AUTOMATIC CLOSURE: THE GATE AUTOMATICALLY CLOSES AFTER THE SET PAUSE TIME.
• DURING CLOSING, A START OR PEDESTRIAN COMMAND INVERTS THE GATE MOVEMENT.
• DURING OPENING, A START OR PEDESTRIAN COMMAND STOPS THE GATE MOVEMENT.
COMMUNITY PLUS AUTOMATIC CLOSURE: THE GATE AUTOMATICALLY CLOSES AFTER THE SET PAUSE TIME.
• DURING CLOSING, A START OR PEDESTRIAN COMMAND INVERTS THE GATE MOVEMENT.
• DURING OPENING, A START OR PEDESTRIAN COMMAND IS IGNORED.
STEP-BY-STEP: THE GATE STAYS OPEN AT THE END OF THE OPENING PHASE.
• DURING CLOSING AND OPENING, A START OR PEDESTRIAN COMMAND STOPS THE GATE MOVEMENT.
STEP-BY-STEP PLUS AUTOMATIC CLOSURE: THE GATE AUTOMATICALLY CLOSES AFTER THE SET PAUSE TIME.
• DURING CLOSING AND OPENING, A START OR PEDESTRIAN COMMAND STOPS THE GATE MOVEMENT.
OBSTACLE SENSOR: IF THE CONTROL BOARD DETECTS AN OBSTACLE IT INVERTS THE GATE MOVEMENT OR ENDS THE WORKING PHASE. IT
INVERTS THE GATE MOVEMENT IF IT’S THE FIRST OBSTACLE DETECTION IN THE CURRENT WORKING CYCLE (OPENING/CLOSURE). OTHERWISE,
IT ENDS THE WORKING PHASE SO TO FIND THE FULLY OPEN/CLOSED GATE POSITION AND RESTORE THE STANDARD GATE FUNCTIONING.
SLOW DOWN: THE GATE SLOWS DOWN FOR THE SET SLOW DOWN TIME AT THE END OF THE OPENING AND CLOSING PHASES. DURING THE SLOW
DOWN PHASE THE MOTOR WORKS AT ITS MAX POWER.
PEDESTRIAN WORKING TIME: THE GATE OPENS AND CLOSES FOR THE SET PEDESTRIAN WORKING TIME.
SOFT START: THE MOTOR POWER INCREASES GRADUALLY TILL IT REACHES ITS MAX VALUE.
TESTS: THE CORRECT FUNCTIONING OF MOTOR AND PHOTOCELLS ARE CHECKED BEFORE ANY GATE MOVEMENT. IF ONE OF THE TWO TESTS
FAILS THE GATE DOES NOT MOVE. THE LEDS ON THE BOARD INDICATES THE TYPE OF FAILURE. THE MOTOR TEST FAILS WHEN THE MOTOR IS IN
TERMAL PROTECTION OR THERE IS A CONNECTION ERROR. THE PHOTOCELLS TEST FAILS IF TRANSMITTER AND RECEIVER ARE NOT PROPERLY
ALIGNED, IF THERE ARE INSTALLATION ERRORS, OR IF THE PHOTOCELLS ARE DAMAGED.
DISABLE NOT WIRED N.C. INPUTS: DISABLE ALL THE NOT WIRED N.C. INPUTS. IF LATER, A N.C. INPUT IS WIRED, THE BOARD WILL
AUTOMATICALLY ENABLE IT.
MOTOR BREAK: THE BOARD AUTOMATICALLY SLOWS DOWN THE MOTOR IF THE GATE REACHES THE LIMIT SWITCH WITHOUT THE GATE
SLOWING DOWN, PREVENTING MOTOR DAMAGE.
FAST CLOSURE: THE GATE STARTS THE CLOSING PHASE 3 SEC AFTER THE EXTERNAL PHOTOCELLS HAVE BEEN ACTIVATED. THIS FUNCTION
WORKS ONLY ONCE PER WORKING CYCLE AND ONLY IF THE GATE HAS NOT BEEN STOPPED DURING OPENING OR CLOSING.
OIL RECIRCULATION / COLD CLIMATE MODE: THE MOTOR IS ACTIVATED AT THE MINIMUM POWER FOR 1 MIN EVERY 10 MIN WHEN THE GATE IS
FULLY OPEN/CLOSED, IF MORE THAN 20 MIN LASTED FROM LAST GATE MOVEMENT.
SUGGESTIONS
THE RADIO CASE CAN BE
INSTALLED IN COMBINATION
WITH THE FLASHING LAMP ONE UP.
THE RADIO
MODULE
HOUSED INSIDE
THE RADIO CASE
(RANPC5T).
TO INCREASE THE SIGNAL RANGE DISCONNECT THE RADIO MODULE FROM THE INTERNAL RECEIVER
POSITION AND WIRE IT ON THE TERMINAL BLOCK EXTERNAL RECEIVER POSITION. IF AVAILABLE, WE
SUGGEST YOU USE THE RADIO CASE (CODE RANPC5T).
1. RADIO MODULE CONNECTED IN
INTERNALRECEIVER POSITION
(DEFAULT CONFIGURATION).
2. DISCONNECT THE RADIO
MODULE FROMTHE INTERNAL
RECEIVER POSITION.
3. WIRE THE RADIO MODULE ON THE
TERMINAL BLOCK EXTERNAL RECEIVER
POSITION.
3. WIRE THE RADIO MODULE
ON THE TERMINAL
BLOCK EXTERNAL
RECEIVER
POSITION.
FLASHING LAMP
24 VAC / MAX 5 W
EXTERNAL PHOTOCELLS
CONNECT TO TERMINAL 3.
DURING CLOSING INVERT
THE MOVEMENT.
INTERNAL PHOTOCELLS
CONNECT TO TERMINAL 4.
DURING OPENING INVERT
THE GATE MOVEMENT FOR
2 SECONDS THEN STOP THE
GATE.
ANTENNA
WITH RADIO
CASE
MOTOR
TYPICAL INSTALLATION