(4) Read device parameters FillMaxDistance
Downlink: 06B1000000000000000000
Device returns:
86B1138800000000000000 (device current configuration parameter)
Level Sensor Calibrate configuration example:
FPort:0x0E
Description CmdID SensorType PayLoad(Fix =9 Bytes)
SetGlobal
CalibrateReq 0x01
0x36
0_Channel1,
Multiplier
(2bytes,Unsigned) Divisor
(2bytes,Unsigned) DeltValue
(2bytes,Signed) Reserved
(2Bytes,Fixed 0x00)
SetGlobal
CalibrateRsp 0x81
0_Channel1,
Status
(1Byte,0x00_success) Reserved
(7Bytes,Fixed 0x00)
GetGlobal
CalibrateReq 0x02 Channel
(1Byte,0_Channel1,1_Channel2,etc) Reserved
(8Bytes,Fixed 0x00)
GetGlobal
CalibrateRsp 0x82
0_Channel1,
Multiplier
(2bytes,Unsigned) Divisor
(2bytes,Unsigned) DeltValue
(2bytes,Signed) Reserved
(2Bytes,Fixed 0x00)
ClearGlobal
CalibrateReq 0x03 Reserved
(10Bytes,Fixed 0x00)
ClearGlobal
CalibrateRsp 0x83 Status
(1Byte,0x00_success) Reserved
(9Bytes,Fixed 0x00)
(1)Set the calibration (GlobalCalibrate configuration):
If the distance between the device and the water R718PE detects is 490mm and the actual distance is 500mm, it means the
calibration we want to make is +10mm.
Channel 1= 00, Multiplier = 000A, Divisor = 0000, DeltValue=0001
Downlink:013600000A000000010000
Response:
8136000000000000000000(Configuration success)
8136010000000000000000(Configuration failure)
(2)Check whether the setting in (1) calibration
Downlink:0236000000000000000000
Response:
823600000A000000010000(Current configuration)
(3)Clear the setting
Downlink:0300000000000000000000
Response:
8300000000000000000000(Configuration success)