Doc. # BA000687 - 11/2010 (Rev. B)
H) Technical data
Entire device
Input voltage 400 V ±10 % AC 3-phase
Line frequency 50 Hz ±10%
Operating current per phase 4 A
Energy supply connection RST20i5 jack, 5-pole (black)
Device protection external; motor starter is to be secured on
the input side with
20 A conductor protection
Diagnostics "Status" AS-i inputs, motor status
Diagnostics "Error message" Bus error, motor failure, overload, over
current, undercurrent
Motor plug outlet
Output voltage 400 V ±10 % AC 3-phase, 50 Hz ±10%
Nominal power min./max. 0.09 / 1.5 kW
Load current min./max. 0.2 A / 4.0 A
Motor connection with 5-pin (black) RST20i5 plug
Switching component Electronic power switch
Switching frequency Max. 1,000 switches per hr.
(load-dependant)
Switching times Type 10 ms
Operating mode DB (EN 60149-1-1 und 1-3), S3 max.
runtime 10 minutes
Utilisation category AC-3; squirrel cage motors: Starting,
switching off during operation
Overload protection Current monitoring
Isolation Safe separation of load circuit to the AS-i
circuit
Protection criteria Overload function (configuration via
parameter download)
Activation characteristics Class 10 approached (parameterisable)
Conductor and overload
protection
Short circuit withstand capability Not short circuit-proof
Device protection not included in the device
Conductor and short circuit protection
of supply line
20 A
Motor protection Internal
AS Interface
Field bus communication AS-i specification V3.0 profile 7.4
(IO=7; ID=4; ID1=F;ID2=0)
Field bus connection (AS-i) with circular plug-in connector M12
Electronic/control motor switch power
supply
from AS interface 60 mA
Current consumption from AS-i Max. 200 mA
Addressing Address 0 to 31 (A-Slave)
via M12-DC jack 1.3 mm
Digital inputs (via AS-i)
Number 3
Type Two- or three-wire initiators
Supply voltage AS-i 20…30 V DC
Input current Type 5 mA
Input resistance Type 5 kΩ
Power supply current per initiator Max. 40 mA ; if all three Initiators
are connected, the sum is 120 mA
Sampling time Approx. 5 ms
Connector sensors with circular plug-in connector M12
General data
Ambient temperature -20…+40 °C (above 40 °C derating)
Degree of protection IP 65
Relative humidity 10…95 %, no condensation
Operating level ≤1000 m
Chemical composition Halogen-free, LBS-free, RoHS conformed
Mounting Wall installation
Orientation optional, preferably vertical
Error confirmation/reset Automatic error reset via process image
Approval AS-i
Noise immunity meets EN 61800-3
Noise emission meets EN 61800-3 as well as limit value
class A according to EN 55011 and EN
55014
Climate class 3 K3
Type of cooling Self-cooling
I) Ordering information
Accessories
Energy bus cable (jack–plug)
(xx=cable length)
96.453.xx80.1
Motor connection cable (plug–free end)
(xx=cable length)
96.453.xx84.1
AS-i Handheld PPG 1 83.209.2204.1
AS-i programming cable 1.5 m 83.209.2205.0
Appendix: Process image (cyclical data exchange)
Process outputs Function
BIT 3 BIT 2 BIT 1 BIT 0
0 0 0 0 Motor stop
0 0 1 0 Enable clockwise (*) motor stop
0 0 1 1 Motor clockwise
0 1 0 0 Enable counterclockwise (*) Motor
stop
0 1 0 1 Motor counterclockwise
1 0 0 0 Acknowledgement (with start error
and after end „write parameter
string“)
x x x x reserved, motor stop
(*) The direction is enabled without delay (pause on reverse) and thus, a higher
switching frequency is made possible with this function.
In cyclical slave-master mode, the state of three sensor inputs and a „Ready for
operation“ message from the drive were reported according to the binary table of
the AS-i input bits:
Process inputs Function
BIT 0 X7 / „1“=24 V
BIT 1 X8 / „1“=24 V
BIT 2 X8 / „1“=24 V
BIT 3 „1“= starter ready (no starter error)
J) Status LED error diagnostics
Fault
Cause
Error Over-
load
Fault M rev M fwd
Current in right rotation > In
−Motor load too high
−Parameter: wrong motor current value
x x
Current in left rotation > In
−Motor load too high
−Parameter: wrong motor current value
x x
Overload switch-off
−Motor load too high
−Parameter: wrong motor protection
value
x flashes flashes
Motor current undercut or motor current
asymmetry switch-off
−Motor supply line interrupted
−Parameter: wrong minimum current
value
−Parameter: wrong asymmetry value
x x flashes flashes
No rotating field detected
−Wrong phase connection
−Motor not connected
x flashes flashes
Excess temperature switch-off
−Temperature inside housing too high
flashes flashes
Invalid parameter set transmitted
−Valid parameters transmitted to soft
starter
flashes flashes
Spin-up or spin-down time counterclock-
wise
flashes
Spin-up or spin-down time clockwise flashes
Flash error
−No access to flash memory
x x x flashes flashes