Pilz PNOZ X7 User manual

PNOZ X7
Operating Manual-19692-EN-06
}Safety relays

Preface
This document is the original document.
All rights to this documentation are reserved by Pilz GmbH & Co. KG. Copies may be made
for the user's internal purposes. Suggestions and comments for improving this documenta-
tion will be gratefully received.
Source code from third-party manufacturers or open source software has been used for
some components. The relevant licence information is available on the Internet on the Pilz
homepage.
Pilz®, PIT®, PMI®, PNOZ®, Primo®, PSEN®, PSS®, PVIS®, SafetyBUS p®,
SafetyEYE®, SafetyNET p®, the spirit of safety® are registered and protected trademarks
of Pilz GmbH & Co. KG in some countries.
SD means Secure Digital

Contents
Operating Manual PNOZ X7
19692-EN-06 3
Introduction 4
Validity of documentation 4
Using the documentation 4
Definition of symbols 4
Safety 5
Intended use 5
Safety regulations 5
Safety assessment 5
Use of qualified personnel 6
Warranty and liability 6
Disposal 6
For your safety 6
Unit features 7
Safety features 7
Block diagram/terminal configuration 7
Types: AC 7
Type: AC/DC 8
Function Description 9
Operating modes 9
Timing diagram 9
Installation 10
Wiring 10
Preparing for operation 11
Operation 12
Status indicators 13
Faults – Interference 13
Dimensions in mm 13
Technical details 14
Safety characteristic data 26
Supplementary data 26
Service life graph 27
Order reference 27
EC declaration of conformity 28

PNOZ X7
Operating Manual PNOZ X7
19692-EN-06 4
Introduction
Validity of documentation
This documentation is valid for the product PNOZ X7. It is valid until new documentation is
published.
This operating manual explains the function and operation, describes the installation and
provides guidelines on how to connect the product.
Using the documentation
This document is intended for instruction. Only install and commission the product if you
have read and understood this document. The document should be retained for future ref-
erence.
Definition of symbols
Information that is particularly important is identified as follows:
DANGER!
This warning must be heeded! It warns of a hazardous situation that poses
an immediate threat of serious injury and death and indicates preventive
measures that can be taken.
WARNING!
This warning must be heeded! It warns of a hazardous situation that could
lead to serious injury and death and indicates preventive measures that can
be taken.
CAUTION!
This refers to a hazard that can lead to a less serious or minor injury plus
material damage, and also provides information on preventive measures
that can be taken.
NOTICE
This describes a situation in which the product or devices could be dam-
aged and also provides information on preventive measures that can be
taken. It also highlights areas within the text that are of particular import-
ance.

PNOZ X7
Operating Manual PNOZ X7
19692-EN-06 5
INFORMATION
This gives advice on applications and provides information on special fea-
tures.
Safety
Intended use
The safety relay PNOZ X7 provides a safety-related interruption of a safety circuit.
The safety relay meets the requirements of EN 60947-5-1, EN 60204-1 and VDE 0113-1
and may be used in applications with
}E-STOP pushbuttons
}Safety gates
The following is deemed improper use in particular
}Any component, technical or electrical modification to the product,
}Use of the product outside the areas described in this manual,
}Use of the product outside the technical details (see Technical details [ 14]).
NOTICE
EMC-compliant electrical installation
The product is designed for use in an industrial environment. The product
may cause interference if installed in other environments. If installed in other
environments, measures should be taken to comply with the applicable
standards and directives for the respective installation site with regard to in-
terference.
Safety regulations
Safety assessment
Before using a device it is necessary to perform a safety assessment in accordance with
the Machinery Directive.
Functional safety is guaranteed for the product as a single component. However, this does
not guarantee the functional safety of the overall plant/machine. In order to achieve the re-
quired safety level for the overall plant/machine, define the safety requirements for the
plant/machine and then define how these must be implemented from a technical and organ-
isational standpoint.

PNOZ X7
Operating Manual PNOZ X7
19692-EN-06 6
Use of qualified personnel
The products may only be assembled, installed, programmed, commissioned, operated,
maintained and decommissioned by competent persons.
A competent person is a qualified and knowledgeable person who, because of their train-
ing, experience and current professional activity, has the specialist knowledge required. To
be able to inspect, assess and operate devices, systems and machines, the person has to
be informed of the state of the art and the applicable national, European and international
laws, directives and standards.
It is the company’s responsibility only to employ personnel who
}Are familiar with the basic regulations concerning health and safety / accident preven-
tion,
}Have read and understood the information provided in the section entitled Safety
}Have a good knowledge of the generic and specialist standards applicable to the spe-
cific application.
Warranty and liability
All claims to warranty and liability will be rendered invalid if
}The product was used contrary to the purpose for which it is intended,
}Damage can be attributed to not having followed the guidelines in the manual,
}Operating personnel are not suitably qualified,
}Any type of modification has been made (e.g. exchanging components on the PCB
boards, soldering work etc.).
Disposal
}In safety-related applications, please comply with the mission time TM in the safety-re-
lated characteristic data.
}When decommissioning, please comply with local regulations regarding the disposal of
electronic devices (e.g. Electrical and Electronic Equipment Act).
For your safety
The unit meets all the necessary conditions for safe operation. However, please note the
following:
}Note for overvoltage category III: If voltages higher than low voltage (>50 VAC or >120
VDC) are present on the unit, connected control elements and sensors must have a
rated insulation voltage of at least 250 V.

PNOZ X7
Operating Manual PNOZ X7
19692-EN-06 7
Unit features
}Positive-guided relay outputs:
– 2 safety contacts (N/O), instantaneous
}Connection options for:
– E-STOP pushbutton
– Safety gate limit switch
– Start button
}LED display for:
– Supply voltage
– Switch status of the safety contacts
}See order reference for unit types
Safety features
The safety relay meets the following safety requirements:
}The circuit is internally redundant with built-in self-monitoring.
}The safety device remains effective in the case of a component failure.
}The correct opening and closing of the safety device relays is tested automatically in
each on-off cycle.
Block diagram/terminal configuration
Types: AC
}UB: 42 VAC; Order no. 774058
}UB: 48 VAC; Order no. 774049
}UB: 110 VAC; Order no. 774053
}UB: 115 VAC; Order no. 774054
}UB: 120 VAC; Order no. 774055
}UB: 230 VAC; Order no. 774056
}UB: 240 VAC; Order no. 774057

PNOZ X7
Operating Manual PNOZ X7
19692-EN-06 8
*Insulation between the non-marked area and the relay contacts: Basic insulation (over-
voltage category III), Protective separation (overvoltage category II)
Type: AC/DC
}UB: 24 VAC/DC; Order no. 774059
*Insulation between the non-marked area and the relay contacts: Basic insulation (over-
voltage category III), Protective separation (overvoltage category II)

PNOZ X7
Operating Manual PNOZ X7
19692-EN-06 9
Function Description
The safety relay PNOZ X7 provides a safety-oriented interruption of a safety circuit. When
the supply voltage is applied via the E-STOP pushbutton, the “POWER” LED is lit. The unit
is ready for operation when the start circuit and feedback loop Y1-Y2 is closed.
}Input circuit is closed (e.g. E-STOP pushbutton not operated):
– The LED "CH.1/CH.2" will light.
– Safety contacts 13-14 and 23-24 are closed. The unit is active.
}Input circuit is opened (e.g. E-STOP pushbutton operated):
– The LEDs "CH.1" and "CH.2" goes out.
– Safety contacts 13-14 and 23-24 are redundantly opened.
Operating modes
}Single-channel operation: No redundancy in the input circuit, earth faults in the start
and input circuit are detected.
}Automatic start: Unit is active once the input circuit has been closed.
}Manual start: Unit is active once the input circuit and the start circuit are closed.
}Increase in the number of available contacts by connecting contact expander modules
or external contactors/relays.
Timing diagram
[1] [2]
Legend
}Power: Supply voltage
}Start: Start circuit
}Input: Input circuit
}Output safe: Safety contacts
}[1]: Automatic start
}[2]: Manual start
}a: Input circuit closes before start circuit
}b: Start circuit closes before input circuit
}t1: Switch-on delay
}t2: Delay-on de-energisation
}t3: Recovery time

PNOZ X7
Operating Manual PNOZ X7
19692-EN-06 10
Installation
}The unit should be installed in a control cabinet with a protection type of at least IP54.
}Use the notch on the rear of the unit to attach it to a DIN rail (35 mm).
}When installed vertically: Secure the unit by using a fixing element (e.g. retaining
bracket or end angle).
Wiring
Please note:
}Information given in the "Technical details [ 14]" must be followed.
}Calculating the max. cable length Imax in the input circuit on PNOZ X7 24 VAC/DC:
Rlmax
Rl / km
Imax =
Rlmax = max. overall cable resistance (see Technical details [ 14])
Rl/km = cable resistance/km
}Calculating the max. cable length Imax in the input circuit on PNOZ X7 AC units:
C
C
Clmax = max. overall line capacitance (see Technical details [ 14])
Cl/km = line capacitance/km
Stub circuit: The max. permitted cable length Imax depends on the max. overall line ca-
pacitance Clmax (see Technical details [ 14]).
Alternative: Loop circuit: Capacitance is negligible; 1 phase: Max. cable length Imax: 1
km
Stub circuit Loop circuit
Cable length
lmax
lmax
WARNING!
If the max. overall line capacitance is exceeded, the unit will no longer
switch off safely and serious injuries and death may result.
Always comply with the max. overall line capacitance.