Argo ADS22MH User manual

TECHNICAL DATA
& SERVICE MANUAL
SPLIT SYSTEM AIR CONDITIONER
ADS28MH 38.7030.032
AD64MHG 38.7006.134
0.8180.440.1 Jun. 2006
ADS36MH
AD45MHG
ADS56MH 38.7030.034
Model No. Product Code No.
ADS22MH
38.7006.147
38.7030.031
38.7030.033

IMPORTANT!
Please read before installation
This air conditioning system meets strict safety and operating
standards.
For the installer or service person, it is important to install or
service the system so that it operates safely and efficiently.
For safe installation and trouble-free operation, you must:
• Carefully read this instruction booklet before beginning.
• Follow each installation or repair step exactly as shown.
• Observe all local, state and national electrical codes.
• Pay close attention to all warning and caution notices given in
this manual.
•The unit must be supplied with a dedicated electrical line.
This symbol refers to a hazard or unsafe practice which can result
in severe personal injury or death.
This symbol refers to a hazard or unsafe practice which can result
in personal injury or product or property damage.
If necessary, get help
These instructions are all you need for most installation sites and
maintenance conditions.
If you require help for a special problem, contact our sale/service
outlet or your certified dealer for additional instructions.
In case of improper installation
The manufacturer shall in no way be responsible for improper
installation or maintenance service, including failure to follow the
instructions in this document.
SPECIAL PRECAUTIONS
• During installation, connect before the refrigerant system and
then the wiring one; proceed in the reverse orden when removing
the units.
When wiring
ELECTRICAL SHOCK CAN CAUSE SEVERE
PERSONAL INJURY OR DEATH. ONLY QUALIFIED,
EXPERIENCED ELECTRICIANS SHOULD ATTEMPT
TO WIRE THIS SYSTEM.
• Do not supply power to the unit until all wiring and tubing are
completed or reconnected and checked, to ensure the grounding.
• Highly dangerous electrical voltages are used in this system.
Carefully refer to the wiring diagram and these instructions when
wiring.
Improper connections and inadequate grounding can cause
accidental injury and death.
•Ground the unit following local electrical codes.
• The Yellow/Green wire cannot be used for any connection
different from the ground connection.
• Connect all wiring tightly. Loose wiring may cause overheating
at connection points and a possible fire hazard.
• Do not allow wiring to touch the refrigerant tubing, compressor,
or any moving parts of the fan.
• Do not use multi-core cable when wiring the power supply and
control lines. Use separate cables for each type of line.
When transporting
Be careful when picking up and moving the indoor and outdoor
units. Get a partner to help, and bend your knees when lifting to
reduce strain on your back. Sharp edges or thin aluminium fins on
the air conditioner can cut your fingers.
When installing...
• Keep all tubing runs as short as possible.
• Use the flare method for connecting tubing.
• Apply refrigerant lubricant to the matching surfaces of the flare
and union tubes before connecting them; screw by hand and
then tighten the nut with a torque wrench for a leak-free
connection.
• Check carefully for leaks before starting the test run.
NOTE:
Depending on the system type, liquid and gas lines may be either
narrow or wide. Therefore, to avoid confusion, the refrigerant
tubing for your particular model is specified as narrow tube for
liquid, wide tube for gas.
When servicing
• Turn the power OFF at the main power board before opening
the unit to check or repair electrical parts and wiring.
• Keep your fingers and clothing away from any moving parts.
• Clean up the site after the work, remembering to check that no
metal scraps or bits of wiring have been left inside the unit being
serviced.
• Ventilate the room during the installation or testing the refrigeration
system; make sure that, after the installation, no gas leaks are
present, because this could produce toxic gas and dangerous
if in contact with flames or heat-sources.
WARNING
CAUTION
WARNING
… In a ceiling
Make sure the ceiling is strong enough to hold the unit-weight.
It may be necessary to build a strong wooden or metal frame to
provide added support.
… In a room
Properly insulate any tubing run inside a room to prevent
"sweating", which can cause dripping and water damage to
walls and floors.
... In moist or uneven locations
Use a raised concrete base to provide a solid level foundation
for the outdoor unit. This prevents damage and abnormal
vibrations.
... In area with strong winds
Securely anchor the outdoor unit down with bolts and a metal
frame. Provide a suitable air baffle.
... In a snowy area (for heat pump-type systems)
Install the outdoor unit on a raised platform that is higher then
drifting snow. Provide snow vents.
When connecting refrigerant tubing
2

Page
1. SPECIFICATIONS 4
1-1 Unit specifications 4
1-2 Major Component specifications 7
1-3 Other Component specifications 10
1-4 Indoor Fan Performance 11
2. DIMENSIONAL DATA 12
3. ELECTRICAL DATA 14
3-1 Electric Wiring Diagram 14
3-2 Control PCB switches and functions 15
4. FUNCTION 16
4-1 Room Temperature Control 16
4-2 Automatic control for heating and cooling 17
5. REPLACING PCB 18
5-1 Replacing PCB 18
5-2 How to replace PCB 19
5-3 How to replace EEPROM with EEPROM included in PCB service pack 20
5-4 Table of setting 22
6. SERVICING AND MAINTENANCE FUNCTIONS 23
6-1 Indoor unit refrigerant noise countermeasures 23
6-2 Outdoor unit noise countermeasures: EEPROM 05 23
7. TROUBLE DIAGNOSIS 24
7-1 Contents of remote controller switch alarm display 24
7-2 Outdoor unit control panel led display 26
7-3 Trouble indications and inspection points 27
7-4 Remote controller servicing functions 29
7-5 Multiset alarm codes 30
7-6 Inspection of parts 53
Table of Contents
3

1. SPECIFICATIONS
1-1 Unit Specifications
ADS22MH - ADS28MH - ADS36MH
Power source
V
olta
g
e ratin
g
Performance
Capacity
Air circulation (High/Med./Low) m³/h
Features
Controls/Temperature controls
Remote Controller (Option) wired
wireless
Fan speed
Air Filter
Sound pressure level (*) high/med/low dB(A)
Refrigerant tubing connections
Refrigerant Narrow tube mm(in.)
tube diameter Wide tube mm(in.)
Refrigerant
Refrigerant control
Dimensions & Wei
g
ht
Dimensions Height mm
Width mm
Depth mm
Package dimensions Height mm
Width mm
Depth mm
Volume m3
Weight Net kg
Shipping kg
DATA SUBJECT TO CHANGE WITHOUT NOTICE
(*) Power noise level measured at operating conditions (5mmH20 external static pressure)
266
Electronic expansion valve
Washable
54/52/49
Flare type
6,35 (1/4)
12,7 (1/2)
R410A
220 - 240V ~ 50Hz
230V
Cooling Heating
See catalogue with the requested matching
600/510/440
Microprocessor/ I.C. thermostat
3 and Auto
REM HW / REM HWSM
REM HL+RIC. A MURO
745
30,0
34
571
0,3
365
1086
852
4

AD45MHG - ADS56MH
Power source
V
olta
g
e ratin
g
Performance
Capacity
Air circulation (High/Med./Low) m³/h
Features
Controls/Temperature controls
Remote Controller (Option) wired
wireless
Fan speed
Air Filter
Sound pressure level (*) high/med/low dB(A)
Refrigerant tubing connections
Refrigerant Narrow tube mm(in.)
tube diameter Wide tube mm(in.)
Refrigerant
Refrigerant control
Dimensions & Wei
g
ht
Dimensions Height mm
Width mm
Depth mm
Package dimensions Height mm
Width mm
Depth mm
Volume m3
Weight Net kg
Shipping kg
DATA SUBJECT TO CHANGE WITHOUT NOTICE
Flare type
39
365
745
1292
0,35
35
1058
571
220 - 240V ~ 50Hz
230V
Cooling Heating
See catalogue with the requested matching
Microprocessor/ I.C. thermostat
875/600/400
REM HL+RIC. A MURO
266
REM HW / REM HWSM
Washable
6,35 (1/4)
R410A
12,7 (1/2)
3 and Auto
54/47/42
Electronic expansion valve
5

AD64MHG
Power source
V
olta
g
e ratin
g
Performance
Capacity
Air circulation (High/Med./Low) m³/h
Features
Controls/Temperature controls
Remote Controller (Option) wired
wireless
Fan speed
Air Filter
Sound pressure level (*) high/med/low dB(A)
Refrigerant tubing connections
Refrigerant Narrow tube mm(in.)
tube diameter Wide tube mm(in.)
Refrigerant
Refrigerant control
Dimensions & Wei
g
ht
Dimensions Height mm
Width mm
Depth mm
Package dimensions Height mm
Width mm
Depth mm
Volume m3
Weight Net kg
Shipping kg
DATA SUBJECT TO CHANGE WITHOUT NOTICE
3 and Auto
57/49/46
Electronic expansion valve
Washable
9,52 (3/8)
R410A
15,88 (5/8)
See catalogue with the requested matching
Microprocessor/ I.C. thermostat
1000/700/600
REM HL+RIC. A MURO
REM HW / REM HWSM
220 - 240V ~ 50Hz
230V
Cooling Heating
Flare type
39
365
745
1292
0,35
35
1058
571
266
6

1-2 Major Component Specifications
ADS22MH - ADS28MH - ADS36MH
Controller PCB
Part No.
Controls
Fan & Fan Motor
Type
Q'ty ……. Dia. and lenght mm
Fan motor model…Q'ty
No. Of poles…rpm (230 V, High)
Running Amps A
Power input W
Coil resistance (Ambient temp. 20 °C )
Ω
BLU-BRN: 95
BRN-BLK: 37
BLK-GRY: 15
GRY-VLT: 15
WLT-RED: 30
RED-YEL: 101
Safety devices Type
Operating temp. Open °C
Run capacitor µF
VAC
Electronic expansion valve
Coil
Valve body
Heat Exch. Coil
Coil
Rows
Fin pitch mm
face area m2
DATA SUBJECT TO CHANGE WITHOUT NOTICE
0,45
110
Centrifugal fan
3RGB-CO-45-30 5V/1….1
4 … 1060
2…. Ø 160 / L 240
UKV-18D31
1,8
Internal thermal protector - 7AM 037 A 5
150 ± 5K
450
UKV-U030E
Microprocessor
CR-CRP50A-B
0,126
Aluminium plate fin / Copper tube
1,6
2
7

AD45MHG - ADS56MH
Controller PCB
Part No.
Controls
Fan & Fan Motor
Type
Q'ty ……. Dia. and lenght mm
Fan motor model…Q'ty
No. Of poles…rpm (230 V, High)
Running Amps A
Power input W
Coil resistance (Ambient temp. 20 °C )
Ω
BLU-BRN: 68
BRN-BLK: 9
BLK-GRY: 36
GRY-VLT: 18
VLT-RED: 18
BRN-YEL: 105
Safety devices Type
Operating temp. Open °C
Close °C
Run capacitor µF
VAC
Electronic expansion valve
Coil
Valve body
Heat Exch. Coil
Coil
Rows
Fin pitch mm
face area m2
DATA SUBJECT TO CHANGE WITHOUT NOTICE
UKV-25D32
0,168
1,6
3
Aluminium plate fin / Copper tube
2,0
450
CR-CRP50A-B
Centrifugal fan
UKV-U030E
Microprocessor
2…. Ø 160 / L 240
3FGB-CO-65-38 5V/1….1
4 … 1106
0,6
138
Internal thermal protector - 7AM 037 A 5
150 ± 5K
8

AD64MHG
Controller PCB
Part No.
Controls
Fan & Fan Motor
Type
Q'ty ……. Dia. and lenght mm
Fan motor model…Q'ty
No. Of poles…rpm (230 V, High)
Running Amps A
Power input W
Coil resistance (Ambient temp. 20 °C )
Ω
BLU-BRN: 68
BRN-BLK: 9
BLK-GRY: 36
GRY-VLT: 18
VLT-RED: 18
BRN-YEL: 105
Safety devices Type
Operating temp. Open °C
Close °C
Run capacitor µF
VAC
Electronic expansion valve
Coil
Valve body
Heat Exch. Coil
Coil
Rows
Fin pitch mm
face area m2
DATA SUBJECT TO CHANGE WITHOUT NOTICE
UKV-U030E
Microprocessor
2…. Ø 160 / L 240
3FGB-CO-65-38 5V/1….1
4 … 1161
0,57
136
Internal thermal protector - 7AM 037 A 5
150 ± 5K
CR-CRP50A-B
Centrifugal fan
3
450
UKV-25D32
0,168
1,6
3
Aluminium plate fin / Copper tube
9

1-3 Other Component Specifications
Trasformer
Rating Primary
Secondary 1
Secondary 2
Secondary 3
Thermal cut-off temp.
Thermistor
(
Coil sensor E1, E2
)
Resistance k
Ω
Thermistor
(
Coil sensor E3
)
Resistance k
Ω
Thermistor
(
Room sensor TA, TF/BL
)
Resistance k
Ω
Drain pump
Model
Rating Voltage
Input
Flow rate
Safet
y
float switch
Model
Contact rating
0,4 l/min
BI 1300 2725
230V AC/DC - 0,5A
PC 309564003
220/240V - 50Hz
14W
ATR-IIJ225A
VAC 230V, 50Hz
AC 20V - 0.2A
AC 14V - 0.3A
PBC-41E-S26
AC 10,2V - 1.4A
136°C
0 °C 15,0 ± 5%
PBC-41E-S42-2
0 °C 15,0 ± 4,42%
25 °C 5,0 ± 4%
DHKTEC-35-S85N
10
Other manuals for ADS22MH
1
This manual suits for next models
5
Table of contents
Other Argo Air Conditioner manuals

Argo
Argo AUG38PCLI Manual

Argo
Argo AWIAS12DC User manual

Argo
Argo ADIAS19DC User manual

Argo
Argo SDIAS8DC User manual

Argo
Argo POLIFEMO CLASS White User manual

Argo
Argo HLA User manual

Argo
Argo ABDGI 20 HW User manual

Argo
Argo AFSI ECO 120HL UI User manual

Argo
Argo X3MI ECO 61SH User manual

Argo
Argo X3 ECO PLUS Operating manual
Popular Air Conditioner manuals by other brands

Fujitsu
Fujitsu Inverter ASBA30JFC operating manual

Toshiba
Toshiba RAS-M10SMUV-E installation manual

Daikin
Daikin FXLQ20MAVE Operation manual

Hitachi
Hitachi RAS-E24CAK instruction manual

CIAT
CIAT Magister 2 Series Installation, Operation, Commissioning, Maintenance

Bestron
Bestron AAC6000 instruction manual