Daikin DGE601A52 User manual

Model : DGE601A52
Installation Manual
3P581074-2D
01_EN_3P581074-2D.indd 1 2021/06/25 14:12:08

01_EN_3P581074-2D.indd 2 2021/06/25 14:12:08

Installation Manual 3P581074-2D
DGE601A52
1English
Safety Precautions
Also see the installation manual provided with the equipment that you connect.
Please read these “SAFETY PRECAUTIONS” carefully before installing the unit, and be
sure to install the unit correctly.
• The installation manual and the “SAFETY PRECAUTIONS” contain important information
regarding safety. Be sure to observe all precautions.
WARNING Failure to follow these instructions properly may result in per-
sonal injury or loss of life.
CAUTION
Failure to observe these instructions properly may result in
property damage or personal injury, which may be serious
depending on the circumstances.
• After completing the installation, conduct a trial run to check for faults, and explain to the
customer how to operate the unit and take care of it with the aid of the operation manual. Ask
the customer to store the installation manual along with the operation manual for future refer-
ence.
WARNING
• Ask your dealer or other qualied personnel to take installation work.
Do not attempt to install the unit yourself. Improper installation may result in an electric
shock or re.
• Do not relocate or reinstall the unit yourself.
Improper installation work may result in an electric shock or re.
Ask your local dealer to carry out the relocation and reinstallation of the unit.
• Install the unit in accordance with the instructions in this installation manual.
Improper installation may result in an electric shock or re.
• Be sure to use only the specied accessories and parts for the installation work.
Failure to use the specied parts may result in the DGE601A52 falling, an electric shock, or
re.
• Install the unit on a foundation strong enough to withstand the weight of the unit.
A foundation of insufcient strength may result in the equipment falling and causing injury.
• Always perform the installation work with the power supply shut off.
Touching energised electric parts causes an electric shock.
• Do not disassemble, modify or repair the unit.
An electric shock or re may be caused.
• Make sure that all wiring is secured, that the specied wires are used, and that there
is no strain on the terminal connections or wires.
Improper connection or securing of wires may result in abnormal heat build-up or re.
• The choice of materials and installations must comply with the applicable national
and international standards.
01_EN_3P581074-2D.indd 1 2021/06/25 14:12:08

2Installation Manual 3P581074-2D
DGE601A52
English
WARNING
• Carry out the installation work taking earthquakes into account.
Failure to do so during installation work may result in the unit falling and causing accidents.
• Make sure that a separate power supply circuit is provided for this unit and that all
electrical work is carried out by qualied personnel according to local laws and regu-
lations and this installation manual.
An insufcient power supply capacity or improper electrical construction may lead to an
electric shock or re.
• When wiring the power supply position the wires so that the electric parts box lid can
be securely fastened.
Improper positioning of the electric parts box lid may result in an abnormal heat build-up, an
electric shock, or re.
• Be sure to earth the unit.
Do not earth the unit to a utility pipe, lightning conductor or telephone earth lead.
Imperfect earthing may result in an electric shock or re.
• Install an earth leakage breaker, as required.
Failure to install an earth leakage breaker may result in an electric shock or re.
• This unit is not intended for use by persons (including children) with reduced physi-
cal, sensory or mental capabilities, or lack of experience and knowledge, unless they
have been given supervision or instruction concerning use of the appliance by a
person responsible for their safety.
•
Children should be supervised to ensure that they do not play with the unit.
This equipment is not suitable for use in locations where children are likely to be present.
01_EN_3P581074-2D.indd 2 2021/06/25 14:12:08

Installation Manual 3P581074-2D
DGE601A52
3English
CAUTION
• Be very careful when transporting the unit.
• Safely dispose of the packing materials.
Tear apart and throw away plastic packaging bags so that children will not play with them.
If children play with a plastic bag which was not torn apart, they face the risk of suffocation.
• This unit is a class B product.
• In a domestic environment, this product may cause radio interference.
In such cases, the user may be required to take adequate measures.
•
Disposal requirements: the dismantling of the unit and of other parts must be done in
accordance with relevant local and national legislation.
• Fill wiring intake hole with putty.
Entry of water or insects may result in electric leakage or malfunction.
• Do not operate with wet hands.
An electric shock and malfunction may be caused.
• Do not wash the unit with water.
An electric shock or re may be caused.
• Install the unit, its power cord, and its wiring at least 1m away from televisions or
radios.
This is to prevent picture interference and noise. (Depending on the incoming signal
strength, a distance of 1m may not be sufcient to eliminate noise.)
• Do not install the unit in the following places.
1.
In places with a high concentration of mineral oil spray or vapour (e.g. a kitchen).
Plastic parts will deteriorate, parts may fall off and water leakage could result.
2. Near machinery emitting electromagnetic radiation.
Electromagnetic radiation may disturb the operation of the control system and result in a
malfunction of the unit.
3. In places where ammable gas may leak, where there is carbon bre or ignitable dust
suspensions in the air, or where volatile ammables such as paint thinner or gaso-
line are handled.
Operating the unit in such places may result in re.
4. In places with high temperatures or where the unit is exposed to direct ames.
Abnormal heat build-up or ring may be caused.
5. In moist areas or places that are exposed to water.
Water entering the unit may cause electric shock and malfunction.
01_EN_3P581074-2D.indd 3 2021/06/25 14:12:08

4Installation Manual 3P581074-2D
DGE601A52
English
Contents
1 Before Installation ........................................................................................................ 6
1.1 Checking that all accessories are included ........................................................ 6
1.2 Understanding external dimensions ................................................................... 7
1.3 Understanding terminals and switches .............................................................. 7
1.3.1 Rear face ................................................................................................ 7
1.3.2 Front face ............................................................................................... 8
1.4 Determining installation place .......................................................................... 10
1.4.1 Installation place and mounting direction ............................................. 10
1.4.2 Environmental conditions ..................................................................... 10
1.4.3 Wiring of cables.................................................................................... 11
1.4.4 Required space .................................................................................... 14
1.5 Equipment which can be connected to the DGE601A52 ................................. 14
2 Installation .................................................................................................................. 1 5
2.1 DIN rail mounting ............................................................................................. 15
2.1.1 Installation procedure ........................................................................... 15
2.1.2 Removal from DIN rail .......................................................................... 17
2.2 Screw-mounting to control enclosure ............................................................... 18
2.2.1 Accessory parts ................................................................................... 18
2.2.2 Installation procedure ........................................................................... 18
2.3 Adding a DGE601A53 ...................................................................................... 19
3 Electrical Wiring ......................................................................................................... 22
3.1 Connecting to the DGE601A51, or equivalent equipment ............................... 22
3.1.1 Terminals location and schematic connection diagram ........................ 23
3.1.2 Wiring specications ............................................................................ 26
3.1.3 Address setup and termination resistor ............................................... 27
01_EN_3P581074-2D.indd 4 2021/06/25 14:12:08

Installation Manual 3P581074-2D
DGE601A52
5English
3.2 Connecting DIII-NET compatible air conditioners ............................................ 28
3.2.1 Terminals location and schematic wiring diagram ................................ 28
3.2.2 Wiring specications ............................................................................ 31
3.2.3 Precautions for using multiple centralised controllers .......................... 31
3.3 Connecting an emergency stop input device or electric energy meters ........... 33
3.3.1 Terminals location and schematic connection diagram ........................ 33
3.3.2 Wiring specications ............................................................................ 34
3.4 Connecting the power supply ........................................................................... 35
3.4.1 Terminals location and schematic connection diagram ........................ 35
3.4.2 Wiring specications ............................................................................ 40
4 Setting addresses for each air conditioner ............................................................. 4 1
4.1 Setting addresses with wired remote controller (BRC1H*) .............................. 41
4.2 Setting addresses with navigation remote controller (BRC1E*) ....................... 59
4.3 Setting address on the outdoor unit ................................................................. 70
4.3.1 Steps for setting the outdoor unit Airnet address ................................. 71
4.3.2 Setting the demand address and enabling demand setting ................. 71
4.3.3 Setting items LED (segment) display ................................................... 72
5 Quick Operation Guide .............................................................................................. 73
5.1 Restarting the unit ............................................................................................ 73
01_EN_3P581074-2D.indd 5 2021/06/25 14:12:08

6Installation Manual 3P581074-2D
DGE601A52
English
1 Before Installation
Before you start installing, make the following preparatory checks.
• Check that the DGE601A52 comes with all accessories.
• Conrm where the terminals and switches of the DGE601A52 are located.
• Check that an appropriate space for installing the DGE601A52 is available.
1.1 Checking that all accessories are included
Based on the following accessory list, check that all accessories for the DGE601A52
are included.
If there is any missing or defective part, contact the DAIKIN dealer where you pur-
chased the product.
<Accessories included with DGE601A52>
A B C
B-2
B-1
B-3
A DGE601A52, 1pc.
B (B-1) Clamp for xing power supply cable, 2pcs.
(B-2) Wood screw (3mm diameter x 15mm length) for securing the body, 4pcs.
(B-3) Round crimp-type terminal (2-M4), 1pc.
C Installation manual (This manual), 1pc.
01_EN_3P581074-2D.indd 6 2021/06/25 14:12:09

Installation Manual 3P581074-2D
DGE601A52
7English
1.2 Understanding external dimensions
81.2 mm70 mm
25.2 mm
2 mm
120 mm
124 mm
74 mm
A B C
138mm
(When DIN rail lock is
“closed”)
146mm
(When DIN rail lock is
“open”)
A Power supply unit
B DGE601A53
C End cover
1.3 Understanding terminals and switches
Understand the arrangement of terminals and switches on the unit to facilitate the
installation procedure.
For details including the cable type, terminal size, and precautions, refer to “3. Electrical
Wiring”.
1.3.1 Rear face
On the rear face of the DGE601A52 there is a DIN rail lock for use when installing on a
DIN rail.
<Rear face>
A
A DIN rail lock
01_EN_3P581074-2D.indd 7 2021/06/25 14:12:09

8Installation Manual 3P581074-2D
DGE601A52
English
1.3.2 Front face
All the terminals used during installation are located on the front face of the DGE601A52.
The power supply terminals are covered with a terminal cover for safety.
In addition to these terminals, several switches and LEDs are also located on the front
face of the DGE601A52.
<Front face of DGE601A52>
A B G
F
Q
E H I
K
M
J
L
N
DC
O
P
Symbol Name Explanation
A[Intake for power
supply cable] Intake for power supply cable.
B[Inter-unit lock] Knob for locking the power supply unit and
DGE601A53.
C[Power supply unit]
Terminals for the connection of the power supply.
These terminals are covered with a protective
cover.
A singe phase 100 to 240 V AC (at 50/60 Hz)
power supply voltage is required.
D[DC OUT] LED LED (Green) When DC output is normal, this LED
is lit.
E[Di]
Terminals for stopping air conditioner operation
by an external signal in case of an emergency, or
for connecting electric energy meters.
01_EN_3P581074-2D.indd 8 2021/06/25 14:12:09