Jung Standard 3361 WW User manual

Presence detector
Presence detector Standard
Art. no.: 3361 WW
Presence detector Standard
Art. no.: 3361 AL
Presende detector Universal
Art. no.: 3361-1 WW
Presende detector Universal
Art. no.: 3361-1 AL
Operating instructions
1 Safety instructions
Electrical devices may only be mounted and connected by electrically skilled persons.
Serious injuries, fire or property damage possible. Please read and follow manual fully.
Do not press on the sensor window. Device can be damaged.
The device is not suitable for use as a burglar alarm or other alarm.
These instructions are an integral part of the product, and must remain with the end customer.
2 Battery safety instructions
This device or its accessories are supplied with batteries in the form of button cells.
DANGER! Batteries can be swallowed. This can lead directly to death by suffocation. Danger-
ous substances may cause severe internal burns leading to death within 2 hours.
Keep new and used batteries away from children.
Do not use devices if the battery compartment does not close securely and keep away from
children.
If you suspect that a battery has been swallowed or is in any orifice of the body, seek immediate
medical attention.
WARNING! Improper handling of batteries can result in explosion, fire or chemical burn due to
leakage.
Do not heat or throw batteries into fire.
Do not reverse polarity, short-circuit or recharge batteries.
Do not deform or disassemble batteries.
Replace batteries only with an identical or equivalent type.
Remove empty batteries immediately and dispose of in an environmentally friendly manner.
1 / 11
82585623 23.07.2019
j0082585623

Presence detector
3 Device components
Figure1: Device components
(1) Supporting frame
(2) Integrated bus coupling unit
(3) Decor ring
(4) Brightness sensor
(5) Sensor window with
Programming LED, red
Status LED, blue
(6) Adjuster Sens. for manual sensitivity adjustment
(7) Programming button Prog.
4 Function
Intended use
– Requirement-oriented control of lighting, room thermostats and other electrical consumers
in interior rooms
– Ceiling mounting on fixed ceilings in appliance box according to DIN 49073 or surface-
mounted housing (see accessories)
Product characteristics
– Integrated bus coupling unit
– 3 PIR sensors
– Detection field 360°
– Integrated brightness sensor
– Deployed as presence detector, motion detector, or for alert operation
– Output functions: Switching, staircase function, switching with forced position, value trans-
mitter, light scene extension, operating mode setting for room temperature controller
– Detection field extendible by parallel switching of several devices as main unit or exten-
sion unit
2 / 11
82585623 23.07.2019
j0082585623

Presence detector
– Adjuster for manual adjustment of sensitivity
– Status LED: Flashes during motion detection; depending on programming in normal oper-
ation or only during the walking test mode
Additional characteristics of "Universal" version:
– Manual operation with IR remote control possible (accessories)
– 5 function blocks for motion or presence detection each with 2 outputs
– Function blocks switchable, e.g. for day/night operation
– PIR sensors can be evaluated separately
– Brightness sensor function with 3 limiting values
– Light control with max. of 3 channels, setpoint shift in operation, separate configuration of
dimming-up, control and dimming-down phase
– Light control can be combined with presence detector function
Presence detector function:
– Detection of the smallest motions e.g. at a workplace for detecting the presence of per-
sons
– Switch on: Motion detection and brightness threshold not reached
– Switch off: No motion in the detection field and run-on-time elapsed or brightness
threshold exceeded
Motion detector function:
– Detection of motions for passageway security in buildings
– Switch on: Motion detection and brightness threshold not reached
– Switch off: No motion in the detection field and run-on-time elapsed
After reacting and switching on, the motion detection works independently of the bright-
ness.
Alert operation:
– Brightness-independent detection of motions in the detection field
– Switch on: After detection of an adjustable number of motions within the set monitoring
period
– Switch off: No persons in the detection field and run-on-time elapsed
5 Operation
Only for "Universal" version:
Obey the battery safety instructions.
■ Keep contacts of batteries and device free of grease.
■ Insert the supplied battery with correct polarity (see IR remote control imprint)
Function buttons IR remote control
Button Function
¿Detection of a motion is sent for function block
1. The automatic mode is exited.
ÁEnd of a motion is sent for function block 1.
The automatic mode is exited.
ÀThe automatic mode is activated again for
function block 1.
The ON state is first exited after a new motion
detection.
3 / 11
82585623 23.07.2019
j0082585623

Presence detector
Adjustable buttons IR remote control
Button Function
´Increasing sensitivity
²Reducing sensitivity
³Resetting sensitivity to presetting
ÊFunction block 1: Brightness threshold 10 lx
ËFunction block 1: Brightness threshold 50 lx
ÌFunction block 1: Brightness threshold 150 lx
ÍFunction block 1: Brightness independent op-
eration
ÉFunction block 1: Set current brightness as
brightness threshold
10 SEK, 30 SEK, 2 MIN, 5 MIN, 30 MIN Function block 1: Extend minimum run-on-time
(10 seconds) by the selected value
START, STOP Function block 1: Extend minimum run-on-time
(10 seconds) individually
Set-up buttons of IR remote control
Button Function
ÙWalking test – Check detection field
ÚReset sensitivity, brightness threshold and
run-on-time to presetting. Press for at least 3
seconds
Operation with IR remote control
If enabled, function block 1 can be operated manually by remote control. In manual operation,
brightness and motion detection for function block 1 are switched off until automatic mode is re-
set.
■ Switch on, e.g. light: Press the ¿ button.
■ Switch off, e.g. light: Press the Á button.
■ Set automatic mode: Press the À button.
Manually changing settings with IR remote control
If enabled, individual settings for function block 1 can be changed during operation using a re-
mote control.
Sensitivity:
■ Increase sensitivity: Press ´ button.
■ Decrease sensitivity: Press ² button.
■ Recall set sensitivity again: Press ³ button.
The manual adjustment of sensitivity by the adjuster Sens. (6) is overwritten by the IR-re-
mote control and vice versa.
Brightness threshold:
■ Change brightness threshold: Depending on requirement, press Ê button, Ë button, Ì
button or Í button.
■ Set current brightness as brightness threshold: Press É button.
Run-on-time: The preset run-on-time of 10 seconds can be extended individually.
4 / 11
82585623 23.07.2019
j0082585623

Presence detector
■ Extend run-on-time: Depending on requirement, press 10 SEK button, 30 SEK button, 2
MIN button, 5 MIN button or 30 MIN button. Other values can be set with the START/
STOP buttons.
6 Information for electrically skilled persons
6.1 Fitting and electrical connection
Detection field and range
Figure2: Tangential and radial direction of motion
The device has a detection field of 360°. The diameter of the detection field depends on the in-
stallation height and the direction of motion of persons in the detection field (Figure 3).
The detection field becomes larger the greater the installation height, while the detection density
and sensitivity are reduced at the same time.
Figure3: Detection range depending on the direction of movement
Diameter of detection field for direction of movement
Installation height 1: 2: 3: 4:
2.20 m 14.5 m 11.5 m 8 m 6 m
2.50 m 16.5 m 13 m 10 m 7 m
5 / 11
82585623 23.07.2019
j0082585623

Presence detector
Installation height 1: 2: 3: 4:
3.00 m 20 m 16 m 12 m 8 m
3.50 m 23 m 18.5 m 14 m 9 m
4.00 m 26 m 17 m 14.5 m*) – *)
5.00 m 28 m 18 m 15 m*) – *)
1: Range for tangential movement on the ground
2: Range for radial movement on the ground
3: Range for typical movements at desks, e.g. torso movement
4: Range of fine detection at desks, e.g. mouse movements
*) When used as a presence detector: Installation height should not be more than
3.5 m, otherwise fine detection is not possible.
Selecting installation location
When used as a presence detector, the device is installed on the ceiling and monitors the sur-
face below it. When used as a motion detector, the device is installed e.g. in the hallway on the
ceiling.
■ Select a vibration-free installation location. Vibrations can lead to unwanted switching.
■ Avoid interference sources in the detection area. Interference sources, e.g. heaters, vent-
ilation, air conditioners, and cooling light bulbs can lead to unwanted detections.
If necessary, the detection field can be limited using the push-on cover in order to minim-
ise the influence of interference sources (see Limiting the detection field).
Limiting the detection field
Figure4: Push-on cover
The push-on cover can be used to limit the detection field, e.g. in order to mask out interference
sources.
6 / 11
82585623 23.07.2019
j0082585623

Presence detector
Cover size Range on the ground (height 3 m)
Complete push-on cover Ø approx. 4.5 m
Area I cut out Ø approx. 7.5 m
Areas I + II cut out Ø approx. 12 m
without push-on cover Ø approx. 20 m
■ Pull off push-on cover.
■ Using scissors, cut out push-on cover along the marked lines as required.
■ Push on push-on cover.
Aligning the device
The device has three independent sensors for motion detection. The arrangement of the areas
A, B and C is clearly evident under the decor ring (Figure 6).
Figure5: Detection field areas A, B and C, installation height 2.50m
Figure6: Arrangement of the areas A, B and C
7 / 11
82585623 23.07.2019
j0082585623

Presence detector
■ When mounting the device, align it so that the alignment of areas A, B and C match the
project design.
Already pay attention to correct alignment when mounting the appliance box and support-
ing frame.
Connecting and fitting the device in a flush-mounted box
Flush-mounted appliance box is mounted on the ceiling at the designated installation location.
In suspended ceilings, we recommend using air-tight, cavity wall appliance boxes.
■ Pull off decor ring (3).
■ When mounting the supporting frame (1), make sure that the areas A, B and C are
aligned correctly.
■ Run the bus cable through the supporting frame.
■ Use connecting terminal to connect bus line to the bus connection on the rear side of the
device.
■ Press the device into the supporting frame correctly aligned until it locks in place.
■ Attach decor ring (3).
Fitting and connecting device in a surface-mounted housing
Using a surface-mounted housing (see accessories).
■ Pull off decor ring (3).
■ Guide the bus cable through the eyelet of the surface-mounted housing provided.
■ Make sure that the areas A, B and C are aligned correctly when mounting the surface-
mounted housing on the ceiling.
■ Use connecting terminal to connect bus line to the bus connection on the rear side of the
device.
■ Mount the device correctly in the housing and screw down tightly.
■ Attach decor ring (3).
6.2 Commissioning
Load the address and the application software
■ Switch on the bus voltage.
■ Press the programming button (7).
The programming LED in the sensor window (5) lights up.
■ Assign physical address.
The programming LED goes out.
■ Write the physical address on the device label.
■ Load the application software into the device.
Testing the detection field
In the case of presence detectors connected in parallel, check the detection fields individually
one after the other.
The presence detector is mounted and connected. The physical address and application soft-
ware are loaded.
■ Activate walking test:
Activate parameter "walking test after download" and download application software.
The presence detector operates independently of the brightness. All sensors are active
according to their programmed sensitivity.
■ Pace off the detection field, paying attention to reliable detection and interference
sources.
Any motions detected are displayed by the blue status LED in the sensor window.
8 / 11
82585623 23.07.2019
j0082585623

Presence detector
■ Limit detection area, if necessary, using the push-on cover. Adjust sensitivity with adjuster
Sens. or IR remote control, or change the programming.
■ Deactivate parameter "walking test after download" and download application software.
Only for "Universal" version:
If enabled, the walking test function can be activated with the button Ù of the IR re-
mote control.
7 Disposal of batteries
Remove empty batteries immediately and dispose of in an environmentally friendly
manner. Do not throw batteries into household waste. Consult your local authorities
about environmentally friendly disposal. According to statutory provisions, the end
consumer is obligated to return used batteries.
8 Technical data
KNX medium TP256
Commissioning mode S-mode
Rated voltage KNX DC 21 ... 32 V SELV
Current consumption KNX max. 12.5 mA
Connection, Bus device connection terminal
Ambient temperature -5 ... +45 °C
Storage/transport temperature -25 ... +70 °C
Relative humidity 5 ... 93 % (no moisture condensation)
Protectionclass III
Motion detection
Detection angle 360°
Range Ø approx. 20 m (installation height 3 m)
Brightness sensor
Measuring range 0 ... 2000 lx
Detection area Ø 2 m
Only for "Universal" version:
IR remote control
Battery type 1×Lithium CR 2450N
9 Troubleshooting
Light does not switch on despite motion detection and low lighting
Cause 1: Wrong function block active.
Change function block switch-over.
Cause 2: Brightness threshold set is too low.
Increase the brightness threshold with the remote control or parameter setting.
Light switches on despite sufficient ambient lighting
Cause 1: Signal function is active and the device therefore operates independently of the bright-
ness.
Check programming.
Cause 2: Device operates independently of the brightness.
Adjust the brightness threshold with the remote control.
9 / 11
82585623 23.07.2019
j0082585623

Presence detector
Adjust parameter setting for brightness threshold.
Light switches off briefly and then on again immediately
Cause 1: Luminaires in the detection field.
Set the configuration barrier parameter so that cooling light bulbs are not detected.
Cause 2: The brightness threshold set is not reached after switching off. Device switches on
again immediately during motion detection.
Increase brightness threshold.
Light switches off early despite motion detection and low lighting
Cause 1: The set time is too short.
Increase the time with the remote control or parameter setting.
Cause 2: Detection problem, the surface to be monitored is not in the detection field, or furniture
or pillars are in the way.
Check detection field, extend presence detector extension if necessary.
Device responds even without any motion in the detection field
Cause: Interference sources in the detection field or device settings are too sensitive.
Limit detection field, remove interference sources.
Adjust sensitivity by one level with blue sensitivity switch (7) or with remote control.
Reduce sensitivity in parameter setting.
The sensitivity should be reduced by 1 to 2 levels in small spaces.
Light does not switch off despite sufficient ambient lighting
Cause 1: Device is set as motion detector and therefore does not evaluate the ambient lighting
after reacting.
Check programming. Set and program device as presence detector.
Cause 2: Brightness threshold set is too high.
Decrease the brightness threshold with the remote control or parameter setting.
Light does not switch on or switches on too late despite motion in the detection field
Cause 1: Device is set for alert operation and does not evaluate the first motion impulse detec-
ted.
Check programming. Set and program device as motion detector.
Cause 2: Evaluation delay is activated so that anyone briefly entering the detection field,
for example, is not evaluated.
Correct the programming, shorten or deactivate evaluation delay.
10 Accessories
IR remote control Art. no. KNX PM FB IR
Surface-mounted housing, white Art. no. PM-KAPPE-1
Surface-mounted housing, aluminium Art. no. PM-KAPPE AL-1
Protection cage Art. no. SK 180-90 WW
11 Warranty
The warranty is provided in accordance with statutory requirements via the specialist trade.
10 / 11
82585623 23.07.2019
j0082585623
This manual suits for next models
3
Table of contents
Other Jung Security Sensor manuals

Jung
Jung KNX 3361MWW-01 User manual

Jung
Jung DWPM17360AL User manual

Jung
Jung PMK 360 WW User manual

Jung
Jung DWPMK360WW User manual

Jung
Jung 17180 Series User manual

Jung
Jung Observer 220 User manual

Jung
Jung BM 240 S1A WW User manual

Jung
Jung BM360MBWW User manual

Jung
Jung HOME BT 17181 Series User manual

Jung
Jung 3360 User manual

Jung
Jung Mini basic User manual

Jung
Jung BT 17182 Series User manual

Jung
Jung Observer 70 User manual

Jung
Jung FM ES 36804 REG User manual

Jung
Jung PMU 360 WW User manual

Jung
Jung 2103 REG ES User manual

Jung
Jung FPM360WW User manual

Jung
Jung BT17361 Series User manual

Jung
Jung Observer 110 User manual

Jung
Jung 3361WW-01 User manual