Vega VEGAPULS 6X User manual

Quick setup guide
Radar sensor for continuous level
measurement of liquids and bulk solids
VEGAPULS 6X
Two-wire 4 … 20 mA/HART
plus PLICSMOBILE 81
Document ID: 66376

2
Contents
VEGAPULS 6X • Two-wire 4 … 20 mA/HART
66376-EN-220111
Contents
1 For your safety ......................................................................................................................... 3
1.1 Authorised personnel ....................................................................................................... 3
1.2 Appropriate use................................................................................................................ 3
1.3 Warning about incorrect use............................................................................................. 3
1.4 General safety instructions............................................................................................... 3
1.5 Modes for worldwide use.................................................................................................. 4
1.6 Installation and operation in the USA and Canada ........................................................... 4
2 Product description ................................................................................................................. 5
2.1 Conguration.................................................................................................................... 5
3 Mounting................................................................................................................................... 6
3.1 Mounting instructions ....................................................................................................... 6
4 Connecting to power supply................................................................................................... 8
4.1 Connection steps voltage supply...................................................................................... 8
4.2 Wiring plan double chamber housing with radio module PLICSMOBILE 81..................... 9
5 Set up with the display and adjustment module ................................................................ 10
5.1 Insert display and adjustment module............................................................................ 10
5.2 Parameterization ............................................................................................................ 10
6 Setup with smartphone/tablet (Bluetooth).......................................................................... 16
6.1 Preparations................................................................................................................... 16
6.2 Connecting..................................................................................................................... 16
6.3 Parameterization ............................................................................................................ 17
7 Menu overview ....................................................................................................................... 19
7.1 Display and adjustment module ..................................................................................... 19
8 Supplement ............................................................................................................................ 22
8.1 Technical data ................................................................................................................ 22
Information:
This quick setup guide enables quick setup and commissioning of
your instrument.
Youcanndsupplementaryinformationinthecorresponding,more
detailed Operating Instructions Manual as well as the Safety Manual
thatcomeswithinstrumentswithSILqualication.Thesemanualsare
available on our homepage.
Operating instructions VEGAPULS 6X - Two-wire 4 … 20 mA/
HARTplus PLICSMOBILE 81: Document-ID 66368
Editing status of the quick setup guide: 2022-01-11

3
1 For your safety
VEGAPULS 6X • Two-wire 4 … 20 mA/HART
66376-EN-220111
1 For your safety
1.1 Authorised personnel
All operations described in this documentation must be carried out
onlybytrained,qualiedpersonnelauthorisedbytheplantoperator.
Duringworkonandwiththedevice,therequiredpersonalprotective
equipment must always be worn.
1.2 Appropriate use
VEGAPULS 6X is a sensor for continuous level measurement.
Youcannddetailedinformationabouttheareaofapplicationin
chapter " Product description".
Operational reliability is ensured only if the instrument is properly
usedaccordingtothespecicationsintheoperatinginstructions
manual as well as possible supplementary instructions.
1.3 Warning about incorrect use
Inappropriate or incorrect use of this product can give rise to applica-
tion-specichazards,e.g.vesseloverllthroughincorrectmounting
or adjustment. Damage to property and persons or environmental
contaminationcanresult.Also,theprotectivecharacteristicsofthe
instrument can be impaired.
1.4 General safety instructions
This is a state-of-the-art instrument complying with all prevailing
regulations and directives. The instrument must only be operated in a
technicallyawlessandreliablecondition.Theoperatorisresponsi-
ble for the trouble-free operation of the instrument. When measuring
aggressive or corrosive media that can cause a dangerous situation
iftheinstrumentmalfunctions,theoperatorhastoimplementsuitable
measures to make sure the instrument is functioning properly.
Thesafetyinstructionsinthisoperatinginstructionsmanual,thena-
tional installation standards as well as the valid safety regulations and
accident prevention rules must be observed by the user.
Forsafetyandwarrantyreasons,anyinvasiveworkonthedevice
beyond that described in the operating instructions manual may be
carried out only by personnel authorised by the manufacturer. Arbi-
traryconversionsormodicationsareexplicitlyforbidden.Forsafety
reasons,onlytheaccessoryspeciedbythemanufacturermustbe
used.
Toavoidanydanger,thesafetyapprovalmarkingsandsafetytipson
the device must also be observed.
The low transmitting power of the radar sensor is far below the inter-
nationallyapprovedlimits.Nohealthimpairmentsaretobeexpected
with intended use.The band range of the measuring frequency can
be found in chapter " Technical data".

4
1 For your safety
VEGAPULS 6X • Two-wire 4 … 20 mA/HART
66376-EN-220111
1.5 Modes for worldwide use
Countryspecicsettingsfortheradarsignalsaredeterminedviathe
mode.The operating mode must be set in the operating menu via the
respective operating tool at the beginning of the setup.
Caution:
Operating the device without selecting the appropriate country group
constitutes a violation of the regulations of the radio approvals of the
respective country.
1.6 Installation and operation in the USA and
Canada
This information is only valid for USA and Canada. Hence the follow-
ingtextisonlyavailableintheEnglishlanguage.
Installations in the US shall comply with the relevant requirements of
the National Electrical Code (ANSI/NFPA 70).
Installations in Canada shall comply with the relevant requirements of
the Canadian Electrical Code
A Class 2 power supply unit has to be used for the installation in the
USA and Canada.

5
2 Product description
VEGAPULS 6X • Two-wire 4 … 20 mA/HART
66376-EN-220111
2 Product description
2.1 Conguration
Thetypelabelcontainsthemostimportantdataforidenticationand
use of the instrument:
5
4
3
2
1
Fig. 1: Layout of the type label (example)
1 Device type, order number
2 Field for approvals, product code
3 Technical data
4 QR-code for VEGA Tools app
5 Reminder to observe the instrument documentation
The type label contains also the serial number of the instrument. With
ityoucanndthefollowinginstrumentdataonourhomepage:
• Product information
• Deviceconguration
• Related documentation
• Further documents
Move to " www.vega.com"andenterinthesearcheldtheserial
number of your instrument.
Alternatively,youcanaccessthedataviayoursmartphone:
• Download the VEGA Tools app from the " Apple App Store" or the
" Google Play Store"
• Scan the QR-code on the type label of the device or
• Enter the serial number manually in the app
Type label
Serial number - Instru-
ment search

6
3 Mounting
VEGAPULS 6X • Two-wire 4 … 20 mA/HART
66376-EN-220111
3 Mounting
3.1 Mounting instructions
Radar sensors for level measurement emit electromagnetic waves.
The polarization is the direction of the electrical component of these
waves.
Thepolarizationdirectionismarkedbyanoseonthehousing,see
following drawing:
1
Fig. 2: Position of the polarisation
1 Nose for marking the direction of polarisation
Turningthehousingchangesthepolarisationandthustheeectof
false echoes on the measured value.
Note:
Therefore,payattentiontothepositionofthepolarisationwhen
mountingorwhenmakingsubsequentchanges.Fixthehousingto
prevent a change in the metrological properties (see chapter " Hous-
ing features").
Whenmountingthedevice,keepadistanceofatleast200mm
(7.874 in) from the vessel wall. If the device is installed in the center
ofdishedorroundvesseltops,multipleechoescanarise.However,
these can be suppressed by an appropriate adjustment (see chapter
" Setup").
Note:
Ifyoucannotmaintainthisdistance,youshouldcarryoutafalse
signal suppression during setup. This applies especially if buildup on
thevesselwallistobeexpected.1)
> 200 mm
(7.87
")
Fig. 3: Mounting of the radar sensor on round vessel tops
Polarisation
Mounting position -
liquids
1) Inthiscase,itisrecommendedtorepeatthefalsesignalsuppressionata
latertimewithexistingbuildup.

7
3 Mounting
VEGAPULS 6X • Two-wire 4 … 20 mA/HART
66376-EN-220111
In vessels with conical bottom it can be advantageous to mount the
deviceinthecentreofthevessel,asmeasurementisthenpossible
down to the bottom.
Fig. 4: Mounting of the radar sensor on vessels with conical bottom
Mount the instrument at least 200 mm (7.874 in) away from the vessel
wall.
200 mm
(7.87
")
Fig. 5: Mounting the radar sensor on the vessel top
Note:
Ifyoucannotmaintainthisdistance,youshouldcarryoutafalse
signal suppression during setup. This applies especially if buildup on
thevesselwallistobeexpected.2)
Mounting position - bulk
solids
2) Inthiscase,itisrecommendedtorepeatthefalsesignalsuppressionata
latertimewithexistingbuildup.

8
4 Connecting to power supply
VEGAPULS 6X • Two-wire 4 … 20 mA/HART
66376-EN-220111
4 Connecting to power supply
4.1 Connection steps voltage supply
The connection of the voltage supply is made via spring-loaded ter-
minals. A small screwdriver is required to open the terminals. Solid as
wellasexiblecoreswithoutcableendsleevescanbeused.
Proceed as follows:
1. Unscrew the housing lid
2. Loosen compression nut of the cable gland and remove blind
plug
3. Removeapprox.10cm(4in)ofthecablemantle,stripapprox.
1 cm (0.4 in) of insulation from the ends of the individual wires
4. Insert the cable into the cable gland through the cable entry
Fig. 6: Connection steps 4 and 5
5. Lift the opening levers of the terminals with a screwdriver
6. Insert the wire ends into the open terminals according to the wir-
ing plan
7. Pressdowntheopeningleversoftheterminals,youwillhearthe
terminal spring closing
8. Check the hold of the wires in the terminals by lightly pulling on
them
9. Connecttheshieldingtotheinternalgroundterminal,connectthe
externalgroundterminaltopotentialequalisation
10. Tighten the compression nut of the cable entry gland. The seal
ring must completely encircle the cable
11. Screw the housing lid back on
Theelectricalconnectionisnished.
Connection technology
Connection procedure

9
4 Connecting to power supply
VEGAPULS 6X • Two-wire 4 … 20 mA/HART
66376-EN-220111
4.2 Wiring plan double chamber housing with
radio module PLICSMOBILE 81
4...20mA Display
12
+
( ) (-)
2
1
Fig. 7: Electronics compartment - double chamber housing
1 Internal connection to the connection compartment
1
SIM
Status
Send Off On
123
+
-
Fig. 8: Connection compartment - Radio module PLICSMOBILE 81
1 Voltage supply
Youcannddetailedinformationforconnectionintheoperating
instructions " PLICSMOBILE".
Electronics compartment
Connection compart-
ment - Radio module
PLICSMOBILE 81

10
5 Set up with the display and adjustment module
VEGAPULS 6X • Two-wire 4 … 20 mA/HART
66376-EN-220111
5 Set up with the display and adjustment
module
5.1 Insert display and adjustment module
The display and adjustment module can be inserted into the sensor
andremovedagainatanytime.Youcanchooseanyoneoffourdier-
ent positions - each displaced by 90°. It is not necessary to interrupt
the power supply.
Proceed as follows:
1. Unscrew the housing lid
2. Place the display and adjustment module on the electronics in the
desired position and turn it to the right until it snaps in.
3. Screw housing lid with inspection window tightly back on
Disassembly is carried out in reverse order.
Thedisplayandadjustmentmoduleispoweredbythesensor,anad-
ditional connection is not necessary.
Fig. 9: Installing the display and adjustment module in the double chamber
housing
Note:
Ifyouintendtoretrottheinstrumentwithadisplayandadjustment
moduleforcontinuousmeasuredvalueindication,ahigherlidwithan
inspection glass is required.
5.2 Parameterization
5.2.1 Lock/Unlock adjustment
In this menu item you safeguard the sensor parameters against unau-
thorizedorunintentionalmodications.
Whentheadjustmentisblocked,onlythefollowingadjustmentfunc-
tions are possible without entering the device code:
Lock/Unlock adjustment
Other manuals for VEGAPULS 6X
9
Table of contents
Other Vega Accessories manuals

Vega
Vega VEGAPULS 66 User manual

Vega
Vega VEGAPULS 68 User manual

Vega
Vega VEGAPULS 69 User manual

Vega
Vega VEGAPULS 69 User manual

Vega
Vega VEGAPULS 61 User manual

Vega
Vega VEGASON 61 User manual

Vega
Vega VEGAPULS 69 User manual

Vega
Vega VEGAFLEX 82 User manual

Vega
Vega VEGAPULS 68 User manual

Vega
Vega VEGAPULS 62 User manual

Vega
Vega VEGAFLEX 81 User manual

Vega
Vega VEGABAR 81 User manual

Vega
Vega VEGAFLEX 86 User manual

Vega
Vega VEGASON 61 User manual

Vega
Vega vegaflex 83 User manual

Vega
Vega VEGAPULS 66 Profibus PA User manual

Vega
Vega VEGAWAVE 61 Instruction Manual

Vega
Vega VEGAPULS SR 68 User manual

Vega
Vega vegaflex 83 User manual

Vega
Vega VEGAFLEX 81 User manual