Takex FS-1000E User manual

InstructionManual
FS-1000E
FLAME SENSOR
We appreciate your purchase of TAKEX ame sensor.
Please read this instruction manual carefully for correct and effective use.
This sensor is designed to detect ames and to initiate an alarm, it is not a re-preventing device.
TAKEX is not responsible for damage, injury or losses caused by accident, theft, Acts of God (Including inductive surge by lightning), abuse,
misuse, abnormal usage, faulty installation or improper maintenance.
This sensor detects Ultraviolet rays in the ames and initiates an alarm.
It does not detect smoke, heat.
1PARTS DESCRIPTION
PRODUCT DESCRIPTION
Wiring hole
Detection window
Wiring hole
Wiring hole
Battery connector
Front mark
Battery cover
Buzzer (Built-in)
Battery case for type-AA
(1 piece)
Sensor locking screw
3×6 (1 piece)
Tapping screw
4×25 (2 pcs.)
φ
φ
LED Mode selector
Terminals
Locking screw hole
Release lever
Knockout
【BASE UNIT】
【SENSOR UNIT】
■ACCESSORY
Flame sensor FS-1000E is designed to detect ultraviolet rays contained in ames, and to initiate an alarm.
This sensor can be operated for 2years with popular type-AA alkaline battery 2 pcs.
Also, by wiring, external power supply (9V DC〜30V DC) is available.
The equipped output terminal enables remote control of other warning devices, and system operation with a
control panel.
Easy separation of the sensor unit and the base unit is very useful for simplifying installation and maintenance.
※Type-AA battery is not included

This sensor is designed to detect ultraviolet rays contained in
ames, and to issue a signal.
This unit is neither re detector nor heat detector nor smoke
detector.
TAKEX is not responsible for damage, injury or losses by re,
accident, calamity, Acts of God (including inductive surge by
lightning), abuse, misuse, abnormal usage, faulty installation or
improper maintenance.
◎Carefully select the installation site and set up the sensor to avoid dead spots.
◎Do not install in the following places.
Product classification
●When an strong impact is given to the sensor, it may cause
damage, malfunction or less performance.
Do not handle in a rough manner.
●Intense ames such as gas explosion's may damage the
sensor, and there may be no detection.
Others
This sensor detects ultraviolet rays contained in ames.
Therefore, this sensor may detect other sources of ultraviolet rays.
This sensor does not detect burning objects which are smoldering.
Objects to be detected
2ATTENTION
3DO'S AND DON'T'S
Do not install in a site
which is subject to direct or
reecting sunlight and rain.
(This sensor is for indoor
use only)
Do not install in high
humid place such as a
bathroom.
Do not install in a site
where re (ame) is usually
used such as a kitchen.
Do not install in front of the
object that intercepts light.
(including glass and trans-
parent resin etc.)
●Do not install in a site where the temperature falls to less
than +14°F (-10°C) or rises more than +140°F (+60°C).
●Do not install the sensor nearby the possible cause of false
alarm. (see section 2)
●Do not give an impact to the sensor. it may cause damage,
malfunction and less performance to the sensor.
●Do not put water on the sensor, or leave the sensor in a humid
place. it may cause malfunction.
●Only type-AA Alkaline battery (2 pcs.) can be used.
Do not use manganese battery because of its short life.
●When low battery alarm is initiated, exchange the battery
immediately. If not, the sensor may not work.
●This sensor's alarm action is 10 sec. offdelay action.
By detecting a ame, the alarm will be initiated after the set
time of timer passed.
The alarm action is continued during the re, and stopped 10
sec. later after the extinction.
(Alarm, LED, external output)
Possible cause of false alarm
Do not install the sensor nearby the followings. Flames which can not be detected.
●Halogen lamp
●Electric discharging lamp such as mercury lamp
●Electric sterilizer lamp
●Spark from welding
●Electric spark (caused by motor, pantograph)
●Sunlight
●Lightning discharge
●High voltage electric field
●All objects which emit ultraviolet rays
●Flames through glass or transparent resin
●Lit portion of cigarette
●Burning charcoal or briquet
●Electric stove
●Smoldering object
● ● ●●

Battery
*Keep the correct polarity
*Take care not
to catch the
wire between
terminal and
battery.
Battery case - Optional
(2)
(2)
Locate the installation site.
(Ref : 3, DO'S AND DON'T'S and
7, DETECTION AREA)
Slide the release lever to detach
the sensor unit.
Detach the battery cover from the back side of
sensor unit with ngers.
Put Type-AA batteries into battery case with the
correct polarity.
Plug the connector of battery case into the main
body and conrm the warm-up sound.
Put wire rst and the battery case next, into the
main body.
Connect wire to terminals of
the base.
(Ref : 4, WIRING)
Detach the battery cover from
the back side of sensor unit
with ngers in order to keep
the wiring space.
To make the exposed wiring,
break the knockout and insert
wires into the wire lead.
Fix the base with the screws
included.
(Ref : Base installation described
later)
④
①
②
③
Power supply by battery. Power supply by wiring
5INSTALLATION
(1) (1)
(2)
※
(2)
(3)
(4)
(5)
Attach the battery cover so that the marks △on the
cover. Face the marks ▼on the back of the sensor.
knockout
Terminal arrangement
External output
−
How to use Input / Output
4 3 2 15
5 4 3 2 1
ALARM POWER
−S+ − +
9to30V DC
50mA Max
S−
++
(1)(2)
(3)(4)(5)
(1)(2)
(3)(4)(5)
+ S −
(1)(2)
(3)(4)(5)
+ S −
+
+
−
+
S −
−Power
Power
+
+
−
−
Sensor
Sensor
1
Sensor
2
Signalinput
(N.O.)
Controlpanel
・
・
・
・
{
4WIRING Wiring is not necessary if power is supplied from battery and external output is not used.
NPN Open collector output
Action : Detection time +
offdelay 10 sec.
(N.O.)
Capacity : 30V DC 50mA
●Single wire (0.14〜1.5mm2) and twisted wire (0.14〜1.0mm2)
can be used for the terminals.
●When power cable is wired, remove battery cover to keep
wiring space.
①Power input (terminal (1), (2))
●Do not use with battery at same time.
●Do not reverse the polarity.
②External output
The following either (1) or (2) output is available by connecting
open collector output terminal and either + or - of extenal
output terminals.
1. Signal output (terminal (4), (5))
N/O signal is issued for a control panel etc.
When more than 2 sensors are connected on 1 circuit, make
wiring in parallel.
2. Output with voltage (terminal (3), (4))
This output is not available with battery use at the same time.
Alarm signal is switched to power input with voltage. (Output
voltage is decreased by approx. 1V compared with input
voltage.) Within the capacity of contact output, alarm devices
(power consumption within 50mA) can be operated by this
output. This is useful for remote control of warning devices etc.
●Example of basic connection
Warning devices (buzzer, bell, etc.)
The warning devices should be within the capacity
of contact output and adopted for power supply.
(Remortcontrolofwarningdevices)---terminal(3),(4)
(Remotecontrolbycontrolpanel)---terminal(4),(5)
Power input (with polarity)
Power output
S
(1)
(5)
(4)
54
S
-
+
ALARM
2 1
+
-
POWER
3
30VDC50mA
OPEN
COLLECTOR
9to30VDC50mA
(non-polarity)
DANGER
Dontusethebothofexternal
powersupplyandbatteryat
thesametime.
Makewiringaccordingto
instructionmanual.
33A554-D

Mode selector
1 2 3 4
Detection Sensitivity
Alarm Sound Detection timer
1
(Factory set : ON)
Detection Sensitivity
SET
L (50%)
SET
H (100%)
(Factory set : H)
2
SET Timer
(Factory set : 1 sec.)
An alarm output occurs when the ame continues for set time of
detection timer or longer.
Detection timer
3 4
This product alarms only by detecting a ame
continuing for the set time of detection timer.
(1sec., 6secs., 15secs., 30secs.)
When the ame continues further, the alarm and
external output (when wired) are also continued
10sec. after the ame goes out, the alarm stops and
the sensor goes back to armed mode.
Installation hole
approx. 5mm
Marking Installation hole
Alarm (Basic action)
This product is equipped with installation holes (pitch 3.29" or 83.5mm) to make
installation easy and the sensor's direction adjustable.
Buzzer : Sounds intermittently every 0.2sec.
LED : Flashing every 0.2sec.
〔
〔
Low battery alarm will be initiated when power is
supplied from a battery.
When low battery alarm sounds, change the battery for
new one. (The sensor stops its operation 2 weeks after
the low battery alarm starts.)
Within 30sec. after the power is turned off, power on
notice is not issued even if the power is supplied
again.
Low battery alarm
Buzzer : Sounds intermittently every 5sec.
LED : Flashing every 5sec.
〔
〔
〔
〔
Power on notice will sound when the power is turned on.
When voltage is low, power on notice will not be
heard. Check the power supply (battery).
Power on notice
(1) Operation
When detection sensitivity is set "L", the detection distance is
50% shorter than when it is set "H".
When operation is unstable on "H" setting, select "L".
For semi-outdoor installation, "L" setting is recommended.
[Installation of base]
Check operation and area.
(Ref : Operation check)
When sensor unit is detached,
wrap it in palm and slide
release lever.
To lock sensor unit, insert
sensor locking screw into
locking screw hole and
tighten it.
Set alarming sound, detection
sensitivity and detection timer.
(Ref : 6-(2) Function setting)
Attach the sensor unit to base
unit.
Turn front marks of base
unit and sensor unit to point
in the same direction.
Insert sensor unit into base
unit.
Push sensor unit until
release lever is locked. Sensor locking screw
×
×
6OPERATION AND FUNCTION
Place the base on the site and
mark ×on 2 points 180°apart.
Insert the 2 pcs. of tapping
screws (accessory) leaving 5mm
exposed from the surface.
Adjust the sensor's direction
by turning the base.
(4) Tighten the screws.
●Installation hole
Buzzer : Sounds intermittently 3 times.
(1) (2) (3)
⑤⑦
⑧
⑨
⑥
(1)
(2)
(3)
※
※
※
1 sec.
6 sec.
15 sec.
30 sec.
Detection sensitivity is selectable, H or L.
1234
FS-1000E is equipped with 3 functions which can be
used according to the application or environment.
Mode setting will be done by mode selector (dip
switch) in accordance with mode setting chart on
the back side of sensor unit.
(2) Mode setting
Alarm sound (buzzer)
Buzzer can be off by mode selector No.1,
SET
ON
OFF
When the ultraviolet rays of a ame is weak (it is related to size
of ame and distance to sensor), alarm initiation may be delayed
beyond the set time.
The ultraviolet rays are not visible, and may be detected from
unexpected object.
When the sensor's operation is not stable (it detects something
but not a ame) and its cause can not be identied, set detection
time longer by one step and see the course.
※
※
Application and installation
●For the quick detection of the flame of lighter
/ match at no smoking zone.
●Fire detection
●In case of uncertain operation on the above
●Fire detection in an area that may be
influenced by uncertain external light
※When the setting is OFF Buzzer of “Low battery alarm” and
“powr on notic” are also off.

When the sensor is soiled, clean the cover with a soft cloth moistened with a small amount of cleaning solution.
Check operation once a week.
Do not fail to check oparation whenever a furniture in the place is moved.
When low battery alarm sounds, change battery for new one immediately.
If it is left, it could cause inactiveness of the sensor.
Maintenance
1. Turn power on, and conrm power on notice
sounds.
(In case of battery use, conrm power on
notice when connecting the battery.)
2. Ignite a lighter etc. within detection area for
more than the set time.
3.
After the set time, buzzer sounds intermittently
and LED ashes. (Alarm action)
4. 10sec. after the ame goes off, the above
alarm action ends.
Do not use a lighter in no fire
zone because it is dangerous.
In such case, operation test
have to be done in other place
with sensor only.
Detection area spreads out in
front of the sensor at approx.
120°conically.
The size of the detection area
is in proportion to the size of
the ame.
The size of the detection area
increases with an increase in
ame size and duration.
When the object of detection is from a source such as a lighter,
conrm detection throughout the area.
Use the optional BCW-401 universal bracket when area adjustment
is required.
Approx.120°
10' (3m) 10' (3m)
20' (6m) 20' (6m)
30' (9m) 30' (9m)
33' (10m) 33' (10m)
7DETECTION AREA
9TROUBLESHOOTING
8OPERATION CHECK
20'
(6m)
20'
(6m)
10'
(3m)
10'
(3m)
10'
(3m)
10'
(3m)
16'
(5m)
16'
(5m)
Solve possible problems according to the following table .
If normal operations can not be restored by these corrective actios, contact either
the dealer from whom you bought the unit or TAKEX.
Trouble
Completely inactive
Sometimes inactive
Activated without
flame
The alarm LED
flashes and buzzer
sounds (5sec./once)
The alarm LED and
buzzer works but the
connected devices are
inactive (when wired)
The alarm LED
lights on but buzzer
does not sound
Check
●No battery connected
●Low battery
●No power supply (Broken wire or improper wire)
●Low voltage (When power supply wired)
●Sensor inside is wet by condensation etc.
●Interrupting rays objects in front of detection area
(Glass, transparent resin are interrupting rays objects)
●Improper area setting
●Low voltage
●Low battery
●Detection window is soiled with dust
●Large electrical noise source such as a redio station or
high-voltage wire nearby
●Unexpected ultraviolet rays nearby (Ref : 2, ATTENTION)
●Sensor inside is wet by condensation etc.
●Low battery
(Low battery alarm)
●Buzzer "OFF"
●Poor contact output connection or broken wire
●The connected unit's trouble
●Relocate the sensor to appropriate position
●Use a BCW-401 (optional) and adjust the
angle setting
●Remove tha dust and soil
●Correct power supply
●Change battery
●Relocate the sensor
●Remove the origin of the ultraviolet rays,
interrupt ultraviolet rays, or relocate the sensor
●
Dry out sensor inside, and remove the cause of wet
●Change battery immediately
●Buzzer "ON"
●Check the wiring or connection
●Check the connected unit
●Connect battery
●Change battery
●Correct power supply or replace broken
wire
●Dry out sensor inside, and remove the
cause of the wet
●Remove the interrupting rays object
Corrective action
Side view : Ceiling / wall mount
Front view : Ceiling mount
Top view : Wall mount
●
●
●
〔
〔
When external output is used by wiring,
a continuous output is issued during the
above 3. and 4. alarm action.
Conrm the operation of the connected
devices.
Detection area
Factory default setting
Detection timer : 1 sec.
Detection sensitivity : H (100%)
Detection object : Gas flame of lighter [2.75" (7cm)]
●
1)
2)
3)

No.05-785 1406
In Japan
Takex America Inc.
4/15 Howleys Road, Notting Hill,
VIC, 3168
Tel : +61 (03) 9544-2477
Fax : +61 (03) 9543-2342
Takenaka Engineering Co., Ltd.
83-1, Gojo-sotokan, Higashino,
Yamashina-ku, Kyoto 607-8156, Japan
Tel : 81-75-501-6651
Fax : 81-75-593-3816
http : // www. takex-eng. co. jp /
Takex America Inc.
3350, Montgomery Drive
Sant Clara, CA 95054, U.S.A.
Tel : 408-747-0100
Fax : 408-734-1100
http : // www. takex. com
Takex Europe Ltd.
Takex House, Aviary Court, Wade Road,
Basingstoke, Hampshire. RG24 8PE, U.K.
Tel : (+44)01256-475555
Fax : (+44)01256-466268
http : // www. takexeurope. com
In the U.S. In the U.K.
In Australia
11 EXTERNAL DIMENSIONS
10 SPECIFICATIONS
■OPTION
◎Ceiling/wall mount attachment
(variable attachment)
〔BCW-401〕
φ4.72" (φ120mm)
φ3.88" (φ98.5mm)
φ3.29"
(φ83.5mm)
φ0.35"
(φ9mm)
2.63"
(66.7mm)
5-φ0.17"
(5-φ4.2mm)
R0.59"
(R15mm)
35°
35°
35°
35°
0.17"
(4.2mm)
Sensor unit
Release lever
Buzzer
(built in)
Locking
screw hole
LED (Red)
Detection window
Wiring hole
MOUNT & WIRING HOLE
Base unit
1.58" (40mm)
1.34"
(34mm)
0.41"
(10.5mm)
0.31" (8mm)
Model No.
Detection system
Detection distance
Sensitivity adjustment
Power supply
Power consumption
LED
Buzzer
External output
Wiring
Ambient temp.
renge
Installation
Weight
External dimensions
Appearance
Accessories
Option
FS-1000E
Ultraviolet rays detection
(Detected wave length 180 to 260nm)
33ft. (10m) [2.75" (7cm) lighter flame, in front]
Detection sensitivity (H [100%], L [50%])
Detection timer (1sec., 6sec., 15sec., 30sec.)
●Type-AA alkaline battery(not included)
●
External power supply 9 to 30V DC with polarity
Stand by :
50μA Max. using battery power supply
5mA Max. using external power supply
Alarm : 50mA Max. when buzzer sounds
(Excluding the current draw for power
output through terminal (3) & (4))
Indication : Red LED
Alarm : Flashing every 0.2sec. during off-delay 10sec.
Low battery : Light on 0.1sec. every approx. 5sec.
Alarm : Sounds intermittently every 0.2sec. during off-delay 10sec.
Low battery : Sounds 0.1sec. intermittently every approx. 5sec.
Volume : 80dB or more 3.3ft. (1m) ahead
(Silent setting is available by cutting internal jumper line)
NPN open collector output
(Useful as an output with voltage when extrnal power is used)
30V DC 50mA offdelay 10sec. continuous output
Terminals
+14°F to +140°F (-10°C to +60°C) without condensation
Battry performance may decrease under +32°F (0°C)
or beyond +104°F (+40°C)
Indoor (ceiling or wall mount)
Approx. 7oz (200g)
including battery (accessory) 1.8oz (50g)
φ4.72" (120mm) × H 1.58" (40mm)
ABS resin (white)
●Battery case for type-3 × 2pcs, × 1
●Type-AA alkaline battery LR-6 × 2
●Sensor locking screw φ3 × 6, × 1
●Tapping screw φ4 × 25, × 2
●Ceiling/wall mount attachment BCW-401
(variable attachment)
detector
elements
alcohol
When detector elements are
stained, spray alcohol to the
elements and remove the stain.
Do not use such chemicals as
mild detergent, thinner or benzine
to clean the detector elements.
When housing is stained, clean it
with a soft cloth.
Limited Warranty :
TAKEX products are warranted to be free from defects in material and
workmanship for 12 months from original date of shipment. Our warranty
does not cover damage or failure caused by Acts of God (including inductive
surge by lightning), abuse, misuse, abnormal usage, faulty installation,
improper maintenance or any repairs other than those provided by TAKEX.
All implied warranties with respect to TAKEX, including implied warranties
for merchantability and implied warranties for tness, are limited in duration
to 12 months from original date of shipment. During the Warranty Period,
TAKEX will repair or replace, at its sole option, free of charge, any defective
parts returned prepaid. Please provide the model number of the products,
original date of shipment and nature of difculty being experienced. There will
be charges rendered for product repairs made after our Warranty period has
expired.
Table of contents
Other Takex Accessories manuals

Takex
Takex PB-IN-50HFA User manual

Takex
Takex F71R User manual

Takex
Takex PXB-100ATC User manual

Takex
Takex PB-30TK User manual

Takex
Takex PR-11BE User manual

Takex
Takex PA-4810E User manual

Takex
Takex PB- 50FA User manual

Takex
Takex PA-470L User manual

Takex
Takex F71 Series User manual

Takex
Takex PA-450EA User manual

Takex
Takex TX-114TR User manual

Takex
Takex ASW-SG85F User manual

Takex
Takex PXB-50HF-KH User manual

Takex
Takex TXF-20TDM User manual

Takex
Takex TXF-125 Series User manual

Takex
Takex GS-1100E User manual

Takex
Takex TX-124R User manual

Takex
Takex MS-12TE User manual

Takex
Takex PS-520E User manual

Takex
Takex PR-5B User manual