Jung 3361WW-01 User manual

Presence detector standard
Art. No. : 3361WW-01
Presence detector standard
Art. No. : 3361AL-01
Presende detector Universal
Art. No. : 3361-1WW-01
Presende detector Universal
Art. No. : 3361-1AL-01
Operating instructions
1 Safety instructions
Presence detector
1/12
82585625
J0082585625 04.12.2017

2 Device components
Figure 1: Device components
(1) Supporting frame
(2) Integrated bus coupling unit
(3) Decor ring
(4) Brightness sensor
(5) Sensor window with
Programming LED, red
Status LED, blue
(6) Adjuster Sens. for manual sensitivity adjustment
(7) Programming button Prog.
3 Function
System information
This device is a product of the KNX system and complies with the KNX directives. Detailed
technical knowledge obtained in KNX training courses is a prerequisite to proper understanding.
The function of this device depends upon the software. Detailed information on loadable soft
ware and attainable functionality as well as the software itself can be obtained from the
manufacturer´s product database. Planning, installation and commissioning of the device are
2/12
Presence detector
82585625
J0082585625 04.12.2017

carried out with the aid of KNXcertified software. The latest versions of product database and
the technical descriptions are available on our website.
Intended use
Requirementoriented control of lighting, room thermostats and other electrical consumers
in interior rooms
Ceiling mounting on fixed ceilings in applicable Listed electrical box or surfacemounted
housing (see accessories)
Presence detector function:
Detection of the smallest motions e.g. at a workplace for detecting the presence of persons
Switch on: Motion detection and brightness threshold not reached
Switch off: No motion in the detection field and runontime elapsed or brightness threshold
exceeded
Motion detector function:
Detection of motions for passageway security in buildings
Switch on: Motion detection and brightness threshold not reached
Switch off: No motion in the detection field and runontime elapsed
iAfter reacting and switching on, the motion detection works brightnessindependently.
Alert operation:
Brightnessindependent detection of motions in the detection field
Switch on: After detection of an adjustable number of motions within the set monitoring
period
Switch off: No persons in the detection field and runontime elapsed
4 Operating Control
Only for "Universal" version:
Function buttons IR remote control
Button Function
¿Detection of a motion is sent for function block
1. The automatic mode is exited.
ÁEnd of a motion is sent for function block 1.
The automatic mode is exited.
ÀThe automatic mode is activated again for
function block 1.
The ON status is first exited after a new
motion detection.
Setting buttons IR remote control
Button Function
´Increase sensitivity
²Reduce sensitivity
³Reset sensitivity to presetting
ÊFunction block 1: brightness threshold 1 fc
ËFunction block 1: brightness threshold 4.7 fc
ÌFunction block 1: brightness threshold 14 fc
ÍFunction block 1: brightnessindependent
operation
ÉFunction block 1: Set current brightness as
brightness threshold
3/12
Presence detector
82585625
J0082585625 04.12.2017

10 SEK, 30 SEK, 2 MIN, 5 MIN, 30 MIN Function block 1: Extend minimum runontime
(10 seconds) by the selected value
START, STOP Function block 1: Extend minimum runontime
(10 seconds) individually
Set-up buttons, IR remote control
Button Function
ÙWalking test – Check detection field
ÚReset sensitivity, brightness threshold and
runontime to presetting. Press for at least 3
seconds
Operation with IR remote control
If enabled, function block 1 can be operated manually by remote control. In manual operation,
brightness and motion detection for function block 1 are switched off until automatic mode is
reset.
oSwitch on, e.g. light: Press ¿ button.
oSwitch off, e.g. light: Press Á button.
oSet automatic mode: Press À button.
Manually change settings with IR remote control
If enabled, individual settings for function block 1 can be changed during operation using a
remote control.
Sensitivity:
oIncrease sensitivity: Press ´ button.
oDecrease sensitivity: Press ² button.
oRecall set sensitivity: Press ³ button.
iThe manual adjustment of sensitivity by the adjuster Sens. (6) is overwritten by the IR
remote control and vice versa.
Brightness threshold:
oChange brightness threshold: Depending on requirement, press Ê button, Ë button, Ì
button or Í button.
oSet current brightness as brightness threshold: Press É button.
Runontime: The preset runontime of 10 seconds can be extended individually.
oExtend runontime: Depending on requirement, press 10 SEK button, 30 SEK button, 2
MIN button, 5 MIN button or 30 MIN button. Other values can be set with the START/STOP
buttons.
4/12
Presence detector
82585625
J0082585625 04.12.2017

5 Information for electrically skilled persons
5.1 Mounting and electrical connection
Detection field and range
Figure 2: Tangential and radial direction of motion
5/12
Presence detector
82585625
J0082585625 04.12.2017

The device has a detection area of 360°. The diameter of the detection area depends on the
installation height and the direction of motions of persons in the detection area (figure 3).
The detection area becomes larger the greater the installation height, while the detection densi
ty and sensitivity are reduced at the same time.
Figure 3: Detection range depending on the direction of movement
Diameter of detection field for direction of movement
Installation
height
1: 2: 3: 4:
7.20 ft 47.60 ft 37.70 ft 26.30 ft 19.70 ft
8.20 ft 54.10 ft 42.70 ft 32.80 ft 23.00 ft
9.80 ft 65.60 ft 52.50 ft 39.40 ft 26.30 ft
11.50 ft 75.50 ft 60.70 ft 45.90 ft 29.50 ft
13.10 ft 85.30 ft 55.80 ft 47.60 ft*) – *)
16.40 ft 91.90 ft 59.10 ft 49.20 ft*) – *)
1: Range for tangential movement on the ground
2: Range for radial movement on the ground
3: Range for typical movements at desks, e.g. torso movement
4: Range of fine detection at desks, e.g. mouse movements
*) When used as a presence detector: Mounting height should not be more than 11.50 ft, oth
erwise fine detection is not possible.
6/12
Presence detector
82585625
J0082585625 04.12.2017

Limiting the detection field
Figure 4: Pushon cover
The pushon cover can be used to limit the detection field, e.g. in order to mask out interference
sources.
Cover size Range on the ground
(mounting height 9.80 ft)
Complete pushon cover Ø approx. 14.80 ft
Area I cut out Ø approx. 24.60 ft
Areas I + II cut out Ø approx. 39.40 ft
without pushon cover Ø approx. 65.60 ft
oPull off pushon cover.
oUsing scissors, cut out pushon cover along the marked lines as required.
oPush on pushon cover.
Align the device
The device has three independent sensors for motion detection. The arrangement of the areas
A, B and C is clearly evident under the decor ring (figure 6).
7/12
Presence detector
82585625
J0082585625 04.12.2017

Figure 5: Detection field areas A, B and C, installation height 8.20 ft
8/12
Presence detector
82585625
J0082585625 04.12.2017

Figure 6: Arrangement of the areas A, B and C
oWhen mounting the device, align it so that the alignment of areas A, B and C match the
project design.
iAlready pay attention to correct alignment when mounting the appliance box and support
ing frame.
Mounting and connecting the device in a wall box
This device may only be installed in applicable listed electrical wall boxes, flushmounted.
iWall boxes must be ordered separately.
oWall boxes for solid walls have to be placed flush to the wall plaster.
oHollow wall boxes were placed by circular cutter. A hole of dia. 2.67 in (68 mm) must be
made.
The wall box will be plugged into and screwed by integrated clamps.
Flushmounted appliance box is mounted on the ceiling at the designated installation loca
tion.
iIn suspended ceilings, we recommend using airtight, cavity wall appliance boxes.
oPull off decor ring (3).
9/12
Presence detector
82585625
J0082585625 04.12.2017

oWhen mounting the supporting frame (1), make sure that the areas A, B and C are aligned
correctly.
oRun the bus cable through the supporting frame.
iUse only cables which are approved for KNX.
oUse connecting terminal to connect bus line to the bus connection on the rear side of the
device.
oPress the device into the supporting frame correctly aligned until it locks in place.
oAttach decor ring (3).
Mount and connect device in a surface-mounted housing
Using a surfacemounted housing (see accessories).Using a surfacemounted housing (see
accessories).
oPull off decor ring (3).
oGuide the bus cable through the eyelet of the surfacemounted housing provided.
oMake sure that the areas A, B and C are aligned correctly when mounting the surface
mounted housing on the ceiling.
iUse only cables which are approved for KNX.
oUse connecting terminal to connect bus line to the bus connection on the rear side of the
device.
oMount the device correctly in the housing and screw down tightly.
oAttach decor ring (3).
5.2 Commissioning
Load the address and the application software
oSwitch on the bus voltage.
oPress the programming button (7).
The programming LED (5) in the sensor window lights up.
oAssign physical address.
The programming LED goes out.
oWrite the physical address on the device label.
oLoad the application software into the device.
Test the detection area
In the case of presence detectors connected in parallel, check the detection areas individually
one after the other.
The presence detector is mounted and connected. The physical address and application soft
ware are loaded.
oActivate walking test:
Activate parameter "walking test after download" and download application software.
The presence detector operates independently of the brightness. All sensors are active
according to their programmed sensitivity.
oPace off the detection area, paying attention to reliable detection and interference sources.
Any motions detected are displayed by the blue status LED in the sensor window.
oLimit detection area if necessary using the pushon cover. Adjust sensitivity with adjuster
Sens. or IR remote control, or change the programming.
oDeactivate parameter "walking test after download" and download application software.
Only for "Universal" version:
iIf enabled, the walking test function can be activated with the button Ù of the IR remote
control.
10/12
Presence detector
82585625
J0082585625 04.12.2017
This manual suits for next models
3
Table of contents
Other Jung Security Sensor manuals

Jung
Jung BM360MBWW User manual

Jung
Jung Mini basic User manual

Jung
Jung Observer 220 User manual

Jung
Jung PMK 360 WW User manual

Jung
Jung 3361MWW User manual

Jung
Jung 17180 Series User manual

Jung
Jung Standard 3361 WW User manual

Jung
Jung 3360 User manual

Jung
Jung Observer 110 User manual

Jung
Jung FPM360WW User manual

Jung
Jung KNX 3361MWW-01 User manual

Jung
Jung FMDW360WW User manual

Jung
Jung PMU 360 WW User manual

Jung
Jung Radio Detector 180 User manual

Jung
Jung DWPMK360WW User manual

Jung
Jung Observer 70 User manual

Jung
Jung FM ES 36804 REG User manual

Jung
Jung 2103 REG ES User manual

Jung
Jung BT17361 Series User manual

Jung
Jung BM 240 S1A WW User manual