Argo LUDVIG User manual

V 04/23
LUDVIG
PORTABLE AIR CONDITIONER (LOCAL)
OPERATING INSTRUCTIONS
Read the instructions carefully before operating the appliance or carrying out maintenance work. Observe
all the safety instructions; failure to do so may lead to accidents and/or damage. Store these instructions in
a safe place for future reference.
EN

22V 04/23
THE REFRIGERANT R290
Appliance is lled with ammable
gas R290.
• To realize the function of the air conditioner unit, a special refrigerant circulates in the system. The refrigerant is the
uoride R290 = 3 GWP (Global warming potential). This refrigerant is ammable and inodorous. It can lead to
explosions under certain conditions, however the ammability of this refrigerant is very low and it can be ignited
only by re.
• Compared to other common refrigerants, R290 is a non-polluting refrigerant with no harm to the ozonosphere and
a no effect upon the greenhouse effect. R290 has very good thermodynamic features which lead to a really high
energy efciency. The units therefore need less lling.
Warning:
Do not try to accelerate the defrosting process or to clean the appliance in different ways other than those recommended
by the manufacturer.
Should repair be necessary, contact your nearest authorized Service Centre.
Any repairs carried out by unqualied personnel may be dangerous.
The appliance has to be stored in a room that doesn’t have any continuously operating ignition sources. (for example:
open ames, an operating gas appliance or an operating electric heater.)
Do not pierce or burn.
Appliance has to be installed, used and stored in a room with a oor area larger than 12 m2.
Before installing and using the
appliance, read the owner
manual.
Before installing the appliance,
read the installation manual. Any repairs you need, contact the nearest
authorized Service Centre and strictly follow
manufacturer’s Service Manual.

23V 04/23
• This appliance is a local air conditioner designed for domestic use.
• Only use this air-conditioner as described in this manual.
• Ensure that the required voltage and frequency (220-240V~/50 Hz)
match the available power source.
• Fuse style 5ET or SMT 250V, the electricity passing through the fuse
cannot be above 3.15A.
• This appliance can be used by children aged from 8 years and above
and people with reduced physical, sensory or mental capabilities or
lack of experience and knowledge if they have been given supervision
or instruction concerning use of the appliance in a safe way and
understand the hazards involved.
• Children shall not play with the appliance.
• Cleaning and user maintenance shall not be made by children without
supervision.
• Ensure that the electricity system is able to deliver the operating current
required by the air conditioner, in addition to that normally absorbed by
other appliances (household appliances, lighting system, etc.). Please
refer to the maximum power input data indicated on the air conditioner’s
data plate.
• Connection to the electricity grid must take place in accordance with
current installation standards.
• Ensure that the automatic switches and system protection valves are able
to withstand a start-up current of 6A (normally for less than 1 second).
• The system socket must always be tted with an efcient earth connection.
• Make sure that the plug is fully inserted. Do not use multiple adapters.
Do not touch the plug with wet hands. Make sure that the plug is clean.
• Do not use the plug as a means by which to start/stop the air conditioner:
use the ON/OFF button on the remote control or on the control panel.
• Do not install the air conditioner in rooms where it may receive water
splashes (e.g. laundry rooms).
• This air conditioner can be used by children of 8 years of age or older,
and by persons with reduced physical, sensory and mental abilities
or who lack the necessary know-how and experience to operate it,
if under the supervision or instruction of a person responsible for their
safety, so that they are fully aware of the attendant risks.
GENERAL OPERATING AND SAFETY INSTRUCTIONS

24V 04/23
• Before moving or cleaning the device, ensure that it is unplugged from
the socket.
• Do not move the air conditioner while it is operating; rst turn the appliance
off, check for any condensate build-up and empty it if necessary.
• To turn the appliance off, set the remote control to OFF and remove the
plug from the socket. Pull on the plug only. Do not pull the cord.
• Do not use the appliance if the cord or plug are damaged. If the power
supply cord is damaged, it must be replaced by the manufacturer,
dealer or a similarly qualied person so as to avoid any safety risks.
• Keep the unit away from re, possible re sources, inammable or
explosive objects.
• Do not leave the unit unattended while it’s operating, turn the unit off
and unplug it.
• If drainage hose is used, the ambient temperature musnt’t be lower than
0 °C. It can cause water leakage to the air conditioner.
• Do not splash or pour water on the air conditioner
PRECAUTION!
• Do not insert any objects into the air conditioner: this is very dangerous
as the fan turns at high speed.
• Ensure that air circulates freely around the unit. Do not cover the air
intake and delivery grilles with drapes or any other means.
WARNING!
• The air conditioner must be positioned at least 50 cm from the wall or
any other obstacles, on a at and stable surface so as to avoid water
leaks.
• The air conditioner is tted with a system for protecting the compressor
from overload. This means that the compressor only starts 3 minutes
after its previous stoppage.
• Please wait at least 3 minutes before starting the unit. This helps prevent
the compressor from being damaged.
WARNING!
In the event of an anomaly, switch the appliance off and unplug it from
the socket. Do not dismantle or attempt to repair or modify the product.

25V 04/23
In the event of a malfunction, contact the service centre directly.
WARNING!
• Do not expose the air conditioner to direct sunlight, as the colour of the
materials may change; moreover, the appliance may overheat causing
the protection mechanism to intervene and switch the appliance off.
• Do not use insecticides, oils, detergents or spray paints near the
appliance; do not use aggressive chemical detergents to clean the
casing: this may damage the nish and colour.
• Close all open windows to maximise air conditioning efciency.
The manufacturer will not be held liable if safety and accident prevention
rules are not observed.

26V 04/23
DESCRIPTION OF THE APPLIANCE
PRE-OPERATING CHECKS AND OPERATIONS
Min/max operating limits (internal temperature)
Cooling: 7 °C D.B./35 °C D.B.
Dehumidication: 17 °C D.B./35 °C D.B.
Cooling mode room temperature adjustment range: 16 °C D.B./32 °C D.B.
The following space must be maintained to ensure the operating efciency of the portable air conditioner.
12
1. Vertical ns and air intake
2. Front panel
3. Control panel and function buttons without remote
control
4. Filter
5. Air intake
6. Cord cable clamp
7. Handle
8. Drain hose
9. Air outake
10. Plug socket
11. Remote control
12. Drain hose in cooling mode

27V 04/23
APPLIANCE START-UP
Open the packaging and pull out the box. Remove the product and the other elements supplied (illustrated in the box
below).
LCD remote control
Round fitting for window (1)
to be positioned between the
end of the tube and the end
fitting for the window
Drainage pipe
Window unit kit with plug.
End fitting for window,
supplied into 2 parts (2)
Hose
Round fitting for window unit,
for positioning between the
end of the tube and the
window unit itself.
Position the product vertically on a at and stable surface, as close as possible to a window and at least 50 cm from
walls or other nearby obstacles.
USE WITH END FITTING FOR WINDOW
1. Connect the at tting to the hose, extend the hose as far as necessary for reaching the outside and it connect to
the back of the air conditioner.
2. SAlign the hose connector with the air outtake and secure it by rotating clockwise.
AA
A
A
BB

28V 04/23
USE WITH WINDOW UNIT KIT
1. To make the hole in the glass it is advisable to take the porthole kit accessory to the glazier (Fig. 1).
2. Insert the window unit into the window (Fig. 2).
3. Insert the round tting into the retractable exible pipe and insert the latter with its round tting into the window
unit without the plug (Fig. 3).
4. Insert the round tting onto the exible pipe (Fig. 4).
5. Insert the exible pipe thus mounted into the rear of the air conditioner.
(Fig. 1) (Fig. 2) (Fig. 3) (Fig. 4)
Connect the power cord to a suitable electric socket (220-240 V). Insert the supplied batteries into the remote control
and make sure the poles match. Select the desired operating mode from the remote control.
Avoid tight bends or folds in the hose.
If the air conditioner is not used for prolonged periods, disconnect the pipe and plug the window unit.
Open the windows and lock one of the two leaves with the handle. Place the end tting against the xed leaf of the
window,and draw the other leaf towards it

29V 04/23
HOW TO USE THE APPLIANCE
OPERATING MODES
This appliance can be used for cooling, dehumidifying and ventilating. When switching between modes, the fan
continues to rotate but the compressor stops: the compressor will start after 3 minutes. This delay protects the compressor
from potential damage.
THE DRAINAGE TUBE MUST BE CONNECTED to the appliance AT ALL TIMES: the only exception is when the
appliance is used in dehumidication mode only, in which case the appliance should be left to discharge directly
into the room for maximum efciency (see the “Dehumidication Mode” paragraph).
Clean the air lters under the easily removable rear grille regularly to keep the air conditioner working efciently.
1. COOLING MODE (COOL)
• The “Cool” LED on the control panel will turn on.
• The temperature can be adjusted to between 16 °C and 32 °C.
• In this mode, each time the ON/OFF button is pressed the unit switches off, the appliance saves the
temperature setting and retains this setting when it is switched on again.
• In this mode, the fan speed can be adjusted and the Timer and SLEEP functions can be set.
• For more silent operation, run the fan at low speed.
2. DEHUMIDIFICATION MODE (DRY)
• Press the MODE button to select the dehumidication mode.
• The temperature is controlled by the electronic board and cannot be adjusted.
• In this mode, each time the ON/OFF button is pressed the unit switches off, the appliance saves the settings
and retains them when it is switched on again.
• The fan speed is set to low and cannot be adjusted.
NOTE: the air conditioner does not cool the room when operating as a dehumidier. When the appliance is
used as a dehumidier, the exible pipe must not be connected. For maximum dehumidication efciency, leave
the rear discharge attachment free to discharge directly into the environment. The dehumidication mode is
recommended during autumn and winter. If used during summer, it is best to leave the exible pipe attached so
that the hot air is discharged towards the outside rather than into the room. During dehumidication, continuous
drainage should be implemented (see the next chapter, “HOW TO ELIMINATE CONDENSATE”).
3. FAN MODE (FAN)
• Press the MODE button to select ventilation until the corresponding icon appears.
• In this mode, the fan speed can be adjusted.
• The temperature cannot be adjusted.
Cooling, Fan Dehumidifying

30V 04/23
HOW TO ELIMINATE CONDENSATE
This appliance automatically vaporises condensate in the cooling mode. When the air conditioner operates in cooling
mode, there is no need to drain condensate continuously; only in certain weather conditions with very humid air may it
occur that water deposits inside the unit. When its inner tank is full, the air conditioner beeps 8 times and the message
“P1” appears on the display to signal that the tank is full and stop the appliance’s operation.
Cooling
When the unit operates in the cooling mode, ensure that the rubber cap closing
the drainage opening on the back of the appliance is properly positioned. To
empty the container, switch the air conditioner off and unplug the cord. Remove
the cap from the rear drainage opening and place its end over a normal drain.
Ensure that the tube is not twisted or bent. The tube must slope downwards. Re-
close the drainage opening with the cap, insert it into the clamp and resume use
of the air conditioner.
Dehumidication
ATTENTION! When using the air conditioner in Dehumidication, it is advisable to always arrange the continuous
drainage to ensure maximum dehumidication efciency. Use the drainage hole in the middle. The water can be
drained into a drain by simply connecting the supplied hose. Avoid draining tube bends.
Table of contents
Other Argo Air Conditioner manuals

Argo
Argo AEI1G80EMX User manual

Argo
Argo ASR518HL Manual

Argo
Argo AW22AL User manual

Argo
Argo AWMI28AHL User manual

Argo
Argo AWMI 28 AHL Operating manual

Argo
Argo Extreme 11 User manual

Argo
Argo K70N142T User manual

Argo
Argo Polifermo Teddy User manual

Argo
Argo GUD35P1/A-S User manual

Argo
Argo CHARM Series User manual
Popular Air Conditioner manuals by other brands

Fujitsu
Fujitsu Inverter ASBA30JFC operating manual

Toshiba
Toshiba RAS-M10SMUV-E installation manual

Daikin
Daikin FXLQ20MAVE Operation manual

Hitachi
Hitachi RAS-E24CAK instruction manual

CIAT
CIAT Magister 2 Series Installation, Operation, Commissioning, Maintenance

Bestron
Bestron AAC6000 instruction manual