Quick setup guide
Pressure transmitter with ceramic
measuring cell
VEGABAR 82
Secondary sensor for electronic dierential
pressure
Document ID: 46332

2
Contents
VEGABAR 82 • Secondary sensor for electronic dierential pressure
46332-EN-220624
Contents
1 For your safety ......................................................................................................................... 3
1.1 Authorised personnel ....................................................................................................... 3
1.2 Appropriate use................................................................................................................ 3
1.3 Warning about incorrect use............................................................................................. 3
1.4 General safety instructions............................................................................................... 3
1.5 EU conformity................................................................................................................... 3
1.6 Environmental instructions ............................................................................................... 4
2 Product description ................................................................................................................. 5
2.1 Conguration.................................................................................................................... 5
3 Mounting................................................................................................................................... 6
3.1 General instructions for use of the instrument .................................................................. 6
3.2 Ventilation and pressure compensation............................................................................ 6
3.3 Combination Primary/Secondary sensor.......................................................................... 6
4 Connecting to power supply................................................................................................... 9
4.1 Connecting....................................................................................................................... 9
4.2 Single chamber housing................................................................................................. 10
4.3 Connection example ...................................................................................................... 10
5 Set up with the display and adjustment module ................................................................ 12
5.1 Parameter adjustment - Quick setup .............................................................................. 12
5.2 Parameter adjustment - Extended adjustment................................................................ 16
5.3 Menu overview ............................................................................................................... 17
6 Supplement ............................................................................................................................ 20
6.1 Technical data ................................................................................................................ 20
Information:
This quick setup guide enables quick setup and commissioning of
your instrument.
You can nd supplementary information in the corresponding, more
detailed Operating Instructions Manual as well as the Safety Manual
that comes with instruments with SIL qualication. These manuals are
available on our homepage.
Operating instructions VEGABAR 82 - Secondary sensor for
electronic dierential pressure: Document-ID 45050
Editing status of the quick setup guide: 2022-04-20

3
1 For your safety
VEGABAR 82 • Secondary sensor for electronic dierential pressure
46332-EN-220624
1 For your safety
1.1 Authorised personnel
All operations described in this documentation must be carried out
only by trained, qualied personnel authorised by the plant operator.
During work on and with the device, the required personal protective
equipment must always be worn.
1.2 Appropriate use
As Secondary Device, the VEGABAR 82 is part of an electronic dif-
ferential pressure meaasurement.
You can nd detailed information about the area of application in
chapter " Product description".
Operational reliability is ensured only if the instrument is properly
used according to the specications in the operating instructions
manual as well as possible supplementary instructions.
1.3 Warning about incorrect use
Inappropriate or incorrect use of this product can give rise to applica-
tion-specic hazards, e.g. vessel overll through incorrect mounting
or adjustment. Damage to property and persons or environmental
contamination can result. Also, the protective characteristics of the
instrument can be impaired.
1.4 General safety instructions
This is a state-of-the-art instrument complying with all prevailing
regulations and directives. The instrument must only be operated in a
technically awless and reliable condition. The operator is responsi-
ble for the trouble-free operation of the instrument. When measuring
aggressive or corrosive media that can cause a dangerous situation
if the instrument malfunctions, the operator has to implement suitable
measures to make sure the instrument is functioning properly.
The safety instructions in this operating instructions manual, the na-
tional installation standards as well as the valid safety regulations and
accident prevention rules must be observed by the user.
For safety and warranty reasons, any invasive work on the device
beyond that described in the operating instructions manual may be
carried out only by personnel authorised by the manufacturer. Arbi-
trary conversions or modications are explicitly forbidden. For safety
reasons, only the accessory specied by the manufacturer must be
used.
To avoid any danger, the safety approval markings and safety tips on
the device must also be observed.
1.5 EU conformity
The device fulls the legal requirements of the applicable EU direc-
tives. By axing the CE marking, we conrm the conformity of the
instrument with these directives.

4
1 For your safety
VEGABAR 82 • Secondary sensor for electronic dierential pressure
46332-EN-220624
The EU conformity declaration can be found on our homepage.
Due to the design of its process ttings, the device does not subject
of EU pressure device directive if it is operated at process pressures
≤ 200 bar.
1.6 Environmental instructions
Protection of the environment is one of our most important duties.
That is why we have introduced an environment management system
with the goal of continuously improving company environmental pro-
tection. The environment management system is certied according
to DIN EN ISO 14001.
Please help us full this obligation by observing the environmental
instructions in this manual:
• Chapter " Packaging, transport and storage"
• Chapter " Disposal"

5
2 Product description
VEGABAR 82 • Secondary sensor for electronic dierential pressure
46332-EN-220624
2 Product description
2.1 Conguration
The type label contains the most important data for identication and
use of the instrument:
7
6
4
5
2
3
1
Conne
Conne
Conn
C
Conn
C
CC
prim
prim
prim
prim
p
ary dary d
ary d
ar
ary d
d
evice
evice
i
vice
vic
evice
Connect to
p
rimar
y
Fig. 1: Layout of the type label (example)
1 Product code
2 Field for approvals
3 Technical data
4 Serial number of the instrument
5 QR code
6 Symbol of the device protection class
7 ID numbers, instrument documentation
The type label contains the serial number of the instrument. With it
you can nd the following instrument data on our homepage:
• Product code (HTML)
• Delivery date (HTML)
• Order-specic instrument features (HTML)
• Operating instructions and quick setup guide at the time of ship-
ment (PDF)
• Test certicate (PDF) - optional
Move to " www.vega.com" and enter in the search eld the serial
number of your instrument.
Alternatively, you can access the data via your smartphone:
• Download the VEGA Tools app from the " Apple App Store" or the
" Google Play Store"
• Scan the QR-code on the type label of the device or
• Enter the serial number manually in the app
Type label
Serial number - Instru-
ment search

6
3 Mounting
VEGABAR 82 • Secondary sensor for electronic dierential pressure
46332-EN-220624
3 Mounting
3.1 General instructions for use of the instrument
Protect your instrument against moisture ingress through the following
measures:
• Use a suitable connection cable (see chapter " Connecting to
power supply")
• Tighten the cable gland or plug connector
• Lead the connection cable downward in front of the cable entry or
plug connector
This applies mainly to outdoor installations, in areas where high
humidity is expected (e.g. through cleaning processes) and on cooled
or heated vessels.
Note:
Make sure that during installation or maintenance no moisture or dirt
can get inside the instrument.
To maintain the housing protection, make sure that the housing lid is
closed during operation and locked, if necessary.
3.2 Ventilation and pressure compensation
1 2 3
4 4 4
Fig. 2: Position of the lter element - non-Ex, Ex-ia version
1 Plastic, stainless steel housing (precision casting)
2 Aluminium housing
3 Stainless steel housing (electropolished)
4 Filter element
With the following instruments a blind plug is installed instead of the
lter element:
• Instruments in protection IP66/IP68 (1 bar) - ventilation via capillar-
ies in non-detachable cable
• Instruments with absolute pressure
3.3 Combination Primary/Secondary sensor
In principle, any sensor combination within the instrument series is
allowed. The following requirements must be fullled:
• Conguration of the sensor suitable for electronic dierential pres-
sure
• Pressure type is identical for both sensors, i.e. relative pressure/
relative pressure or absolute pressure/absolute pressure
Protection against mois-
ture
Filter element - Position

7
3 Mounting
VEGABAR 82 • Secondary sensor for electronic dierential pressure
46332-EN-220624
• Primary Device measures the higher pressure
• Measurement setup as shown in the following chapters
The measuring range of each sensor is selected such that it ts the
measuring loop. For this, the max. recommended turn down must be
noted. See chapter " Technical data". It is absolutely necessary the
the measuring ranges of Primary and Secondary Device correspond.
Measurement result = Measured value of Primary (total pres-
sure) - measured value of Secondary (static pressure)
Depending on the application, individual combinations can result, see
following examples:
Data
Application: Level measurement
Medium: Water
Vessel height: 12 m, hydrostatic pressure = 12 m x 1000 kg/m3x
9.81 m/s2 = 117.7 kPa = 1.18 bar
Superimposed pressure: 1 bar
Total pressure: 1.18 bar + 1 bar = 2.18 bar
Instrument selection
Nominal measuring range Primary: 2.5 bar
Nominal measuring range Secondary: 1 bar
Turn Down: 2.5 bar/1.18 bar = 2.1 : 1
Data
Application: Level measurement
Medium: Water
Vessel height: 500 mm, hydrostatic pressure = 0.50 m x 1000 kg/m3x
9.81 m/s2 = 4.9 kPa = 0.049 bar
Superimposed pressure: 350 mbar = 0.35 bar
Total pressure: 0.049 bar + 0.35 bar = 0.399 bar
Instrument selection
Nominal measuring range Primary: 0.4 bar
Nominal measuring range Secondary: 0.4 bar
Turn Down: 0.4 bar /0.049 bar = 8.2 : 1
Data
Application: Dierential pressure measurement
Medium: Gas
Static pressure: 0.8 bar
Dierential pressure on orice: 50 mbar = 0.050 bar
Total pressure: 0.8 bar + 0.05 bar = 0.85 bar
Instrument selection
Nominal measuring range Primary: 1 bar
Nominal measuring range Secondary: 1 bar
Turn Down: 1 bar/0.050 bar = 20 : 1
Example - large vessel
Example - small vessel
Example - orice in
pipeline

8
3 Mounting
VEGABAR 82 • Secondary sensor for electronic dierential pressure
46332-EN-220624
The measuring result (level, pressure dierence) as well as measured
value Secondary (static or superimposed pressure) are output by the
sensor. Depending on the instrument version, output as 4 … 20 mA
signal or digitally via HART, Probus PA or Foundation Fieldbus.
Output measured values

9
4 Connecting to power supply
VEGABAR 82 • Secondary sensor for electronic dierential pressure
46332-EN-220624
4 Connecting to power supply
4.1 Connecting
The connection to the Primary Device is carried out through spring-
loaded terminals in the respective housing. For this, use the supplied,
confectioned cable. Solid cores as well as exible cores with cable
end sleeves are inserted directly into the terminal openings.
In case of exible cores without end sleeves, press the terminal from
above with a small screwdriver, the terminal opening is then free.
When the screwdriver is released, the terminal closes again.
Information:
The terminal block is pluggable and can be removed from the
electronics. To do this, lift the terminal block with a small screwdriver
and pull it out. When reinserting the terminal block, you should hear it
snap in.
You can nd further information on the max. wire cross-section under
" Technical data - Electromechanical data".
Proceed as follows:
1. Unscrew the housing lid
2. Loosen compression nut of the cable gland and remove blind
plug
3. Remove approx. 10 cm (4 in) of the cable mantle, strip approx.
1 cm (0.4 in) insulation from the individual wires or use supplied
connection cable
4. Insert the cable into the sensor through the cable entry
Fig. 3: Connection steps 5 and 6
5. Insert the wire ends into the terminals according to the wiring plan
6. Check the hold of the wires in the terminals by lightly pulling on
them
Connection technology
Connection procedure

10
4 Connecting to power supply
VEGABAR 82 • Secondary sensor for electronic dierential pressure
46332-EN-220624
7. Connect the shielding to the internal ground terminal, connect the
external ground terminal to potential equalisation
8. Tighten the compression nut of the cable entry gland. The seal
ring must completely encircle the cable
9. Unscrew the blind plug on the Primary, screw in the supplied
cable gland
10. Connection cable to Primary, see steps 3 to 8
11. Screw the housing lid back on
The electrical connection is nished.
4.2 Single chamber housing
The following illustration applies to the non-Ex, Ex-ia and Ex-d-ia
version.
5678 4
2
1
connect to Primary
Fig. 4: Wiring plan VEGABAR 82 Secondary Device
1 To the Primary Device
2 Ground terminal for connection of the cable screening 1)
4.3 Connection example
5678
4
2
3
1
4
connect to Primary
5
12
+
( ) (-)
678
4...20mA
Fig. 5: Connection example, electronic dierential pressure
1 Primary Device
2 Secondary Device
3 Connection cable
4 Supply and signal circuit Primary Device
Electronics and connec-
tion compartment
Connection example,
electronic dierential
pressure
1) Connect shielding here. Connect ground terminal on the outside of the hous-
ing to ground as prescribed. The two terminals are galvanically connected.
Other manuals for VEGABAR 82
22
Table of contents
Other Vega Accessories manuals

Vega
Vega VEGAPULS 62 User manual

Vega
Vega VEGAPULS WL 61 User manual

Vega
Vega VEGAPULS 61 User manual

Vega
Vega VEGAPULS 67 User manual

Vega
Vega VEGAPULS Air 23 User manual

Vega
Vega VEGAPULS 69 User manual

Vega
Vega VEGAFLEX 86 User manual

Vega
Vega VEGAPULS WL 61 User manual

Vega
Vega VEGAPULS 66 User manual

Vega
Vega VEGAPULS 66 User manual

Vega
Vega vegacap 62 User manual

Vega
Vega VEGAPULS 6X User manual

Vega
Vega VEGAPULS 6X User manual

Vega
Vega VEGAPULS 62 User manual

Vega
Vega vegaflex 83 User manual

Vega
Vega SOLITRAC 31 User manual

Vega
Vega VEGAPULS 64 User manual

Vega
Vega VEGAKON 61 User manual

Vega
Vega VEGAFLEX 81 User manual

Vega
Vega VEGAPULS 62 User manual