SJE SP6R-X User manual

User Manual
SP6R-X
LEVEL CONTROLLER
INSTALLATION INSTRUCTIONS
Manufactured by: SJE Inc.
Technical support: +1-800-746-6287
www.csicontrols.com www.primexcontrols.com www.sjerhombus.com

TABLE OF CONTENTS
Warnings ............................................................................... 1
Introduction and Specifications ............................................. 2
Main Screen .......................................................................... 3
User Interface........................................................................ 3
Main Menu ............................................................................ 4
Relay Setpoints ..................................................................... 4
Level Simulation.................................................................... 5
Analog Scaling Menu ............................................................ 6
Level Units ............................................................................ 7
MODBUS Setup Menu.......................................................... 8
Analog I/O Status Screen ..................................................... 8
Operation .............................................................................. 9
I/O Terminal Configuration.................................................. 10
SP6R-X I/O Table .............................................................. 11
MODBUS Communication .................................................. 12
MODBUS Registers ............................................................ 13
Mounting Dimensions.......................................................... 14
Controller Dimensions......................................................... 15
Electrical Wiring Diagram.................................................... 16
SP6R-X Controller Setpoints List........................................ 17
SJE® SP6R-X Controller User Manual

WARNINGS
Failure to read and understand the information provided in this manual may result in personal injury or
death, damage to the product or product failure. Please read each section in its entirety and be sure
you understand the information provided in the section and related sections before attempting any of
the procedures or operations given.
Failure to follow these precautions could result in serious injury or death.
Keep these instructions with warranty after installation. This product must be
installed in accordance with National Electrical Code, ANSI/NFPA 70 so as to
prevent moisture from entering or accumulating within the controller housing.
ELECTRICAL SHOCK HAZARD
A qualified service person must install and service this product
according to applicable codes and electrical schematics.
Disconnect power prior to servicing any equipment with the
SP6R-X controller.
EXPLOSION OR FIRE HAZARD
Do not use this product with flammable liquids. Do not install in
hazardous locations as defined by National Electrical Code,
ANSI/NFPA 70.
• Do not connect power to this equipment if it has been damaged or has any missing parts.
• The SP6R-X contains no serviceable parts; do not attempt to repair this equipment.
• Do not install in areas with: excessive or conductive dust, corrosive or flammable gas,
moisture or rain, excessive heat, regular impact shocks, or excessive vibration.
SJE® 1 SP6R-X Controller User Manual
Warning: Users must read this manual and understand controller operation before changing any settings.
Entering incorrect settings may result in damage to equipment.
If the SP6R-X controller was shipped pre-installed in a control panel, some default values may have been
changed at the factory in order to properly test the control panel operation. The user must adjust the settings
to the requirements of their particular installation
The user should always keep a record of the settings before making changes, in case there is a need to
revert to previous settings. The user should also record all settings changed for use in programming a new
controller in case a replacement is ever needed.
Always thoroughly test controller operation in the installed configuration to verify user settings.

INTRODUCTION & SPECIFICATIONS
Thank you for your purchase of the SP6R-X controller. This manual explains the features and
operations of the SP6R-X controller which was designed to monitor a 4-20mA input signal. The
controller features six programmable relay outputs that can be used for control and alarm puposes.
The input range is fully configurable. A rotary selector knob is included along with back and escape
pushbuttons for intuitive menu navigation and quick setting adjustments. A simulation mode allows the
user to easily test the setpoints and relay operation.
GENERAL
Six configurable relay outputs
Normally-Open or Normally-Closed operation
Configurable units
Operates using 4-20mA level transmitter
Scalable 4-20mA output
Relay ouput status indicator on display
Rotary selector for menu navigation
2.7” blue OLED 64 x 256 pixel display
ELECTRICAL SPECIFICATIONS
Power
• 24 VDC (19-28 VDC, 325 mA max)
• Optional battery backup
Dedicated I/Os
• 6 relay outputs (120 VAC, 3A Max.)
• 1 analog input (4-20mA, 14 bit resolution,
non-isolated)
• 1 analog output (4-20mA, 12 bit resolution,
non-isolated, fully scalable)
Serial Communication Port
• RS-485 3-Wire (half duplex)
• Modbus RTU
• 9600 baud, 1 stop bit, no parity
• Designed for complete compatibility with the
SJE Panel Link™Gateway.
File #E305146
DIMENSIONS
7.2 x 5.7 x 2.5 inches (18.3 x 14.5 x 6.4 cm)
SYSTEM
• Individual on and off setpoints for each relay
output
• Level Simulation mode
• Configurable relay operation in case of level
transmitter failure
• The bar graph range is user adjustable
ENVIRONMENT
Operational temperature -4ºF to 158ºF (-20ºC to
70ºC)
Storage temperature -4ºF to 185ºF (-20ºC to
85ºC)
Relative Humidity (RH) 5% to 95%
(non-condensing)
Not outdoor rated—use only indoors or inside an
outdoor rated enclosure
An SP6R-X-N4X is avaliable which includes an
SP6R-X controller mounted within a NEMA 4X
enclosure with a pre-wired power supply and
terminal blocks.
SJE® 2 SP6R-X Controller User Manual

PROGRAMMING
MAIN SCREEN
The main screen gives the operator an overview of the system status including any active alarms.
Relay Output Status Indicators
Level Bar Graph
(user scalable)
Modbus Communication Indicator
Process Level Indication
Outlined Box =
Relay Open
Process Level Units
(user settable)
Solid Box =
Relay Closed
USER INTERFACE
PRESS FOR ENTER
Rotary Selector Knob
• Turn knob for scrolling
through menus or
adjusting values.
• Press knob for ENTER
or to save settings.
Power Indicator LED
Button Returns To Previous Menu
Screen, and Exits a Parameter Edit
Screen Without Saving Changes.
ESC
Back Button for Stepping
Backward and Changing Value
Adjustment Scale.
SJE® 3 SP6R-X Controller User Manual

MAIN MENU
While in the Main Display screen, press the ENTER button to view the Main Menu.
RELAY SETPOINTS
These are the Relay Setpoints that can be adjusted.
An edit screen can be brought up by pressing the selection knob when the desired setpoint is
highlighted.
To adjust the value simply scroll the knob to the desired value and click the knob to save the setting.
The adjustment scale will default to tenths. The adjustment scale can be set to tenths, ones, tens
and hundreds as shown on previous page. Depending on the specific adjustment, hundreds may not
be an option.
To adjust the scale, click the ◄button until the desired increment is highlighted.
Ones will be adjusted Tens will be adjusted Hundreds will be adjusted
SJE®4 SP6R-X Controller User Manual

The default scale is feet. This can be changed using the Analog Scaling menu.
To ignore any changes and return to the previous screen, press the ESC button or press and hold
the ◄button.
LEVEL SIMULATION
When Enabled, Level Simulation is used to temporarily use the selector wheel to simulate input
level changes. This can be helpful for troubleshooting a system to ensure the controller is functioning
correctly without actually having various level scenarios available.
Rotate the selector knob to make fine adjustments. To make coarse adjustments, press and hold the
◄button while rotating the selector knob.
SJE® 5 SP6R-X Controller User Manual

The Analog Scaling menu contains the following 8 settings.
ANALOG INPUT (4mA)
Set this to the displayed level reading when the signal value is equal to 4 mA.
Allowable range: 0-999.9.
ANALOG INPUT (20mA)
Set this to the displayed level reading when the signal value is equal to 20 mA.
Allowable range: 0-999.9.
TRANSMITTER OFFSET
Use the Transmitter Offset to add a constant amount to the measured level input. For example,
in the case where a 20.0-ft range submersible level transmitter was mounted one foot above the
bottom of the tank, the Transmitter Offset setting would be “001.0 ft”. This would add 1.0 ft to
whatever the input reading would be, so that all displayed levels were with respect to the bottom of
the tank, not merely the bottom of the level sensor. In the example given, a 20mA input would be
displayed as 21.0 ft. All level setpoints are referenced to the displayed level, which includes any
Transmitter Offset.
Allowable range: -999.9 – to 999.9.
ANALOG OUT LOW LEVEL
This setting defines the displayed level reading that corresponds with 4.0 mA on the analog output.
This can be set below or above the Analog Out High Level setting.
ANALOG OUT HIGH LEVEL
This setting defines the displayed level reading that corresponds with 20.0 mA on the analog output.
This can be set above or below the Anlog Out Low Level setting.
Example: If you want the 4-20mA output to be scaled such that it ouputs 4mA at a 5.0-ft level
reading, and 20 mA at a 10.0-ft level reading, you would set the Analog Out Low Level setting
to 5.0 ft, and the Anolog Out High Level setting to 10.0 ft.
BAR GRAPH MINIMUM
Set this value to the displayed level reading that should correspond with the bottom of the bar graph.
BAR GRAPH MAXIMUM
Set this value to the displayed level reading that should correspond with the top of the bar graph.
SJE®6 SP6R-X Controller User Manual
ANALOG SCALING MENU

LEVEL UNITS
This setting defines what units label is applied to the level input reading and all level settings. The
available settings are:
ft = Feet
in = Inches
m = Meters
cm = Centimeters
PSI = Pounds Per Square Inch
bar = Bar
kPa = Kilopascals
% = Percentage
°C = Degrees Celsius
°F = Degrees Fahrenheit
GPM = Gallons Per Minute
m³/hr = Cubic Meters Per Hour
V = Volts
A = Amps
mA = Milliamps
(none)= Blank, no units will be displayed
OUT-OF-RANGE BEHAVIOR
These settings for relay outputs 1-6 control the operation of each relay when the analog input is
out of its allowable range (below 3.75 mA or above 20.25 mA). By default, the relay outputs are off
(open) when the analog input is out of range. Within the allowable range, the relays operate accord-
ing to the relay setpoints.
SJE®7 SP6R-X Controller User Manual

MODBUS SETUP MENU
The Modbus Setup menu contains the following two settings:
NODE ADDRESS
This is the Modbus address of the SP6R-X.
BAUD RATE
The Modbus communication baud rate can be set to the following:
1200, 2400, 4800, 9600, 19.2K, 38.4K
ANALOG I/O STATUS SCREEN
ANALOG I/O STATUS
This screen shows the current in mA of the analog input (A Input) and analog output (A Output). This
can be used for troubleshooting to make sure the 4-20 mA signals are behaving as expected.
SJE®8 SP6R-X Controller User Manual
Table of contents
Other SJE Controllers manuals
Popular Controllers manuals by other brands

Digiplex
Digiplex DGP-848 Programming guide

YASKAWA
YASKAWA SGM series user manual

Sinope
Sinope Calypso RM3500ZB installation guide

Isimet
Isimet DLA Series Style 2 Installation, Operations, Start-up and Maintenance Instructions

LSIS
LSIS sv-ip5a user manual

Rockwell Automation
Rockwell Automation 1769-L31 installation instructions