Exhausto VEX320CX User manual

VEX320CX
(3rd party control system)
Installation instructions
Product information........................................Chapter 1 + 6
Mechanical assembly.....................................Chapter 2 + 3
Electrical installation.......................................Chapter 4
Maintenance...................................................Chapter 5
Closing damper, LSR315-24, with
spring-return (LSFR outdoor)
The following accessories are
supplied seperately:
Prod.order no.:
Sales order no.:
Unit supplied with (factory fitted):
Compact filter F7
VEX320, motor type 1
VEX320, motor type 2
Self-adhesive foam strip
(VEX with hinged doors only)
V300CDHS, hinged doors
V300CDRS, sliding doors
Closing damper, LS315-24, (LSA exhaust)
Closing damper, LS315-24, (LSF outdoor)
Compact filter M5
pieces, HMI control panel
HCE external heating coil (electrical)
HCW external heating coil (water)
Original instructions
3004210-2016-02-23 VEX320CX
EXHAUSTO A/S
Odensevej 76
DK-5550 Langeskov
Tel. +45 65 66 12 34
Fax +45 65 66 11 10
www.exhausto.dk

1. Product information
1.1. Model overview......................................................................................................6
1.2. Terms used in these instructions.........................................................................7
1.2.1.Simplified diagram............................................................................................7
1.3. Application.............................................................................................................7
1.4. Location requirements..........................................................................................7
1.4.1.Space requirements.........................................................................................8
1.4.2.Ceiling requirements........................................................................................8
1.4.3. Requirements for duct system........................................................................9
1.5. Description.............................................................................................................9
1.5.1. Construction of the VEX unit...........................................................................9
1.5.2.Parts of the VEX unit......................................................................................11
1.6. Principal dimensions...........................................................................................11
1.6.1.VEX320C, general dimensions .....................................................................11
1.6.2.Dimensional sketches, doors.........................................................................14
2. Handling 2.1. Unpacking.............................................................................................................15
2.1.1. Weight...........................................................................................................15
2.2. Transport..............................................................................................................15
2.2.1. Passage through openings ..........................................................................16
2.2.2. Internal transport with reduced weight..........................................................16
3. Mechanical assembly
3.1. Positioning of unit...............................................................................................17
3.1.1.Mounting on ceiling........................................................................................17
3.1.2.Insulation using self-adhesive foam strip.......................................................18
3.2. Condensation drain.............................................................................................18
4. Electrical installation
4.1. Electrical installation...........................................................................................19
5. Maintenance, hygiene and servicing
5.1. Maintenance.........................................................................................................20
5.1.1.VEX300C with hinged doors..........................................................................20
5.1.2.VEX300C with sliding doors...........................................................................21
5.1.3.Overview of maintenance intervals................................................................22
5.2. Hygiene.................................................................................................................22
5.3. Servicing and cleaning........................................................................................22
5.3.1.Filter change..................................................................................................22
5.3.2.Servicing and cleaning the motor...................................................................23
5.3.3. Removing and cleaning the counter flow heat exchangers..........................24
5.3.4.Cleaning the heating coils..............................................................................26
5.4. Airflow measurement..........................................................................................27
5.4.1.Determining airflow and pressure..................................................................27
6. Technical data 6.1. Weight, corrosion class, temperature ranges, etc............................................30
6.2. Compact filters.....................................................................................................31
3004210-2016-02-23
2/36

6.3. Capacity diagram.................................................................................................32
6.3.1.Capacity diagram, VEX320C-1......................................................................32
6.3.2.Capacity diagram, VEX320C-2......................................................................33
6.4. Ordering spare parts...........................................................................................33
3004210-2016-02-23
3/36

Symbols, terms and warnings
Prohibition symbol Failure to observe instructions marked with a prohibition symbol
may result in serious or fatal injury.
Danger symbol Failure to observe instructions marked with a danger symbol may
result in personal injury and/or damage to the unit.
Scope This instruction manual is for use with EXHAUSTO VEX-type air handling units.
Please refer to the product instructions regarding accessories and extra equipment.
The instructions must be fully observed to ensure personal safety and to protect the
equipment and ensure its correct operation. EXHAUSTO A/S accepts no liability for
accidents caused by equipment not used in accordance with the manual’s instruc-
tions and recommendations.
Warnings
Opening the unit Do not open the service doors until the supply voltage has been
disconnected at the isolation switch and the fans have stopped.
Prohibited uses The VEX unit is not to be used to transport solid particles or in
areas where there is a risk of explosive gases.
No duct connection If one or more of the spigots is not connected to a duct: fit a pro-
tective net to the spigots with a maximum mesh width of 20 mm.
Icing monitor The high-efficiency of the counter flow heat exchanger means that
some operating conditions will increase the risk of ice formation
insidetheheatexchanger.Ensurethecounterflowheatexchanger
is protected against icing.
Information plate The VEX unit information plate shows:
1. VEX model
2. Production order no.
1
2
NB Always have the production number ready when contacting EXHAUSTO A/S.
3004210-2016-02-23
4/36

Supply air/extract
air This instruction manual uses the following terminology:
●Supply air (air blown in)
●Extract air (air removed)
●Outdoor air
●Exhaust air
Front page: Acces-
sories The front page of the instruction manual contains a checklist, detailing the acces-
sories delivered with the VEX unit.
NB When retrofitting EXHAUSTO accessories, please update the checklist on the
front page.
Left/Right See definition of Left/Right in Section 1.1 Model overview.
3004210-2016-02-23
5/36

1. Product information
1.1 Model overview
Elements Description
Fan
RD12763-01
Compact filter
1,1 Extract air spigot
1,2 Exhaust air spigot
2,1 Outdoor air spigot
2,2 Supply air spigot
1
Air direction, extract air
2
Air direction, supply air
Fan placement Air directions
LEFT,
VEX unit from above
RD12944GB_DK_DE_NO_SE_NL-01
2,2
1,1
1,2
2,1
1
1
1
2
2
2
Bypass
RIGHT,
VEX unit from above
RD12945GB_DK_DE_NO_SE_NL-01
2,2
1,1
1,2
2,1
1
1
1
2
2
2
Bypass
3004210-2016-02-23 Product information
6/36

1.2 Terms used in these instructions
1.2.1 Simplified diagram
Component Function Standard/accessory
BP1 Bypass damper Standard
Main Connection Main control/control box Standard
M1 Extract/exhaust air motor Standard
M2 Outdoor/supply air motor Standard
1.3 Application
Comfort ventilation EXHAUSTO VEX is used for comfort ventilation tasks. The VEX unit is designed for
ceiling mounting and must be used as such.
Operating temperature range for the unit – see section "Technical data".
Prohibited uses The VEX unit is not to be used to transport solid particles or in areas where there is
a risk of explosive gases.
1.4 Location requirements
Positioning The unit is designed for indoor fitting. The unit may be positioned with the side op-
posite the connection box up against a rear wall.
NB If the VEX unit has sliding doors, space must be allowed for opening the snap locks
on the rear (75 mm).
3004210-2016-02-23 Product information
7/36

1.4.1 Space requirements
VEX320C with
hinged doors The cabinet has two hinged doors. The drawing below indicates how much head-
room is needed for opening the doors and servicing the unit, i.e. changing filters,
cleaning, servicing, etc.
1085
800
RD12946-02
1600
Space requirements, width: 1,295 mm. (Width of unit (995 mm.) plus space for
opening connection box (300 mm)).
VEX320C with slid-
ing doors Thecabinet has2 doorswhich can be individually releasedand slid behind the other
door.The drawing below indicates how much space is neededfor opening the doors
and servicing the unit, i.e. changing filters, cleaning, servicing, etc.
RD12947-03
540
800
1985-2770
1335-1035
Space requirements, width: 1,370 mm. (Width of unit (995 mm.) plus room for
opening connection box (300 mm) and for opening tension fittings on the rear (75
mm)).
See also ●section "Principal dimensions of VEX320C" for further dimensions
●section "Maintenance" for information on opening the doors
1.4.2 Ceiling requirements
When fitting the unit to a ceiling, the ceiling must be:
●flat
●resistant to vibration
●horizontal or sloping towards the condensation outlet
●designed to bear the weight of the unit
3004210-2016-02-23 Product information
8/36

1.4.3 Requirements for duct system
Silencers The duct system must be fitted with silencers specified by the Project Manager,
which meet the requirements of the operating area.
Connection to duct
system Aductbend maybefitted immediately aftertheunit, becausetheairflow inthespigot
has a uniformly low speed profile, resulting in negligible system pressure drop.
Insulation The duct system must be insulated to prevent
●condensation
●sound leakage
●heating/cooling losses
Prerequisites Adequate insulation of the duct system in the operating area is a prerequisite for
achieving the calculated sound data during operation.
Condensation Condensation in the ducts may occur when the exhaust/outdoor air has high hu-
midity. EXHAUSTO recommends a condensation outlet is also fitted at the lowest
point in the ducts.
No duct connection If one or more of the spigots is not connected to a duct: Fit a pro-
tective net to the spigots with a maximum mesh width of 20 mm.
1.5 Description
1.5.1 Construction of the VEX unit
The drawings below shows an overview of the VEX unit construction. The lower draw-
ing shows a VEX with sliding doors.
3004210-2016-02-23 Product information
9/36

RD12976-02
3 4
567891011
1 2
RD13207GB-01
15
14
13
Pos. no. Part Function
1 Bypass motor Opens/closes bypass damper
2 Terminals Connection of ventilation components
3 Connection box Connection of power and diverse accesso-
ries
4 Suspension clamps Clamps for fitting the unit to the ceiling
5 Extract air fan Removes "stale" air
6 Filter for supply air Filters the supply air
7 Counter flow heat ex-
changer Counter flow heat exchanger(s) in alumini-
um
8 Bypass duct Directs air around the counter flow heat ex-
changer
9 Bypass damper Bypass damper, provides option for temper-
ature regulation
10 Extract air filter Filters extract air
11 Supply air fan Blows air into the room
13 Door Sliding door/hinged door for inspection,
cleaning and service
14 Condensation tray Collects the condensate and drains it away
from the cross-flow heat exchanger to the
condensation outlet
3004210-2016-02-23 Product information
10/36
This manual suits for next models
1
Table of contents
Other Exhausto Control System manuals

Exhausto
Exhausto EXact2 VEX240 series Installation guide

Exhausto
Exhausto EXact2 HMI2-350-TOUCH Installation guide

Exhausto
Exhausto VEX240HX User manual

Exhausto
Exhausto EXact2 HMI2-350-TOUCH Installation guide

Exhausto
Exhausto EFC 25 Manual

Exhausto
Exhausto VEX260HX User manual

Exhausto
Exhausto EXact2 VEX240 series Installation guide

Exhausto
Exhausto VEX370H User manual

Exhausto
Exhausto VEX150CF H User manual

Exhausto
Exhausto VEX200 series Installation guide