2.2 Dimensioning and electrical installation
●The supply cable must be dimensioned and installed in ac-
cordance with applicable rules and regulations.
●The earth terminal (PE) must always be connected.
Diagram The supply voltage must be connected to the isolation switch as shown in the dia-
gram in section 1.
2.2.1 Installation requirements and recommendations
Fuses The fuses must be suitable for:
●Short-circuit protection of the unit
●Short-circuit protection of supply cable
●Overload protection of supply cable
Max. rating Maximum fuse rating is 13 A (gG/gL).
Power supply cable When dimensioning the supply cable, the conditions at the installation location, in-
cluding temperature and cable duct layout, must be taken into consideration.
Earth leak circuit
breaker
●The unit must be protected against indirect contact.
If current earth leak circuit breakers are fitted in the installation, they must be
of a type that meets the following requirements:
●PFI type A breaker that breaks the circuit when a vagrant
current with DC content (pulsating DC) in accordance with
EN 61008.
●The circuit breakers must be marked with the following sym-
bol:
●Cutout time must be max. 0.3 s.
When there is cur-
rent leakage A leak current of up to 100 mA can be generated.
Electrical wiring
VEX type Motor Voltage Dimensioned power con-
sumption
VEX320C/330C/330H -1 1 x 230 V + N + PE 3.1 A
VEX320C/330C/330H -2 1 x 230 V + N + PE 5.3 A
Short-circuit current Maximum short circuit current (lcu), in accordance with EN60947.2 is 10 kA.
3004224-2014-09-03 Installation of the VEX
10/20