Technical manual
myGEKKO BASE R22
Technical manual

2
Table of contents
1 Safety and warranty.........................................................................3
2 General information......................................................................... 5
3 Technical specifications..................................................................6
3.1 Digital Inputs...................................................................................7
3.2 Analogue Inputs............................................................................. 8
3.3 Digital outputs................................................................................ 9
3.4 Analogue outputs...........................................................................9
3.5 AUX1/RS-485................................................................................10
3.6 Ethernet connection.....................................................................10
3.7 WLAN Network.............................................................................12
4 REG Installation instructions.........................................................14
4.1 User group.................................................................................... 14
4.2 General safety information..........................................................14
4.3 Installation instructions............................................................... 14
5 External fuse protection................................................................ 16
6 Commissioning controller............................................................. 17
6.1 Text display.................................................................................. 17
6.2 Web access.................................................................................. 18
7 Configuration.................................................................................. 19
8 List of connections........................................................................ 21
9 Notes...............................................................................................23

3
1 Safety and warranty
These reliable devices are built according to the current rules of technology.
They were tested and left the factory in perfect condition.
However, there are residual risks. Read and follow the safety instructions to
avoid hazards.
Ekon GmbH assumes no liability for damages caused by non-observance of
safety instructions.
Used safety
instructions
The following notes indicate special hazards when handling devices or provide
useful hints:
Hints in these boxes are general tips on text that will be highlighted.
NOTE
The signal word Note indicates useful tips and recommendations for the
efficient handling of the product.
CAUTION
Health damage/Property damage
The respective warning symbol in conjunction with the signal word Caution
indicates a danger that can lead to slight (reversible) injury or material dam-
age.
WARNING
Serious damage to health
The respective warning symbol in conjunction with the signal word Warning
indicates an imminent danger, that can lead to death or serious (irreversible)
injuries.
DANGER
Danger to life/Serious damage to health
The respective warning symbol in conjunction with the signal word Danger
identifies an imminent danger that leads to death or serious (irreversible)
injuries.
Safety information Safety instructions for the product described in this document are listed below.
Please note these when using the product.

4
DANGER
Electrical Voltage!
Danger to life and fire due to electrical voltage
Inside the device are unprotected live components. Observe the VDE regu-
lations. Disconnect all cables to be installed and take precautions against
unintentional switching on. Do not operate the device if damaged. Decom-
mission the device or system and secure it against unintentional operation
if it can be assumed that safe operation is no longer guaranteed.
CAUTION
Device damage due to external influences!
Moisture and contamination of the equipment can destroy the equipment.
Protect devices from moisture, dirt and damage during transport, storage
and operation.
Warranty The device is intended solely for proper use. Any improper modification or non-
observance of the operating instructions invalidates any warranty or guarantee
claim. After unpacking, the device must be inspected immediately for mechan-
ical damage. If there is damage in transit, the supplier must be informed im-
mediately. The device may only be operated as a fixed installation, ie only when
installed and after completion of all installation and commissioning work, and
exclusively in the environment provided for this purpose. Ekon GmbH shall not
be liable for changes to standards after publication of the operating instruc-
tions.

5
2 General information
myGEKKO B.Series BASE R22 is a REG controller for the implementation of all
areas of modern building control.
The combination of numerous complex control algorithms with a user-friend-
ly and easy-to-understand interface enables the visualisation and operation
of various building functions via smart devices such as smartphones, tablets,
laptops or PCs. The configuration and commissioning is carried out directly
via myGEKKO B.Series BASE R22 and via the already installed software. Com-
missioning takes place via the IO configuration or the parameterisation level.
Programming skills are not necessary for this.
Features n4x digital inputs 24VDC (DI)
n4x analogue inputs (AI)
n2x digital outputs 24VDC (DO)
n4x digital outputs 230VAC (DO)
n2x Analogue outputs (AO)
n2x RS485
n1x microUSB
n2x Ethernet ports
n1x WLAN modem
n1x microSD card slot

6
3 Technical specifications
Parameters Value
Housing Plastic
Color White similar to RAL9003
Installation REG installation
Dimensions 98.7 x 105 x 64mm
Weight 280 g
Operating temperature +5°C to +40°C
Storage temperature -20°C to +70°C
Ambient humidity Max. 85% RH not condensing
Supply voltage 24 VDC
Power consumption (internal) Max. 200mA
Protection class IP20
Degree of soiling 2
Protection class III
Certifications: Directive 2014/53 / EU (RED)
Directive 2014/30 / EU (EMCD)
Directive 2014/35 / EU (LVD)
Directive 2011/65 / EU (ROHS)
Health and Safety of the User:
EN 60950-1:2006
+A1+A2+A11+A12+CORR1
EN 60730-1:2016
Electromagnetic compatibility:
EN 61000-6-2:2005+CORR
EN 61000-6-3:2007+A1
Restriction of Hazardous Sub-
stances:
EN 50581:2012
EN60947-4-1
EN60721-3-3

7
Connection data Parameters Value Note
Insulation stripping
length
7 mm
DI 0.1 -1.5 mm² Plug-in screw terminal
AI 0.1 -1.5 mm² Plug-in screw terminal
DO (RO) 0.1 -2.5 mm² Plug-in screw terminal
DO (SSR) 0.1 - 2.5 mm² Plug-in screw terminal
AO 0.1 -1.5 mm² Plug-in screw terminal
Care 0.1 - 2.5 mm² Plug-in screw terminal
3.1 Digital Inputs
The inputs are galvanically isolated from the module via optocouplers.
Parameters Value
Input Optically isolated/optocoupler
Circuit insulation voltage 1 kV
Input voltage 18-30V DC / 18-26VAC
Switching point <5V DC / AC max.
Input 1
Input 2
COM (Input 1-4)
Input 3
Input 4

8
3.2 Analogue Inputs
Parameters Value/Resolution
PT 1000 input -50 to 150°C
Resolution: 0.01°C
Deviation: 0.25%
Voltage input Voltage: 0-10V
Deviation: 0.25%
Power input Electricity: 0-25mA
Deviation 1%
Input AI1, AI2 fixed:
1. PT1000 -50 ... 150°C
Input AI3, AI4 switchable via DIP switch:
nPT1000 -50 ... 150°C
AI3: J1=OFF, J2=ON
AI4: J3=OFF, J4=ON
nVoltage 0V – 10 V
AI3: J1=ON, J2=OFF
AI4: J3=ON, J4=OFF
nCurrent 0 – 20 mA
AI3: J1=OFF, J2 OFF
AI4: J3=OFF, J4=OFF
In addition, an external resistor 125 ohms is required.

9
3.3 Digital outputs
Parameters Value
RO output (digital relay output) Single-pole switch with working con-
tact Continuous load current: 5A
Switching voltage: 250VAC / 30VDC
Isolation
(EN 60947-4-1 ed. 3 general use,
AC1, no inductive loads)
(EN60730-1: 2017: Chapter 13, Ta-
ble 12)
DO output: (Solid State Relays
(SSR))
Continuous load current: 0.4 A
Switching voltage: 24V AC / DC
Isolation 1kV
EN 60947-4-1 ed. 3 general use,
AC1, no inductive loads
Digital relay output 1
Digital relay output 3
Digital relay output 2
Digital relay output 4
SSRO
SSRO
COM for DO5 and DO6
3.4 Analogue outputs
Parameters Value
Output 0-10V
Max. 10 mA
Isolation voltage 1 kV

10
Parameters Value
Typical load 10kOhm
Analogue output 1
Analogue output 2
GND analogue output
3.5 AUX1/RS-485
Parameters Value
Interface RS-485
Baud rates 9.600, 19.200, 38.400, 57.600 and
115.200
Parity adjustable
TS (Termination Switch) 180 ohm terminal resistance
3.6 Ethernet connection
Parameters Value
Ethernet type 10/100 base T
Circuit insulation voltage 1kV electrically isolated
The two Ethernet ports are separated by default, thus a technology network
(ETH1) and an Internet network (ETH0) can be realised. Ports can also be
This manual suits for next models
1
Table of contents
Other myGekko Controllers manuals
Popular Controllers manuals by other brands

Digiplex
Digiplex DGP-848 Programming guide

YASKAWA
YASKAWA SGM series user manual

Sinope
Sinope Calypso RM3500ZB installation guide

Isimet
Isimet DLA Series Style 2 Installation, Operations, Start-up and Maintenance Instructions

LSIS
LSIS sv-ip5a user manual

Rockwell Automation
Rockwell Automation 1769-L31 installation instructions