
Met One BAM 1020 SOP page 8 of 53
4. Heater Kit: The inlet heater kit includes a heater block that slides over the lower end of the
inlet tube (inside the station). When installed, the heater will cover approximately four
(4) inches in length of the inlet tube. The installed heater should be a minimum of two (2)
inches away from any object at either end of the heater, such as the instrument rack or ceiling.
These measurements suggest that the minimum distance between the BAM-1020 central
unit and the ceiling should be NO less than eight (8) inches.
5. Inlet: The straight, vertical inlet tubing of the BAM-1020 limits the placement of the
BAM-1020 central unit. The BAM-1020 inlet tubing is a 1 5/16" OD, 8' long rigid
aluminum tube. The lower end of the inlet tube inserts directly into the top of the BAM-1020
housing, the other end points horizontally upward through all roofing material and above
the roof line. The selected particle size inlet(s) are mounted on the upper end of the inlet
tube. The BAM-1020 FRM PM10 head should be installed so that its height is equal to the
same inlet height of the PM2.5 FRM or HiVol SSI filter sampler heads. In addition, the
sampler inlet must be between 2 meters above the roof line and between 2 to 15 meters above
the ground. Provisions must be made during installation to allow future removal,
maintenance and re-installation of all equipment.
6. Specifications: Specifications for siting a BAM-1020 will mirror the Federal EPA PM2.5
criteria listed in the Code of Federal Regulations (40 CFR, Part 58).
2.4 Installing BAM-1020 Central Unit:
The BAM-1020 can be rack mounted, placed on a table, shelf or other flat surface. As with all
instrumentation installations, the racks, table or fixture must be secure and the overall installation
must protect both the instrument and personnel.
Because the BAM-1020 connector fitting for the inlet tube is located on top of the BAM-1020
central unit, installation of the BAM-1020 does not allow for other instruments to be mounted
above it. However the BAM-1020 is installed, space for the vertical position of the inlet tube must be
taken into account.
2.5 Drilling Inlet Tube Hole:
Applications may vary due to structural and material makeup. Forethought may help alleviate
problems and frustration. After locating a suitable place for the BAM-1020 monitor, the holes for
the BAM inlet tube can be drilled. Protect instruments from falling debris. The inlet support
hardware should include a rooftop mounting plate for stations with a flat roof. The mounting plate
has a circular ridge that protrudes beneath the surface and therefore a 2¼” diameter recess must
be made on top of the roof in order to accommodate the ridge.
Inside station ceiling hole: The hole on the inside of the station should only be large enough to
accommodate the outside diameter of the inlet tube. Use a 1 3/8" diameter hole saw. A plumb
bob can help locate the best position on the ceiling of air monitoring stations. Drill a 1 3/8" hole
vertically through the ceiling directly above the BAM-1020 monitor inlet spout. STOP drilling
when the tip of the guide bit just begins to poke through the top of the roof. The drill bit hole will be
used as a guide when drilling down from above and therefore do NOT drill a 1 3/8" hole all the way
through the roof.
Outside roof top hole: Relocate to the topside of the roof after drilling the 1 3/8" inside ceiling
hole from underneath (remember to only drill until the hole saw bit just pokes through the roof
top). Using the hole created by the guide drill of the 1 3/8” hole saw bit, drill downward with a 2 ¼”