2.2
Adding A Detector To An Existing RF Interlink Network
At some point, you might want to add another smoke alarm unit to your existing RF interlink
network for additional protection, or to replace an old unit. Follow the steps in the following table.
User Input Detector Response Timeout
Step 1 Press the LINK button twice
on any existing 6000WB (or
6000DCW) unit.
Unit will respond with two quick
flashes every 2 seconds if it is the Coor-
dinator of the Network; three quick
flashes every 2 seconds if it is a RFD in
the Network - Join Mode is open.
Join Mode will timeout
in 15 minutes
Step 2 Power up unit(s) to be added -
by mounting the smoke alarm
onto the RF baseplate. For
previous units that have been
reset, press the LINK button
twice to enter Join Mode.
Red LED flashes three times every 2
seconds to indicate it is configured (as
a RFD) in the network
Join Mode will timeout
in 15 minutes
Step 3 After new unit(s) have joined,
press LINK button twice on
any unit in the network to
close Join Mode.
Red LED on each unit will power off
indicating Standby Mode
Join Mode will timeout
in 15 minutes
Step 4 Follow installation instructions
in Section 4.
User Input Detector Response Timeout
Step 4 Connect each additional smoke
alarm on its RF baseplate.
The Red LED of each unit will initially
flash one second ON and one second
OFF. After each unit joins the network,
its Red LED will flash three times every
2 seconds to show it is now a RFD in
the network.
Join Mode will timeout in 15 minutes
after last unit joins.
Step 5 After all units have joined,
press LINK button twice on the
baseplate.
Red LED on each unit will turn off
indicating Standby Mode
Step 6 Follow installation instructions
in section 4.