Gira KNX 1039 00 User manual

Blind actuator
Table of Contents
1 Safety instructions ............................................................................................................ 3
2 Device components .......................................................................................................... 3
3 System information........................................................................................................... 4
4 Intended use..................................................................................................................... 4
5 Product characteristics ..................................................................................................... 4
6 Operation.......................................................................................................................... 5
7 Information for electrically skilled persons........................................................................ 8
7.1 Mounting ................................................................................................................ 8
7.2 Connect bus line .................................................................................................... 8
7.3 DC 24 V Venetian blind actuator: electrical connection ......................................... 9
7.4 Shutter actuators AC 230 V and roller shutter actuator: electrical connection..... 10
7.5 Commissioning .................................................................................................... 12
8 Technical data ................................................................................................................ 14
9 Troubleshooting.............................................................................................................. 16
10 Warranty ......................................................................................................................... 18
2 / 18
32560272 108707200 27.04.2023

1 Safety instructions
Electrical devices may only be mounted and connected by electrically skilled
persons.
Serious injuries, fire or property damage are possible. Please read and follow the
manual fully.
Danger of electric shock. Always disconnect before carrying out work on the device
or load. In so doing, take all the circuit breakers into account, which support danger-
ous voltages to the device and or load.
Risk of injury. Use the device only for controlling Venetian blind and roller shutter mo-
tors or awnings. Do not use it to switch other loads.
For parallel connection of several motors to an output it is essential to observe the
corresponding instructions of the manufacturing company, and to use a cut-off relay if
necessary. The motors may be destroyed.
Use only Venetian blind motors with mechanical or electronic limit switches. Check
the limit switches for correct mastering. Observe the information on the motors from
the manufacturing company. Device can be damaged.
Danger of electric shock on the SELV/PELV installation. Do not connect loads for
mains voltage and SELV/PELV together to the device.
This manual is an integral part of the product, and must remain with the customer.
2 Device components
Figure1
(1) Button field for manual operation
(2) Programming button and LEDs
(3) KNX connection
(4) Connection for mains supply
(5) Status LEDs for outputs
3 / 18
32560272 108707200 27.04.2023
Blind actuator

(6) Connection for Venetian blind motors
3 System information
System information
This device is a product of the KNX system and complies with the KNX directives.
Detailed technical knowledge obtained in KNX training courses is a prerequisite to
proper understanding.
The function of this device depends upon the software. Detailed information on load-
able software and attainable functionality as well as the software itself can be ob-
tained from the manufacturer´s product database. Planning, installation and commis-
sioning of the device are carried out with the aid of KNX-certified software. The latest
versions of product database and the technical descriptions are available on our
website.
4 Intended use
– Switching of electrically driven Venetian blinds, shutters, awnings and similar
hangings for AC 230 V mains voltage or DC 12...48 V extra-low voltage.
– Mounting on DIN rail according to DIN EN 60715 in sub-distribution unit
5 Product characteristics
– Outputs can be operated manually, construction site mode
– Blind/shutter position directly controllable
– Acknowledgement of the blind/shutter position in bus and manual mode
– Safety functions: 3 independent wind alarms, rain alarm, frost alarm
– Integration into the temperature management of the building
– Disabling of individual outputs manually or by bus
Delivery state: Outputs can be operated using button field, construction site
mode.
Only Venetian blind actuators:
– Automatic operation time detection for 230 V motors can be set
– Slat position directly controllable
– Acknowledgement of movement state and slat position in bus and manual
mode
– Scene function
– "Top" and "Bottom" forced position via higher-level controller
– Sun protection function
4 / 18
32560272 108707200 27.04.2023
Blind actuator

6 Operation
Operating elements
Figure2
(5) Status LEDs for outputs
(7) Button c – Manual operation
(8) LED c – on: continuous manual mode
(9) Button n: move hanging upwards / stop
(10) LED n – on: hanging moves up, manual mode
(11) Button o: move hanging downwards / stop
(12) LED o – on: hanging moves down, manual mode
(13) Button ALL OFF: stop all hangings
In operation with the button field the device distinguishes between a short and a long
press.
– Short: Pressing for less than 1 second
– Long: Pressing for between 1 and 5 seconds
Status indication
The status LED A1… (5) indicate the states of the outputs.
– Off: Output switched off
– On: Output switched on
– Flashes slowly: Output in manual mode
– Flashes quickly: Output disabled via continuous manual mode
Operating modes
– Bus operation: operation via push-button sensors or other bus devices
– Temporary manual operation mode: manual operation locally with button field,
automatic return to bus operation
– Permanent manual operation mode: exclusively manual operation on the
device
No bus operation is possible in manual mode.
No manual mode is possible in case of bus failure.
5 / 18
32560272 108707200 27.04.2023
Blind actuator

After a bus failure and restoration the device switches to bus operation.
After a power failure and restoration the device switches to bus operation.
The manual mode can be disabled in ongoing operation via a bus telegram.
Priorities
– Highest priority: manual mode
– 2th priority: forced position
– 3rd priority: safety function
– 4th priority: sun protection
– Lowest priority: bus mode: moving up/down, slat positioning, scenes, position-
ing
Switching on temporary manual operation mode
Operation using the button field is programmed and not disabled.
■ Press the c button briefly.
LEDs A1 flash, LED c remains off.
After 5 seconds without actuating a button, the actuator returns automatically
to bus operation.
Switching off temporary manual operation mode
The device is in temporary manual operation mode.
■ No button has been actuated for 5 seconds.
- or -
■ Press the c button briefly as many times as necessary until the actuator exits
temporary manual operation mode.
LEDs A1... no longer flash, but rather indicate the output status.
Depending on the programming, the hangings move to the position that is act-
ive after the manual mode is switched off, e.g. to the forced position, safety or
sun protection position.
Switching on permanent manual operation mode
Operation using the button field is programmed and not disabled.
■ Press the c button for at least 5 seconds.
LED c is illuminated, LEDs A1 flash, continuous manual mode is switched
on.
Switching off permanent manual operation mode
The device is in permanent manual operation mode.
6 / 18
32560272 108707200 27.04.2023
Blind actuator

■ Press the c button for at least 5 seconds.
LED c is off, bus operation is switched on.
Depending on the programming, the hangings move to the position that is act-
ive after the manual mode is switched off, e.g. to the forced position, safety or
sun protection position.
Operating the outputs
The device is in permanent or temporary manual operation mode.
■ Press the button c briefly as many times as necessary until the desired out-
put is selected.
LEDs of the selected output A1... flash.
The LEDs n and o indicate the status.
■ Operate output with n button or o button.
Short: Stop hanging.
Long: Move hanging upwards/downwards.
The selected hanging executes the corresponding commands.
The LEDs n and o indicate the status.
Short-term manual mode: After running through all of the outputs the device
exits manual mode after another brief actuation.
Stop all hangings
The device is in permanent manual operation mode.
■ Press the ALL OFF button.
All outputs switch off; all hangings stop moving.
Disabling individual outputs
The device is in permanent manual operation mode.
■ Press the button c briefly as many times as necessary until the desired out-
put is selected.
The status LEDs of the selected output A1... flash.
■ Press buttons n and o simultaneously for at least 5 seconds.
Selected output A1... is disabled.
The status LEDs of the selected output A1... flash quickly.
■ Activate bus mode (see section Deactivating permanent manual control).
A disabled output can be operated in manual mode.
7 / 18
32560272 108707200 27.04.2023
Blind actuator

When a disabled output is selected in manual mode, the corresponding status
LEDs flash twice briefly at intervals.
Re-enabling outputs
The device is in permanent manual operation mode.
■ Press the button c briefly as many times as necessary until the desired out-
put is selected.
The status LEDs of the selected output A1... flash twice briefly at time inter-
vals.
■ Press buttons n and o simultaneously for at least 5 seconds.
Selected output A1... is enabled.
LEDs of the selected output A1... flash slowly.
■ Activate bus mode (see section Deactivating permanent manual control).
7 Information for electrically skilled persons
7.1 Mounting
Mounting the device
DANGER!
Electric shock when live parts are touched.
Electric shocks can be fatal.
Always disconnect before carrying out work on the device or load. For this, switch off
all corresponding circuit breakers, secure against being switched on again and check
that there is no voltage. Cover up adjacent live parts.
DANGER!
Danger of destruction if several motors are connected in parallel to one output.
Limit switch contacts can weld together and motors, blinds/shutters and the venetian
blind actuator can be destroyed.
Observe the manufacturer's instructions. Use cutoff relay if necessary!
Observe the temperature range. Ensure sufficient cooling.
■ Mount the device on DIN rail. Output terminals must be at the top.
7.2 Connect bus line
■ Connect bus line with KNX device connection terminal observing the correct
polarity (see figure 3), (see figure 4).
8 / 18
32560272 108707200 27.04.2023
Blind actuator

■ Attach the cover cap to the KNX connection as protection against hazardous
voltages.
7.3 DC 24 V Venetian blind actuator: electrical connection
Connecting the device
Image3: Connection example for DC Venetian blind actuator
Only for DC motors 12...48 V. Observe the admissible load ratings.
Terminals 1/2 supply power to the device electronics and outputs A1 and A2. For op-
eration of the actuator it is necessary to connect an external 24 V DC power supply
to 1/2.
Terminals 3/4 supply power to outputs A3 and A4.
The supply voltages must be designed in such a way that a safe and reliable operat-
ing voltage is provided under all load conditions – especially when the motors are first
switched on.
Do not connect any AC voltage.
■ Connect power supply to terminals 1/2 or 3/4 (see figure 3).
■ Connect motors to load terminals A1 ... A4 (see figure 3).
9 / 18
32560272 108707200 27.04.2023
Blind actuator

Drives for venting louvers or windows must be connected in such a way that
they open in travel direction "UP " and close in travel direction "DOWN".
7.4 Shutter actuators AC 230 V and roller shutter actuator: electrical
connection
Connecting the device without automatic operation time detection
Image4: Connection of bus and mains voltage supply
■ Connect mains voltage supply (see figure 4).
■ Connecting the motors (see figure 5).
■ Mark 230 V use on label (see figure 5).
The N conductor connections (14) serve only to detect the operation time and
do not provide any N potential.
If motors with high-impedance inputs are connected, then the corresponding N
conductor can be connected. The associated output must not be under current
for a longer period without interruption due to retriggering. This can lead to im-
permissible heating of the device. Observe maximum duty cycle (see chapter
"Technical data").
10 / 18
32560272 108707200 27.04.2023
Blind actuator
This manual suits for next models
4
Table of contents
Other Gira Controllers manuals

Gira
Gira 5431 00 User manual

Gira
Gira 1288 Series User manual

Gira
Gira 2100 Series User manual

Gira
Gira 5423 00 User manual

Gira
Gira One 5061 00 User manual

Gira
Gira 1289 00 User manual

Gira
Gira 0566 Series User manual

Gira
Gira System 3000 User manual

Gira
Gira 0425 00 User manual

Gira
Gira 2100 Series User manual
Popular Controllers manuals by other brands

Digiplex
Digiplex DGP-848 Programming guide

YASKAWA
YASKAWA SGM series user manual

Sinope
Sinope Calypso RM3500ZB installation guide

Isimet
Isimet DLA Series Style 2 Installation, Operations, Start-up and Maintenance Instructions

LSIS
LSIS sv-ip5a user manual

Rockwell Automation
Rockwell Automation 1769-L31 installation instructions