Jung DWPMK360WW User manual

Light management
Motion and presence detector
Motion and presence detector
Art. no.: DWPMK360WW
Motion and presence detector
Art. no.: DWPMK360AL
Operating instructions
1 Safety instructions
Electrical devices may only be mounted and connected by electrically skilled persons.
Serious injuries, fire or property damage possible. Please read and follow manual fully.
DANGER! Danger of electric shock. Device is not suitable for disconnection from supply
voltage. The load is not electrically isolated from the mains even when the device is switched
off.
Always disconnect before carrying out work on the devise or load. In so doing, take all the cir-
cuit breakers into account, which support dangerous voltages to the device and or load.
Do not press on the sensor window. Device can be damaged.
The device is not suitable for use as a burglar alarm or other alarm.
These instructions are an integral part of the product, and must remain with the end customer.
2 Battery safety instructions
This device or its accessories are supplied with batteries in the form of button cells.
DANGER! Batteries can be swallowed. This can lead directly to death by suffocation. Danger-
ous substances may cause severe internal burns leading to death within 2 hours.
Keep new and used batteries away from children.
Do not use devices if the battery compartment does not close securely and keep away from
children.
If you suspect that a battery has been swallowed or is in any orifice of the body, seek immediate
medical attention.
WARNING! Improper handling of batteries can result in explosion, fire or chemical burn due to
leakage.
Do not heat or throw batteries into fire.
Do not reverse polarity, short-circuit or recharge batteries.
Do not deform or disassemble batteries.
Replace batteries only with an identical or equivalent type.
Remove empty batteries immediately and dispose of in an environmentally friendly manner.
1 / 19
82593223 27.06.2019
J0082593223

Light management
Motion and presence detector
3 Device components
Figure1
(1) Connection box
(2) Sensor top
(3) Brightness sensor
(4) Sensor window with red and blue display LED
(5) Decor ring
(6) Push-on cover
Figure2
(7) IR end customer remote control, included in the scope of delivery
(8) IR installation engineer remote control (see Accessories)
4 Intended use
– Automatic switching of lighting depending on the heat motion and ambient brightness
– Indoor ceiling mounting, surface-mounted
Product characteristics
– 2-point light control
– Functions settable with IR remote controls
2 / 19
82593223 27.06.2019
J0082593223

Light management
Motion and presence detector
– Restriction of the detection field by switching off individual sensors or push-on cover
– Operation with IR remote control, 2-wire extension or installation button
– Teach function for adjustment of the brightness threshold, in combination with IR remote
controls
– Switch-off warning
– Short-time operation, e.g. to activate acoustic signal encoders
– Display LEDs
– Presence simulation
– Function as twilight switch
– Dynamic run-on time
– Extension of the detection field through parallel switching of multiple devices
The extension of the detection area with 3-wire extensions is not possible.
Automatic operation
The device detects heat motions of people, animals and objects.
– The light is switched on if a person enters the detection field and the brightness threshold
is below the set brightness threshold.
The run-on time restarts with each detected motion.
– The light is switched off when it is no longer required because:
no more movement is detected in the detection field and the run-on time has elapsed or
the ambient light is bright enough.
The switch-off brightness is calculated from the set brightness threshold and the connec-
ted light.
To avoid brief shading from causing switch-off, switch-off only takes place when the set
run-on time has elapsed. The run-on time does not restart on movement detection for as
long as the switch-off brightness is exceeded.
The minimum switch-off brightness is 100 lux, even if a lower value is set.
To avoid any switch-on caused by a cooling illuminant, no movement signals are evaluated for a
brief lockout time after switching off. The motion detector adjusts itself to the ambient conditions
to keep the time as short as possible.
Short time operation
If motion occurs, then a short pulse of approx. 0.5 seconds is triggered depending on the bright-
ness. The pulse is cyclically repeated as long as motions are detected.
Switch-off warning
If the switch-off warning is active, the light is not switched off immediately after the run-on time
has elapsed. Triple flashing at an interval of 10 seconds shows that the light will be switched off
soon. The run-on time is thereby prolonged by approx. 30 seconds. If movement is detected
during the switch-off prewarning, then the run-on time is restarted and the light remains on.
Dynamic run-on time
The function determines a run-on time within specified limits automatically and dynamically from
detected movements. In so doing, the run-on time is increased if presence continues or de-
creased if absence is detected.
Presence simulation
In automatic operation, the motion detector continuously saves times for which the lighting was
switched on. A maximum of 60 switching operations are saved over a period of 24 hours. If
more switching operations take place, the oldest ones are overwritten respectively. If the pres-
ence simulation is activated, the motion detector switches the lighting at the saved times ac-
cording to the brightness. Switch-off takes place after the run-on time has elapsed. Detected
motions prolong the run-on time or the light is switched on depending on brightness. Times are
not saved.
3 / 19
82593223 27.06.2019
J0082593223

Light management
Motion and presence detector
Function as twilight switch
The function is active as soon as all the PIR sensors have been switched off (see Commission-
ing).
The light is switched according to the brightness. Motions are not evaluated
– The light is switched on if the brightness is below the set brightness threshold for
4 minutes.
– The light is switched off when the switch-off brightness (see Automatic mode) is exceeded
for 4 minutes.
Switch-on and switch-off of the light via 2-wire extensions or installation buttons is not
possible. The Continuous on/off and on/off for 2 hours functions cannot be used.
Behaviour after mains return
After mains return, the device performs a self-test for a maximum of 20 seconds. After the self-
test has been completed, the device is ready for operation. The device switches the light ac-
cording to the settings made.
The following applies during the self-test:
– The red and blue indication LEDs (4) light up.
– The device cannot be operated or set using an IR remote control.
– Movements are not detected.
– The device can be switched via 2-wire extensions or installation buttons.
5 Operation
Special functions can be switched and settings adjusted using the supplied IR remote control.
Special functions can restrict operation via the 2-wire extension inserts or installation but-
tons.
If multiple devices are within the range of the IR remote control, then align it so that only
the device to be operated can receive the signals.
Insert battery
Obey the battery safety instructions.
■ Keep contacts of batteries and device free of grease.
■ Insert the supplied battery with correct polarity (see IR remote control imprint)
LED display
Behind the sensor window (4) are a red and a blue LED (Figure 1) for indicating different states
of operation.
Red LED Blue LED Signalling
Off On Light switched on continuously
On Off Light switched off continuously
or twilight button function ac-
tivated
Flashing slowly Off Presence simulation switched
on
Flashing Off Receipt of IR signals
Off Flashing IR signal detected
Button assignment of the end user IR remote control
Taste Funktion
ů
Pressing for less than 0.4 seconds
Switching on automatic mode
4 / 19
82593223 27.06.2019
J0082593223

Light management
Motion and presence detector
ů
Actuation of between 1 and 4 seconds
In automatic mode: Switch-on for the duration
of the run-on time
Ű
Pressing for less than 0.4 seconds
Continuous on
ű
Pressing for less than 0.4 seconds
Continuous off
2h on
Pressing for less than 0.4 seconds
On for 2 hours
2h off
Pressing for less than 0.4 seconds
Off for 2 hours
Ų
Pressing for less than 10 seconds
In the next 10 seconds, the brightness
threshold can be changed incrementally using
the Ű or ű buttons.
Ų
Pressing for longer than 10 seconds
Saving the current ambient brightness as the
brightness threshold
Set 2
Pressing for longer than 10 seconds
Activating the settings saved by the installation
engineer
ų
Pressing for longer than 10 seconds
Switching the presence simulation on or off
Time
Pressing for less than 10 seconds
In the next 10 seconds, the run-on time can be
changed incrementally using the Ű or
ű buttons.
Switching on light for the duration of the run-on time
A 2-wire extension or an installation button is connected.
In short-time operation, cyclic pulses take place whilst the 2-wire extension at top or bot-
tom or installation button is pressed.
Alternatively, press the ů button of the IR remote control for between 1 and
4 seconds. In short-time operation, there is a single pulse after releasing the button.
Light is switched off.
Motion detector operation
■ Press the 2-wire extension or installation button for less than 0.4 seconds.
If the 2-wire extension or the installation button is pressed again after switch-on, then the
run-on time is restarted.
Presence detector operation
■ Press the top or full-surface of the 2-wire extension or installation button for less than
0.4 seconds.
Light is switched on depending on brightness and motion. Movements are evaluated ac-
cording to the brightness and prolong the run-on time.
Switching the light off for a period of 3 minutes
This function can only be used in presence detector operation.
A 2-wire extension or an installation button is connected.
Light is switched on.
■ Press the bottom 2-wire extension or installation button.
The light is switched off for the period of 3 minutes. When movements are detected, the
time is restarted.
5 / 19
82593223 27.06.2019
J0082593223

Light management
Motion and presence detector
Switch on the light for 2 hours
Motions are not evaluated during this time. It is not possible to switch off via a 2-wire extension
or installation button.
■ Press 2 h On button of the IR remote control.
Light is switched on for 2 hours. The motion detector is in automatic operation again after
the 2 hours have elapsed.
The time is restarted if actuation is repeated.
Automatic operation is switched on again using the ů button.
Switch on the light continuously
Motions are not evaluated during this time. It is not possible to switch off via a 2-wire extension
or installation button.
■ Press the Ű button for shorter than 0.4 seconds.
Light is switched on continuously. The blue LED lights up.
Automatic operation is switched on again using the ů button.
Switch off the light for 2 hours
Motions are not evaluated during this time. It is not possible to switch on via a 2-wire extension
or installation button.
■ Press the 2 h Off button.
Light is switched off for 2 hours. The device is in automatic operation again after the time
has elapsed.
The time is restarted if actuation is repeated.
Automatic operation is switched on again using the ů button.
Switch off the light continuously
Motions are not evaluated It is not possible to switch on via a 2-wire extension insert or installa-
tion button.
■ Press the ű button for shorter than 0.4 seconds.
Light is switched off continuously. The red LED lights up.
Automatic operation is switched on again using the ů button.
Adjusting the switch-on brightness
The switch-on brightness is set during commissioning. The switch-on brightness can be adjus-
ted at a later time using the supplied IR remote control.
■ Press Ų button briefly.
■ Within 10 seconds, press the Ű or ű button briefly.
Each button press extends or shortens the brightness threshold by 10% of the set value,
but by at least 1 lux.
Saving the current brightness as the switch-on brightness
■ Press the Ų button for longer than 10 seconds.
The current brightness is saved as the switch-on brightness.
Adjusting the run-on time
The run-on time is set during commissioning. The run-on time can be adjusted at a later time
using the supplied IR remote control.
■ Press Time button briefly.
■ Within 10 seconds, press the Ű or ű button briefly.
Each button press extends or shortens the run-on time by 10% of the set value, but by at
least 1 second.
6 / 19
82593223 27.06.2019
J0082593223

Light management
Motion and presence detector
Recalling saved settings
During commissioning, the installation engineer can save the settings made (see Saving set-
tings). These can be recalled if, for example, changes made later are no longer required.
■ Press the Set 2 button for longer than 10 seconds.
Settings saved by the installation engineer are active again.
Switching the presence simulation on or off
■ Press the ų button for longer than 10 seconds.
The presence simulation is switched on or off alternately. If the function is switched on,
the red LED flashes slowly.
The function cannot be activated until 24 hours after first commissioning.
6 Information for electrically skilled persons
DANGER!
Mortal danger of electric shock.
Before carrying out work on the device or load, disengage all the corresponding cir-
cuit breakers. Cover up live parts!
6.1 Fitting and electrical connection
Detection field and range
Figure3: Tangential and radial direction of motion
The device has a detection field of 360°. The diameter of the detection field depends on the in-
stallation height and the direction of motion of persons in the detection field (Figure 4).
The detection field becomes larger the greater the installation height, while the detection density
and sensitivity are reduced at the same time.
7 / 19
82593223 27.06.2019
J0082593223

Light management
Motion and presence detector
Figure4: Detection range depending on the direction of movement
Diameter of detection field for direction of movement
Installation height 1: 2: 3: 4:
2.20 m 14.50 m 11.50 m 8.00 m 6.00 m
2.50 m 16.50 m 13.00 m 10.00 m 7.00 m
3.00 m 20.00 m 16.00 m 12.00 m 8.00 m
3.50 m 23.00 m 18.50 m 14.00 m 9.00 m
4.00 m 26.00 m 17.00 m 14.50 m *) – *)
5.00 m 28.00 m 18.00 m 15.00 m *) – *)
6.00 m 29.00 m 19.00 m – *) – *)
1: Range for tangential movement on the ground
2: Range for radial movement on the ground
3: Range for typical movements at desks, e.g. torso movement
4: Range of fine detection at desks, e.g. mouse movements
*) When used as a presence detector: Installation height should not be more than 3.5
m, otherwise fine detection is not possible.
Selecting installation location
For use as a presence detector, the device is installed, for example, above a workplace and
monitors the surface below it. For use as a motion detector, the device is installed, for example,
in the hallway.
■ Select a vibration-free installation location. Vibrations can lead to unwanted switching.
■ Avoid interference sources in the detection area. Interference sources, e.g. heaters, vent-
ilation, air conditioners, and cooling light bulbs can lead to unwanted detections.
The detection field can be limited in order to minimise the influence of interference
sources. For this, use the push-on cover (see Limiting the detection field with the push-on
cover) or switch off individual sensors (see Limiting the detection field).
Aligning the device
The device has three independent PIR sensors for motion detection (Figure 5).
8 / 19
82593223 27.06.2019
J0082593223

Light management
Motion and presence detector
Figure5: Detection field areas A, B and C, installation height 2.50m
Figure6: Arrangement of the areas A, B and C
■ Align the connection box (1) in such a way that the areas A, B and C match the structural
conditions. The arrangement is clearly evident under the decor ring (Figure 6).
9 / 19
82593223 27.06.2019
J0082593223

Light management
Motion and presence detector
Preparations for installation
Figure7: Mounting
(1) Connection box
(2) Sensor top
(5) Decor ring
(9) Fastening pins
(10) Screws
■ Pull off decor ring (5) (Figure 7).
■ Loosen screws (10) (Figure 7).
Installing the connection box
Figure8: Connection box
(11) Fastening holes
(12) Cable entry, surface-mounted
(13) Thin points for optional cable entries
■ Align the device (for the position of areas A, B, C, see Aligning the device) – the bright-
ness sensor should, if possible, be located on the side away from the window. This re-
duces the effects of scattered light.
■ For an additional flush-mounted cable entry or surface-mounted cable entry, break out the
appropriate thin point (13) (Figure 8).
■ Fastening the connection box (1) through holes (11) (Figure 8).
10 / 19
82593223 27.06.2019
J0082593223
This manual suits for next models
1
Table of contents
Other Jung Security Sensor manuals

Jung
Jung DWPM17360AL User manual

Jung
Jung BM360MBWW User manual

Jung
Jung FPM360WW User manual

Jung
Jung 2103 REG ES User manual

Jung
Jung Radio Detector 180 User manual

Jung
Jung BT17361 Series User manual

Jung
Jung HOME BT 17181 Series User manual

Jung
Jung Observer 220 User manual

Jung
Jung PMU 360 WW User manual

Jung
Jung Standard 3361 WW User manual

Jung
Jung 3361MWW User manual

Jung
Jung KNX 3361MWW-01 User manual

Jung
Jung 3360 User manual

Jung
Jung BT 17182 Series User manual

Jung
Jung FM ES 36804 REG User manual

Jung
Jung BM 240 S1A WW User manual

Jung
Jung Observer 110 User manual

Jung
Jung Mini basic User manual

Jung
Jung FMDW360WW User manual

Jung
Jung 17180 Series User manual