Note: This device should be installed as per applicable
requirements of the authorities having jurisdiction.
Use the information in this document to determine the
total current draw of the devices. The total current draw of
the devices must not exceed the power supply of the
panel. In all cases, the installer should consider the voltage
drop to ensure that the last device on the circuit operates
within its rated voltage. For maximum strobe operating
current, please refer to Table 4.
Figure 5 DEVICE CONNECTION
Note: Wiring must be in accordance with CSA C22.1,
Canadian Electrical Code, Part I, Safety Standard for
Electrical Installations, Selection 32 and NFPA 70.
CAUTION
FOR SYSTEM SUPERVISION, FOR ALL TERMINAL TAPS, DO
NOT USE LOOPED WIRE UNDER TERMINALS. BREAK WIRE
RUN TO PROVIDE SUPERVISION OF CONNECTIONS.
ATTENTION
NE PAS UTILISER DE FILS EN BOUCLE SOUS LES BORNES.
POUR FOURNIR UN BON SUIVI DES CONNEXIONS.
INTERROMPRE LA CONTIUITÉ DES CÂBLES.
MOUNTING
MGC recommends spacing speaker strobe appliances in
compliance with CAN/ULC S524 and NFPA72.
(Optional. In case of using a standard 4” square 2 1/8 deep
electrical box, attach MP-184 adaptor ring from SPKC-W kit
to the unit using 4 snaps.)
1. Attach the unit to IB-104 electrical box with
two mounting screws.
2. Rotate the top cover clockwise to snap it in place.
3. Secure the top cover with securing screw and snap the
nameplate over the securing screw.
Figure 6 MOUTING DIAGRAM