NetApp AFF A300 User manual

Chassis
ONTAP Systems
NetApp
May 13, 2022
This PDF was generated from https://docs.netapp.com/us-en/ontap-systems/a300/chassis-replace-
overview.html on May 13, 2022. Always check docs.netapp.com for the latest.

Table of Contents
Chassis. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Ê1
Overview of chassis replacement - AFF A300 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Ê1
Shut down the controllers - - AFF A300 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Ê1
Replace hardware - AFF A300 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Ê4
Restore and verify the configuration - AFF A300 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Ê10

Chassis
Overview of chassis replacement - AFF A300
To replace the chassis, you must move the power supplies, fans, and controller modules
from the impaired chassis to the new chassis, and swap out the impaired chassis from
the equipment rack or system cabinet with the new chassis of the same model as the
impaired chassis.
All other components in the system must be functioning properly; if not, you must contact technical support.
•You can use this procedure with all versions of ONTAP supported by your system.
•This procedure is written with the assumption that you are moving the controller module or modules to the
new chassis, and that the chassis is a new component from NetApp.
•This procedure is disruptive. For a two-node cluster, you will have a complete service outage and a partial
outage in a multi-node cluster.
Shut down the controllers - - AFF A300
To replace the chassis, you must shutdown the controllers.
Option 1: Shut down the controller
You must shut down the controller or controller in the chassis prior to moving them to the new chassis.
About this task
•If you have a cluster with more than two controllers, it must be in quorum. If the cluster is not in quorum or
a healthy controller shows false for eligibility and health, you must correct the issue before shutting down
the impaired controller; see the Administration overview with the CLI.
•If AutoSupport is enabled, suppress automatic case creation by invoking an AutoSupport message:
system node autosupport invoke -node * -type all -message
MAINT=number_of_hours_downh
The following AutoSupport message suppresses automatic case creation for two hours: cluster1:*>
system node autosupport invoke -node * -type all -message MAINT=2h
Steps
1. If your system has two controller modules, disable the HA pair.
If your system is running
clustered ONTAP with…
Then…
Two controllers in the cluster cluster ha modify -configured false storage failover
modify -node node0 -enabled false
More than two controllers in the
cluster
storage failover modify -node node0 -enabled false
1

2. Halt the controller, pressing ywhen you are prompted to confirm the halt: system node halt -node
node_name
The confirmation message looks like the following:
Warning: This operation will cause controller "node-name" to be marked
as unhealthy. Unhealthy nodes do not participate in quorum voting. If
the controller goes out of service and one more controller goes out of
service there will be a data serving failure for the entire cluster.
This will cause a client disruption. Use "cluster show" to verify
cluster state. If possible bring other nodes online to improve the
resiliency of this cluster.
Do you want to continue? {y|n}:
You must perform a clean system shutdown before replacing the chassis to avoid losing
unwritten data in the nonvolatile memory (NVMEM/NVRAM). Depending on your system, if
the NVMEM/NVRAM LED is flashing, there is content in the NVMEM/NVRAM that has not
been saved to disk. You need to reboot the controller and start from the beginning of this
procedure. If repeated attempts to cleanly shut down the controller fail, be aware that you
might lose any data that was not saved to disk.
3. Where applicable, halt the second controller to avoid a possible quorum error message in an HA pair
configuration: system node halt -node second_node_name -ignore-quorum-warnings true
-skip-lif-migration-before-shutdown true
Answer ywhen prompted.
Option 2: Controllers are in a two-node MetroCluster configuration
To shut down the impaired controller, you must determine the status of the controller and, if necessary, switch
over the controller so that the healthy controller continues to serve data from the impaired controller storage.
About this task
•If you are using NetApp Storage Encryption, you must have reset the MSID using the instructions in the
"Return a FIPS drive or SED to unprotected mode" section of NetApp Encryption overview with the CLI.
•You must leave the power supplies turned on at the end of this procedure to provide power to the healthy
controller.
Steps
1. Check the MetroCluster status to determine whether the impaired controller has automatically switched
over to the healthy controller: metrocluster show
2. Depending on whether an automatic switchover has occurred, proceed according to the following table:
If the impaired controller… Then…
Has automatically switched over Proceed to the next step.
2

If the impaired controller… Then…
Has not automatically switched
over
Perform a planned switchover operation from the healthy controller:
metrocluster switchover
Has not automatically switched
over, you attempted switchover
with the metrocluster
switchover command, and the
switchover was vetoed
Review the veto messages and, if possible, resolve the issue and try
again. If you are unable to resolve the issue, contact technical
support.
3. Resynchronize the data aggregates by running the metrocluster heal -phase aggregates
command from the surviving cluster.
controller_A_1::> metrocluster heal -phase aggregates
[Job 130] Job succeeded: Heal Aggregates is successful.
If the healing is vetoed, you have the option of reissuing the metrocluster heal command with the
-override-vetoes parameter. If you use this optional parameter, the system overrides any soft vetoes
that prevent the healing operation.
4. Verify that the operation has been completed by using the metrocluster operation show command.
controller_A_1::> metrocluster operation show
Ê Operation: heal-aggregates
Ê State: successful
Start Time: 7/25/2016 18:45:55
Ê End Time: 7/25/2016 18:45:56
Ê Errors: -
5. Check the state of the aggregates by using the storage aggregate show command.
controller_A_1::> storage aggregate show
Aggregate Size Available Used% State #Vols Nodes RAID
Status
--------- -------- --------- ----- ------- ------ ----------------
------------
...
aggr_b2 227.1GB 227.1GB 0% online 0 mcc1-a2
raid_dp, mirrored, normal...
6. Heal the root aggregates by using the metrocluster heal -phase root-aggregates command.
3

mcc1A::> metrocluster heal -phase root-aggregates
[Job 137] Job succeeded: Heal Root Aggregates is successful
If the healing is vetoed, you have the option of reissuing the metrocluster heal command with the
-override-vetoes parameter. If you use this optional parameter, the system overrides any soft vetoes that
prevent the healing operation.
7. Verify that the heal operation is complete by using the metrocluster operation show command on
the destination cluster:
mcc1A::> metrocluster operation show
Ê Operation: heal-root-aggregates
Ê State: successful
ÊStart Time: 7/29/2016 20:54:41
Ê End Time: 7/29/2016 20:54:42
Ê Errors: -
8. On the impaired controller module, disconnect the power supplies.
Replace hardware - AFF A300
Move the power supplies, fans, and controller modules from the impaired chassis to the
new chassis, and swap out the impaired chassis from the equipment rack or system
cabinet with the new chassis of the same model as the impaired chassis.
Step 1: Move a power supply
Moving out a power supply when replacing a chassis involves turning off, disconnecting, and removing the
power supply from the old chassis and installing and connecting it on the replacement chassis.
1. If you are not already grounded, properly ground yourself.
2. Turn off the power supply and disconnect the power cables:
a. Turn off the power switch on the power supply.
b. Open the power cable retainer, and then unplug the power cable from the power supply.
c. Unplug the power cable from the power source.
3. Press down the release latch on the power supply cam handle, and then lower the cam handle to the fully
open position to release the power supply from the mid plane.
4

Power supply
Cam handle release latch
Power and Fault LEDs
Cam handle
5

Power cable locking mechanism
4. Use the cam handle to slide the power supply out of the system.
When removing a power supply, always use two hands to support its weight.
5. Repeat the preceding steps for any remaining power supplies.
6. Using both hands, support and align the edges of the power supply with the opening in the system chassis,
and then gently push the power supply into the chassis using the cam handle.
The power supplies are keyed and can only be installed one way.
Do not use excessive force when sliding the power supply into the system. You can damage
the connector.
7. Push firmly on the power supply cam handle to seat it all the way into the chassis, and then push the cam
handle to the closed position, making sure that the cam handle release latch clicks into its locked position.
8. Reconnect the power cable and secure it to the power supply using the power cable locking mechanism.
Only connect the power cable to the power supply. Do not connect the power cable to a
power source at this time.
Step 2: Move a fan
Moving out a fan module when replacing the chassis involves a specific sequence of tasks.
1. Remove the bezel (if necessary) with two hands, by grasping the openings on each side of the bezel, and
then pulling it toward you until the bezel releases from the ball studs on the chassis frame.
2. Press down the release latch on the fan module cam handle, and then pull the cam handle downward.
The fan module moves a little bit away from the chassis.
6

Cam handle
Fan module
Cam handle release latch
Fan module Attention LED
3. Pull the fan module straight out from the chassis, making sure that you support it with your free hand so
that it does not swing out of the chassis.
The fan modules are short. Always support the bottom of the fan module with your free hand
so that it does not suddenly drop free from the chassis and injure you.
4. Set the fan module aside.
5. Repeat the preceding steps for any remaining fan modules.
6. Insert the fan module into the replacement chassis by aligning it with the opening, and then sliding it into
the chassis.
7. Push firmly on the fan module cam handle so that it is seated all the way into the chassis.
The cam handle raises slightly when the fan module is completely seated.
8. Swing the cam handle up to its closed position, making sure that the cam handle release latch clicks into
the locked position.
The fan LED should be green after the fan is seated and has spun up to operational speed.
9. Repeat these steps for the remaining fan modules.
7

10. Align the bezel with the ball studs, and then gently push the bezel onto the ball studs.
Step 3: Remove the controller module
To replace the chassis, you must remove the controller module or modules from the old chassis.
1. If you are not already grounded, properly ground yourself.
2. Loosen the hook and loop strap binding the cables to the cable management device, and then unplug the
system cables and SFPs (if needed) from the controller module, keeping track of where the cables were
connected.
Leave the cables in the cable management device so that when you reinstall the cable management
device, the cables are organized.
3. Remove and set aside the cable management devices from the left and right sides of the controller module.
4. Loosen the thumbscrew on the cam handle on the controller module.
Thumbscrew
Cam handle
5. Pull the cam handle downward and begin to slide the controller module out of the chassis.
Make sure that you support the bottom of the controller module as you slide it out of the chassis.
6. Set the controller module aside in a safe place, and repeat these steps if you have another controller
module in the chassis.
8
Other manuals for AFF A300
1
Table of contents
Other NetApp Storage manuals

NetApp
NetApp DS2246 Manual

NetApp
NetApp DS4243 Manual

NetApp
NetApp FAS26 Series Manual

NetApp
NetApp AFF A250 User manual

NetApp
NetApp E-Series 3040 40U User manual

NetApp
NetApp StorageGRID SD100 User manual

NetApp
NetApp AltaVault System Manual

NetApp
NetApp FAS22 Series User manual

NetApp
NetApp AFF A900 Manual

NetApp
NetApp E Series User manual

NetApp
NetApp FAS25 Series User manual

NetApp
NetApp E Series User manual

NetApp
NetApp DS460C User manual

NetApp
NetApp EF550 User manual

NetApp
NetApp FAS2240-2 User manual

NetApp
NetApp DS4486 Manual

NetApp
NetApp DE6900 User manual

NetApp
NetApp StorageGRID SG5600 Series Operating manual

NetApp
NetApp DE5600 User manual

NetApp
NetApp H410S Owner's manual