
Length

Alderon Industries™ - Leading Edge Control Products | 7
Cast Iron Cable Weight - USER GUIDE
Installing Float Switch Cable (continued)
STEP 3: SECURE FLOAT SWITCH CABLE
To secure oat switch cable to the cable weight, place the top half of the cable weight over the oat switch cable and align the
screw holes to the bottom half of the cable weight (3A). Tighten the two screws so both halves of the cable weight are snug
against the cable (3B). Perform a pull test, if the oat switch cable slips, tighten the screws until securely fastened to prevent
slipping of the cable, this will maintain an accurate activation level (control switches) or pumping range (pump switches).
3A
3B

8 | Alderon Industries™ - Leading Edge Control Products
Cast Iron Cable Weight - USER GUIDE
Installing Float Switch Cable in Application Area
STEP 1: INSTALL AT DETERMINED ACTIVATION LEVEL
Suspend the oat switch with cable weight at the determined
activation level using a mounted oat bracket or per local codes.
STEP 2: WIRING
Wire the oat switch per manufacturer’s instructions.
Testing
STEP 1: TESTING THE ACTIVATION LEVEL
Check the installation of the oat switch by cycling the oat on
and off to ensure proper system operation.
Activation Range
Activation Level
Deactivation Level
(narrow angle control switch, normally open example)
MOUNTED FLOAT BRACKET
Activation Level
(narrow angle control switch, normally open example)

Alderon Industries™ - Leading Edge Control Products | 9
Cast Iron Cable Weight - USER GUIDE
General Operation
The cast iron cable weight is used as a pivot point for the activation of a control or pump oat switch. Typically used in a tank
where the oat switch cable is suspended from a mounted oat bracket to monitor liquid levels. The examples shown in this
section indicate the total operating angles for Alderon™ oat switches.
Note: Other brands of oat switches may have different total operating angles or activation/deactivation levels above/below
horizontal. Refer to the instructions that came with the oat switch for complete operation information.
▪ 20° total operating angle
Normally Open:
▪ Activates 15° above horizontal
▪ Deactivates 5° below horizontal
Normally Closed:
▪ Activates 5° below horizontal
▪ Deactivates 15° above horizontal
Normally Open - High Level Alarms or Pump Down (empty) applications
Normally Closed - Low Level Alarms or Pump Up (ll) applications
Narrow Angle Control or Pump Switch Information
(normally open example)

10 | Alderon Industries™ - Leading Edge Control Products
Cast Iron Cable Weight - USER GUIDE
▪ 60° total operating angle
Normally Open:
▪ Activates 15° above horizontal
▪ Deactivates 45° below horizontal
Normally Closed:
▪ Activates 45° below horizontal
▪ Deactivates 15° above horizontal
Normally Open - High Level Alarms or Pump Down (empty) applications
Normally Closed - Low Level Alarms or Pump Up (ll) applications
Medium Angle Control Switch Information
(normally open example)
(normally open example)
▪ 50° total operating angle
Normally Open:
▪ Activates 45° above horizontal
▪ Deactivates 5° below horizontal
Normally Closed:
▪ Activates 5° below horizontal
▪ Deactivates 45° above horizontal
Normally Open - High Level Alarms or Pump Down (empty) applications
Normally Closed - Low Level Alarms or Pump Up (ll) applications
Medium Angle Pump Switch Information