Sinclair SCMI-01 User manual

SCMI-01
USBCommunicator
USER'S MANUAL
EN


1. Introduction
USBCommunicator allows easier and faster setting of SCMI-01 and is available on mini CD or on our
website www.sinclair-solutions.com. USBC software can also display current setting of SCMI-01
module.
2. Preparation
Mini USB cable is needed for communication between computer and SCMI-01 module. This cable is
not included in standard package.
Fig 1: Mini USB cable Fig 2: Front panel of module
Connect the SCMI-01 module with computer using mini USB cable (Fig 1). Display of module will turn
on after successful connection.
3. SCMI-01 setting via USBCommunicator
Application bookmark
Here you can find the information about this software (“About”), select the language (“Language”)
and you can also close whole application (“Close”).
Fig 3: „Application“ bookmark

Device bookmark
This option shows „Supported devices” interface. To set SCMI-01 module, choose SCMI Sinclair driver
option. USBC software will automatically detect SCMI-01 device after you connect it to computer.
Fig 4: „Device“ bookmark

The setting options in USBC software are the same as options in SCMI-01 module itself. You can find
detailed information about each feature in user manual for SCMI-01 module.
Fig 5: SCMI Sinclair driver interface

Main menu Submenu/Option Range Default Note:
Target value Setting of desired temperature; this menu is not accessible in the slave
mode.
-10 to +60 +10,0°C p. 7
Function Operated Slave unit mode. The module is controlled by an external voltage 0-
10V.
Operated p. 8
Reg. P Autonomous pressure (evaporation temperature) control mode p. 9
Reg. T* Autonomous temperature control mode for cooling p. 10
Reg. T+ Autonomous temperature control mode for heating
Defrost Mode Off Defrosting of indoor unit evaporator is not in use Off p. 11
External Defrosting with external support (heating cable etc.)
Reverse Defrosting by switching from cooling to heating
mode.
Period Setting the minimum time period between defrosting
cycles
0.1 to 99.9 1 hour p. 12
Length Setting the maximum duration of defrosting 1.0 to 60.0 10 min
Start Setting the temperature to start defrosting -20 to +5,0 -5,0°C p. 13
Stop Setting the temperature to stop defrosting +3 to +25.0 +7,0°C
Outputs Relay 1 Function ON/OFF Relay is controlled by On/Off input. On/Off p. 14
Compres. Relay is controlled according to the
compressor
Defrost Relay is controlled according to the
operation (Heat/Cool)
Error Relay is controlled according to the
error state
Heat/Cool Relay is controlled according to the
operation (Heat/Cool)
Limiting Relay to limit the long lasting
compressor load.
Logic Direct Relay switches with direct logic Direct
Inverse Relay switches with inverse logic
Relay 2 Function This setting is the same as setting the Relay 1 Compres.
Logic This setting is the same as setting the Relay 1 Direct
Relay 3 Function This setting is the same as setting the Relay 1 Error
Logic This setting is the same as setting the Relay 1 Direct
DC Vent Fixed Setting the speed and mode (Co, Fa, On) of the
indoor fan
Off p. 15
Auto 1 Fan speed according to compressor speed 1:1
Auto 2 Fan speed of 60-200% of compressor speed
Off Output not used
Reg.cons Time con Setting the time constant of the module. 10 to 999 30 sec. p. 16
Prop.con Setting the proportional constant of the module. 0 to 999 35
Int.cons Setting the integral constant of the module. 0 to 999 0
Der.cons Setting the derivative constant of the module. 0 to 999 60
Display Backlight Setting the LCD backlight. 1 to 16 8 p. 17
Contrast Setting the LCD contrast. 1 to 16 8
Time gap Setting the time period of the operator inactivity 10 to 999 60
Language Setting the language version CZ / EN EN p. 18
Password Enter the password before setting the module. After logging in, you can perform
setting for about 30 minutes. Without knowing the password, you can only adjust the
contrast and backlight brightness of the display.
201201 p. 6
Tab 1: Summary of the module settings
After setting is done, click on “Write” button to save all parameters in module memory.
All saved parameters can be displayed by clicking “Read” button.

4. Language update of SCMI-01 module
Click on “globe” icon in SCMI Sinclair driver interface (as shown in fig 5). In the dialog window
you need to open “languages” folder located in downloaded files/on mini CD and choose desired
language set (XXX.RAW file). Each language set consists of two languages – English and the chosen
one (DE, PL, CZ, HR, HU).
5. Password
You can change or deactivate password via USBC software.

NOTE CONCERNING PROTECTION OF
ENVIRONMENT
This product must not be disposed of via normal household waste after its service life, but must be
taken to a collection station for the recycling of electrical and electronic devices. The symbol on the
product, the operating instructions or the packaging indicate such disposal procedures. The materials
are recyclable in accordance with their respective symbols. By means of re-use, material recycling or
any other form of recycling old appliances you are making an important contribution to the protection
of our environment. Please ask your local council where your nearest disposal station is located.
In case of quality problem or other please contact your local supplier or authorized service center.
Emergency number: 112
PRODUCER
SINCLAIR CORPORATION Ltd.
1-4 Argyll St.
London W1F 7LD
Great Britain
www.sinclair-world.com
This product was
manufactured in Czech Republic (Made in Czech Republic).
REPRESENTATIVE
SINCLAIR EUROPE spol. s r.o.
Purkynova 45
612 00 Brno
Czech Republic
TECHNICAL SUPPORT
NEPA spol. s r.o.
Purkynova 45
612 00 Brno
Czech Republic
Tel.: +420
800 100 285
Fax: +420 541 590 124
www.sinclair-solutions.com
info@sinclair-solutions.com
Table of contents